SE,SEC,PWD
Office of the Senior Superintending Engineer SOUTHERN ELECTRICAL CIRCLE, 2nd FLOOR, MECHANICAL COMPLEX, BAGUIATI, KOLKATA 700 059.
Set up of Mechanized Laundry within the compound of Naihati State General Hospital, North 24 Parganas - SITC of 1000 KVA Electrical Power Substation including allied Electrical works.
2026_WBPWD_1012233_1
WBPWD/SESEC/eNIT-11/25-26
Open Tender
ELECTRICAL WORKS ORG
Item Rate
120 days
Naihati
As in NIT
4 documents required · 4 mandatory
₹3.3 L
Superintending Engineer SEC PWD
16 Jun 2026
20 Feb 2026
25 Mar 2026
20 Feb 2026
23 Mar 2026
27 Feb 2026
25 Feb 2026
HT Gear: Supply & Delivery of 3 panel metal clad,Indoor type single tier, fully compartmentalized,free standing, floor role type , 26.3 kA for 3 sec,horizontal drawout type 11KV 800A VCB having following Specification:
CIRCUIT BREAKER:- Type : VCB autoreclosing, system voltage :- 11kV, 50 Hz, 3 phase, rated voltage : 11 kV, rated current : 800A in 50 ° C ambient, Short time rating for 3 sec : 26.3 kA, System Ground : Solidly Earthed, Duty Cycle : 0 - 0.3 sec - CO - 3 min - CO, Circuit breaker should withstand 10000 mechanical operation at full load & 100 no. electrical operation at full short circuit current.rated short circuit current.[ Make : Schneider/ Siemens / Energypac]. (Incomming - 1 no., Outgoing - 2 nos.)
BUSBAR:- Rated Current : 800A @ 50°C ambient, Material, Silver Plated /Tined , High conductivity elecrolytic Copper Bus Bar sleeve :Heat Shrinkable PVC Sleeve with joints having full voltage soft PVC shroude Short time rating for 1 sec : 26.3kA…………1 set.
CURRENT TRANSFORMER:- Voltage class: As specified in Circuit breaker ; Type : cast resin type , Dual core , Dual Ratio , Barden :15VA ;. Protection core: 5P20, Metering :0.5 , Short time rating for 1 sec : 26.3kA Ratio :100-5A/1+1 No. (for incoming Breakers) & 50/1-1 (metering for ECBC monitoring)-2 nos. for outgoing Breakers (Make: As per manufacturer's standard).
POTENTIAL TRANSFORMER:- Rated Voltage : Primary - 11000/√3 , Sec -110√3; Type : Cast resin , draw out type, 3- phase , 3-limb complete with HV fuses . PT should be drawnout type and serivce continuously shall be indepandent of Breaker trolly position (Make: As per manufacturer's standard)- 1 set.
RELAYS FOR PROTECTION & CONTROL:- Type : Flush mounted , Drawnout, Numerical and multifuntional (With 3 O/C, 1 E/F & 3 VT I/P), undervoltage , over voltage, CB maintance & Trip circuit supervision, Trip circuit supervision relay -3 set/ inbuilt feature of High Speed Master Trip relay- 3 Set, 8 Window Annunciation Facia . with ACCEPT, RESET & TEST Push Button - 2 Set for Outgoing . Auxillary relay for Transformer faults- VAA33- 2 Set.
METERING:- For Incomer Digital Ammeter, Digital Voltmeter.For Outgoing - Digital Ammeter. Multifunctional Meter Type: Flush mounted , sealed dustproof construction (Front- IP5X, Rear -IP4X), multifunctional Display Parameters: Voltage, Current , PF/Frequency and all energy & power parameters, (Make : As per manufacturer's strandard).......3 set
Testing: Making testing arrangement and submitting the test report for high voltage testing of specified voltage incl. checking & testing of all HT / LT equipments
Transformer: Supply & Delivery of 500KVA Dry type Transformer (Make: ABB / BHEL/ Energypac) Applicable standared IS 11171-1985 /IS 2026 with latest modification (if any) Rating:- 500 KVA, 3 phase, 50Hz, Delta / Star Type:- Cast Resin type (CRT), three phase, copper wound, air cooled dry type. Voltage ratio:- 11000V / 433 Volt Links / Tappings:- Off circuit Links, tapping range +5% to -5% in steps of 2.5% on HV side. Cooling:- Air Natural (AN), Powder Coating, Class of Insulation:- Class F, Temp. rise:- 90° C over ambient of 50°C Arrangement of Neutral :- extra neutral will be brought out Separately with copper stud to facilate earth connection.
Core & Coils:-The core shall be built up with high grade, non-aging, low loss, high permeability, grain oriented, cold-rolled silicon steel laminations especially suitable for core material. The coils shall be manufactured from electrolytic copper conductor & fully insulated for rated voltage, coils shall be resin-molded for both LV & HV with epoxy resin, encapsulated, Class F, naturally cooled (AN). Insulating material shall be of proven design. Coils shall be so insulated that impulse & power frequency voltage stresses are minimum. Coil assembly shall be suitably supported between adjacent sections by insulating spacers & barriers. All leads from the windings to the terminal board & bushings shall be rigidly supported to prevent injury from vibration or short circuit stresses. Guide tube shall be used where practicable.The core and coil assembly shall be securely fixed in position so that no shifting or deformation occurs during movement of transformer or under short circuit stresses. Transformer losses shall be guaranteed as below: Total loss at 50% loading:- 2.8 KW ( Max) & 100% - 7.25 KW ( Max), Impedance:- 5% (Allowable tolerance as per IS),Degree of Protection IP33.
Cable Termination: Terminal arrangement: HV: Cable box suitable for HT Cable 3Cx240sqmm XLPE insulated cable, LV: Cable box for terminating 4 nos. 4Cx300 sqmm XLPE insulated cable. Two nos earthing terminals shall be provided of copper of non-corrosive materials on transformer enclosure and one earthing terminal of neutral on the cable boxes.
Enclosure: Sheet steel with protection Class IP- 33, For HV 60KV peak fittings- i) Hinged type inspection cover on two sides of the transformer shall be provided. ii) The arrangement of lifting the active part of the transformer alongwith the cover of the tank by means of lifting lugs without disturbing the connections. iii) 4 nos. bi-directional type roller shall be provided to the transformer on cross channels to facilate the movement of transformer in both the directions. iv) Lifting hooks should be provided. Temperature scanner: Transformer will be provided with 3 RTDs for sensing winding temperatures alongwith temperature scanners for display of winding temperature and with alarm/ Trip Contacts.
Testing: All routine tests as per relavent IS will be conducted at manufacturer's works. The manufacturer should have in-house test facilities & should arrange for type tests i.e. impulse test & temp. rise test.
Sub-Station LT Panel: Supplying, installation, testing & commissioning of LT cubical type fully compartmentalized distribution panel board (Raw Normal Power), having rigid and self supporting structure fabricated with 14 SWG CRCA sheet with M.S. angle iron frame (main frame with 50 x 50 x 6 mm angle and each vertical compartment with 40 x 40 x 6 mm MS angle iron). The base of panel should be made with 75 mm x 40 mm x 4.4 mm M.S. channel. Before Fabrication Drawing of this item has to approved by EIC mentioning all major technical details with specificationto be submitted by the successful bidder. [Manufacturer/Fabricator having Test Certificates from CPRI].
Construction Details: All incoming & outgoing switches are to be housed in respective compartments hinged and gasket doors at the front. All doors should have panel locking arrangement in such a fashion that it can not be on unless the feeder remains in off position. The rear panel should gasketed arrangement will be made of easy accessibility to each compartment by providing rear panel doors with locking system . The panel is to be properly gasketed to prevent the dust & vermin. All vertical bus bar chambers is to properly arrange and all electrical equipments are to be fixed by nuts and bolts on suitable Hylam board / porcelain insulators of adequate size and dimension. The outgoing feeder connection from respective switches are to be made at rear side of panel by means of busbar, copper multi core cables, to be terminated on bolted type terminals for cable connection or on bush insulators for bus bar connection. Each compartment will be providing with DMC/FRP board at back side.
Incoming Arrangement: a) Air Circuit Breaker, Horizontal Manual Draw Out type, 4 pole, 1250 Amps, 415 volts, 50 kA for 1 sec rating manually operated with interlocked doors, automatic safety shutters, mechanical ON / OFF and service / test / isolated position indicators and frame earthing contact, with microprocessor release for LSING protection, 1 no. independent manual spring closing mechanism, conforming to IS 13947 - 2 - 1993,1 no. shunt trip coil 220 Volts AC, (Make:- L&T/Siemens/ABB/Legrand) ----- 02 nos. b) Air Circuit Breaker, Horizontal Manual Draw Out type, 4 pole, 1250 Amps, 415 volts, 50 kA (Ics) manually operated with interlocked doors, automatic safety shutters, mechanical ON / OFF and service / test / isolated position indicators and frame earthing contact with microprocessor release for LSI protection, 1 no. independent manual spring closing mechanism, 1 no. shunt trip coil 220 Volts AC, conforming to IS 13947 - 2 - 1993 as amended upto date - 1 set ----- 01 no. (for B/C)
Busbar section: 500V, 1000 Amp capacity 99.9% – 99.5% electrolytic tinned 4 bar Copper bus bar mounted on non-hygroscopic porcelain insulator / hylam sheet having sufficient di-electric strength duly wrapped with colour PVC tapes (Red, yellow, blue & black) for phases & neutral identification - 1 set. The busbar is to be rigidly supported on suitable non-hygroscopic insulating materials of robust ration to with stand electromechanical stress in the event of earth fault. All connection to bus to made by suitable nuts & bolts. The busbar is too wrapped with coloured PVC (Red. Yellow, Blue & Black) for colour identifications.
Outgoing arrangement : a) 4 pole, 1250 Amps, 415 volts, 50 kA for 1 sec rating manually operated type ACB(Make:- L&T/Siemens/ABB/ Schneider/Legrand).---- 02 nos.
b) 415 V, 100 Amps TPN SFU units with HRC fuses (Make:- L&T/Siemens/ABB/ Schneider) in open exexution.---- 01 no.
c) 415 V, 63 Amps TPN SFU units with HRC fuses (Make:- L&T/Siemens/ABB/ Schneider) in open exexution.---- 03 nos.
d) E.I. Danger Board of suitable size ------- 2 no.
Metering panel: a) 3Ph LED Voltmeter Cl 0.5 (Make: L&T/ABB/Siemens)
b) 3Ph LED Ammeter Cl 0.5 (Make: L&T/ABB/Siemens)
c) Indicating LED Lamp with colour glasses showing (Red/Yellow/Blue/Amber) (Make: Siemens /L&T/ABB/ SCHNEIDER) - 2 sets.
d)1000/5 Amp ratio C.T (Kappa/Trinity/AE or equivalent) --- 3 nos.
e) Supplying & Fixing 6 Amp SP MCB---- 6 nos.
Interconnection: All interconnection between incoming main to Busbar are to be made with suitable size electrolytic tinned Aluminium bars or equivalent flexible pve insulated multistranded single core Aluminium cable and the same between busbar to each outgoing mains and & for metering arrangements are to be made by suitable size of Copper with proper socketing of the end of each wire leads.
Earthing: A separate continuous GI earth busbar of size 50mm x 6mm is to be placed at the inside bottom of the panel and run across the full length of the panel board atleast extended for 75 mm at both side end of panel and should have drill hole to fit in 12x50mm GI nut bolt for earth strip connection. The complete panel board is to be spray painted after required surface treatment by 7 tanks process / sand blasting with 2 coat of red oxide primer & 2 coat of finished paint over dried or powder coating.
Installation: The complete panel board is to be installed on suitable brick padestal as directed by the E.I.C. All incoming/outgoing switches is to be properly lebeled on Acrylic sheet as per direction of EIC.
Electrical and Mechanical Interlocking: Electrical iterlocking through advance contacts in ACBs and mechanical interlocking with 3 castles lock and 2 keys for 2 nos. incoming ACBs and Bus Coupler ACB to ensure that only one supply is available at any time on each section of the bus and to eliminate any possibility of accidental approaching of two supplies at one bus section - 1 set
Supply & Laying of 3 core 240 sqmm, 11kV (UE) grade XLPE insulated Al. HT Cable through existing covered masonry trench incl. taking out RC covers, setting them in order, mending good the damages filling the trench with fine dry sand incl. supplying sand. (Polycab/Gloster/RR Kabel).
Making terminating joint (Heat shrinkable) of above HT cable incl. supplying of jointing Kit (3M/Raychem/Denson make) wiping tapes, brass cable gland and earthing attachment by HT jointer as per GS.
Earthing with 80 mm dia GI pipe (TATA-Medium)x 3.0 Mts. long and 1 x 19/8 stranded GI (Hot Dip) wire (4 Mts. long), 25 mm dia x 150 mm long galvanized bolt, double nuts, double washers including socketing at both ends of stranded GI (Hot Dip) wire by crimping sockets/ thimbles and S & F 40 mm dia GI pipe (ISI-Medium) protection (3 Mts. long) to be filled with bitumen partly under the ground level and partly above ground level to an average depth of 3.65 Mts.
Extra for providing masonery enclosure on the top of the earth electrode of overall size 86.36 cm x 86.36 cm x 46 cm deep (below Ground level) complete with cemented brick work(1:6) of 25 cm width duly plastered with cement morter (inside) CI hinged inspection cover of size 36.56 cm x 35.56 cm with locking arrangement, GI reducer including drilling of 46 nos. 12 mm dia holes on the GI pipe.
Extra for treatment of soil by using salt & charcoal or coke for plate electrode.
Extra for connecting the neutral of Transformer/Earth busbar to earth electrode including S & F Galvanized (Hot Dip) Steel strip 65 mm x 8 mm on wall/floor with GI saddles & insulating the same by one layer of PVC strip over one layer of ampere tape.
Supplying & fixing earth busbar of galvanized (Hot Dip) MS flat 65 mm x 8 mm on wall having clearance of 6 mm from wall including providing drilled holes on the busbar complete with GI bolts, nuts, washers, spacing insulators etc. as required.
Connecting the equipments body to earth busbar incl. S & F 50 mm x 6 mm Galvanized (Hot Dip) MS flat on wall/floor with GI saddle as required and connection to equipments with incl. drilling holes, bolts, nuts,washers etc.
S&F 9 ltr. Capacity round fire Bucket incl. S&F of MS hook and duly filled up by sand as directed by EIC.
S&F 2 Kg. capacity Gas Pressure (DPC) fire extinguisher (MINIMEX/SUREX) on wall incl. S&F MS bracket as directed by EIC.
S&F best quality FIRST AID BOX (Al. body) as per PWD specification complete with all the items as required by rule of sub-station on MS bracket on wall incl. mending good the damages to origional finish.
S&F shock treatment Chart pasted on hard board on wall with screw as required.
S&F 6 KV grade rubber hand gloves.
Supply & Delivery of 6'x3'x0.5" rubber mat for Sub-Station. (Best quality and ISI approved).
S&F EI Danger board of size 20cmX30cm on wall.
Supply & delivery of 1.1 KV grade XLPE/PVC insul+B58:B64ated following size Al. armoured cable. (KONSTRUCT / LAPP / PLAZA / AKG / Gloster). 4 core 300 sq. mm. (For Power Substation)
4 core 95 sq. mm. (For Tumbler dryer of 120 kg.)
4 core 70 sq. mm. (For LT panel to VTPN DB, Washer cum Extractor of 120 kg. & Steam Boiler)
4 core 50 sq. mm. (For Washer cum Extractor of 50 kg. & Tumbler Dryer of 50-60 kg.)
4 core 25 sq. mm. (For Washer cum Extractor of 30-35 kg., Blood Linens Sluicing Machine, Flat Work Ironer & Flat Bed Press)
4 core 16 sq. mm. (VTPN DB to HTPN DB)
4 core 10 sq. mm. (For Air Compressor of 5 HP)
2 core 10 sq. mm. (For Ironing Table with Electronic Iron, Water Feed Pumps of 2 HP & 1 HP each & compound lights)
Laying of two nos. 4 core 300 sq. mm Al. armoured cable in an underground trench in single tier formation (horizontal), the trench size : 680 mm x 760 mm average depth, with brick protection on the top of each cable 08 (Eight) nos. bricks per mtr. and 04 (Four) nos. bricks per mtr. as separator between the bricks and cables and also trench to be filled up with shifted soil, levelling up and restoring surface duly rammed. (Substation to Laundry. 02 nos. of underground trenches.)
Laying of 2 core 10 sq. mm Al. armoured cable in underground trench 460 mm wide x 760 mm average depth with brick protection on the top of the cable with 08 (Eight) nos. bricks per metre including filling the space between the bricks & cable and also the trench with shifted soil, leveling up and restoring surface duly rammed. (For compound lights)
Supplying & fixing 100 mm dia GI pipe (ISI-Medium) protection with necessary fittings and jointing metarials as required.
Supplying, installation, testing & commissioning of LT cubical type fully compartmentalized distribution panel board (Raw Normal Power), having rigid and self supporting structure fabricated with 14 SWG CRCA sheet with M.S. angle iron frame (main frame with 50 x 50 x 6 mm angle and each vertical compartment with 40 x 40 x 6 mm MS angle iron). The base of panel should be made with 75 mm x 40 mm x 4.4 mm M.S. channel. Before Fabrication Drawing of this item has to approved by EIC mentioning all major technical details with specificationto be submitted by the successful bidder. [Manufacturer/Fabricator having Test Certificates from CPRI].
Construction Details: All incoming & outgoing switches are to be housed in respective compartments hinged and gasket doors at the front. All doors should have panel locking arrangement in such a fashion that it can not be on unless the feeder remains in off position. The rear panel should gasketed arrangement will be made of easy accessibility to each compartment by providing rear panel doors with locking system . The panel is to be properly gasketed to prevent the dust & vermin. All vertical bus bar chambers is to properly arrange and all electrical equipments are to be fixed by nuts and bolts on suitable Hylam board / porcelain insulators of adequate size and dimension. The outgoing feeder connection from respective switches are to be made at rear side of panel by means of busbar, copper multi core cables, to be terminated on bolted type terminals for cable connection or on bush insulators for bus bar connection. Each compartment will be providing with DMC/FRP board at back side.
Incoming Arrangement: Air Circuit Breaker, Horizontal Manual Draw Out type, 4 pole, 630 Amps, 415 volts, 50 kA for 1 sec rating manually operated with interlocked doors, automatic safety shutters, mechanical ON / OFF and service / test / isolated position indicators and frame earthing contact, with microprocessor release for LSING protection, 1 no. independent manual spring closing mechanism, conforming to IS 13947 - 2 - 1993,1 no. shunt trip coil 220 Volts AC, with cable end box of suitable size. -1 Set (Make:- L&T/Siemens/ABB)
Busbar section: 500V, 1000 Amp capacity 99.9% – 99.5% electrolytic tinned 4 bar Copper bus bar mounted on non-hygroscopic porcelain insulator / hylam sheet having sufficient di-electric strength duly wrapped with colour PVC tapes (Red, yellow, blue & black) for phases & neutral identification - 1 set. The busbar is to be rigidly supported on suitable non-hygroscopic insulating materials of robust ration to with stand electromechanical stress in the event of earth fault. All connection to bus to made by suitable nuts & bolts. The busbar is too wrapped with coloured PVC (Red. Yellow, Blue & Black) for colour identifications.
Outgoing arrangement: a) 415 V, 200 Amps TPN SFU units with HRC fuses (Make:- L&T/Siemens/ABB) in open exexution.---- 01 no.
b) 415 V, 160 Amps TPN SFU units with HRC fuses (Make:- L&T/Siemens/ABB) in open exexution.---- 03 nos.
c) 415 V, 100 Amps TPN SFU units with HRC fuses (Make:- L&T/Siemens/ABB) in open exexution.---- 02 nos.
d) 415 V, 63 Amps TPN SFU units with HRC fuses (Make:- L&T/Siemens/ABB) in open exexution.---- 01 no.
e) E.I. Danger Board of suitable size ------- 1 no.
Metering panel: a) 3Ph LED Voltmeter Cl 0.5 (Make:- L&T/Siemens/ABB) -- 1nos
b) 3Ph LED Ammeter Cl 0.5 (Make:- L&T/Siemens/ABB) -- 1nos
c) Indicating LED Lamp with colour glasses showing (Red/Yellow/Blue/Amber) (Make: Siemens /L&T/ABB) - 1 sets.
d)1000/5 Amp ratio C.T (Kappa/Trinity or equivalent) --- 3 nos.
e) Supplying & Fixing 6 Amp SP MCB---- 6 nos.
Interconnection: All interconnection between incoming main to Busbar are to be made with suitable size electrolytic grade Tinned Copper bars and the same between busbar to each 200A SFU outgoing mains to be made with suitable size electrolytic grade Tinned Copper bars, for other SFU to be made with suitable size PVC insulated multi-stranded FR, PVC insulated multistranded single core Copper wire and for metering arrangements are to be made by suitable size of Copper with proper socketing of the end of each wire leads.
Earthing: A separate continuous GI earth busbar of size 50mm x 6mm is to be placed at the inside bottom of the panel and run across the full length of the panel board atleast extended for 75 mm at both side end of panel and should have drill hole to fit in 12x50mm GI nut bolt for earth strip connection. The complete panel board is to be spray painted after required surface treatment by 7 tanks process / sand blasting with 2 coat of red oxide primer & 2 coat of finished paint over dried or powder coating.
Installation: The complete panel board is to be installed on suitable brick padestal as directed by the E.I.C. All incoming/outgoing switches is to be properly lebeled on Acrylic sheet as per direction of EIC.
Laying of cable as below on existing cable tray and binding with suitable size GI wire. Upto 50 sq. mm.
From 70 sq. mm to 150 sq. mm.
Laying of cable of 2 core 10 sq. mm on wall/surface incl. S & F MS saddles with earthing attachment in 10 SWG GI (Hot Dip) wire, making holes etc. as necessary, mending good damages and painting.
Laying of cable of 4 core 25 , 16 & 10 sq. mm on wall/surface incl. S & F MS saddles with earthing attachment in 10 SWG GI (Hot Dip) wire, making holes etc. as necessary, mending good damages and painting.
Laying of cable of 4 core 50 sq. mm on wall/surface incl. S & F MS saddles with earthing attachment in 2 x 10 SWG GI (Hot Dip) wire, making holes etc. as necessary, mending good damages and painting.
Laying of cable of 4 core 70 & 95 sq. mm on wall/surface including S & F MS clams with earthing attachment in 2 x 10 SWG GI (Hot Dip) wire, making hole etc. as necessary, mending good damages and painting.
Supplying and fixing compression type gland complete with brass gland, brass ring & rubber ring for dust & moisture-proof entry of following size of XLPE/PVC Al armoured cables as below. 4 core 300 sq. mm
4 core 95 sq. mm
4 core 70 sq. mm
4 core 50 sq. mm
4 core 25 sq. mm
4 core 16 sq. mm
4 core 10 sq. mm
2 core 10 sq. mm
Finishing the end of following size of armoured cable by crimping method incl. supplying and fixing solderless socket (Make: Dowels), tapes, anticorrosive paste & jointing materials. 4 core 300 sq. mm
4 core 95 sq. mm
4 core 70 sq. mm
4 core 50 sq. mm
4 core 25 sq. mm
4 core 16 sq. mm
4 core 10 sq. mm
2 core 10 sq. mm
Supply & Installation of 8 mtr. Octagonal Pole with 3mm sheet thickness in MS condition before galvanization, TOP A/F 70, BOTTOM A/F 135 Base plate 225 x 225 x 16 mm thick and Anti- theft arrangement to sustain prevailing wind speed 180km/hr as per IS: 875 with 4 No. M20x 700 "J” Type foundation bolts as per EN-8 (TS-600) and water proof looping cable box having 250 V, 15 A kit- kat fuse unit, one NL on porcelain insulator etc. Including: 1 Mtr. Single Arm Bracket made of 40NB MS Pipe 48.3 X 2.9 mm thick i) Material grade of shaft shall be of S355JO / JR as per BSEN 10025 or Equivalent IS: 2062 grade E350 (BR) li) Material grade of Base Plate shall be E250(BR) as per IS:2062 iii) Galvanization as per BSEN ISO:1461 iv) Fusion Welding as per ISO 3834-2:2021. [Make: Transrail / Valmount /Bajaj]
a) Construction of suitable Shallow foundation with M-16 grade concrete for mast considering soil bearing capacity (SBC) 10T/sq. mtr. at 2 Mtr. depth with all materials and labour. Payment made as per PWD civil schedule & as per direction of EIC & Erecton, Testing & Commissioning of mast by using of lifting equipment like hydra etc. and fixing of foundation bolts, anchor plate etc. with necessary arrangement.
b) Supplying and drawing of 1.1 kv grade single core stranded ”FR’ PVC insulated and unsheathed copper wire of size 3x22/0.3 (1,5 sq.mm.) through 13 mm dia heavy gauge ploythin pipe including S&F of polyethene pipe (from loop box of pole to fittings).
c) Supply and fixing 120 W LED Street Light Lumen Efficacy >120lm/W. CRI>70, CCT 5700K, lP- 66, Aluminium Dia Cast Housing. with Toughened Glass, Potted driver. In build Surge Protection 4kv Internal & 10 kv external LM 79 Report shall be provided from manufactures NABL Lab LM 80 Nichia/Osram/Lumiled/Seoul/Bridge Lux -5 Years Warranty. Make- Halonix, Transrail, Lighting Technology.
Bidder should upload following documents from OEM, otherwise bid shall be treated as cancelled. 1) Authorization from OEM of LED manufacture. 2) NABL Lab Certificate of LED Manufacturer. 3) EN 1090-1:2029/A1:2011 Certificate of Conformity.
S&F of 240V double door Timer DB [equivalent of 2+10 SPNDB] with sheet steel enclosure, pnosphitised powder coated neutral bar, DIN rail with IP-43 potection comprising with 1 no. 240V, 25 A DP MCB , 1 no. 240V, 25A, DP Power Contactor, 1 no. Digital time switch-24 hrs with minimum switching of 15 minutes, 1 no. 240V, 25A SP MCB ('C' Curve 10kA) with inner-outer plate & internal wiring by suitable size of Cu wire incl. 1 no. Auto-Manual bypass toggle switch and provision for earthing attachment, incl. LED indication light for running condition with mechanical locking arrangement as directed by EIC. (For compound lighting control)
Excavation of soil for installation of earth electrode and filling & ramming. (For soft soil)
Earthing with 50 mm dia ISI-Medium GI pipe 3.64 mm thick x 3.04 mtr. long and 1 x 4 SWG GI (Hot dip) wire (4 mtr. long), 13 mm dia x 80 mm long GI bolts, double nuts, double washers incl. S & F 15 mm dia GI pipe protection (1 mtr. long) to be filled with bitumen partly under the ground level and partly above ground level driven to an average depth of 3.65 mtr. below the ground level. (01 set each for compound light & 02 sets each for Sub LT Panels installed at Laundry)
Extra for providing masonery enclosure on the top of the earth electrode of overall size 86.36 cm x 86.36 cm x 46 cm deep (below ground level) complete with cemented brick work (1:6) of 25 cm width duly plastered with cement morter (inside) CI hinged inspection cover of size 36.56 cm x 35.56 cm with locking arrangement, GI reducer including drilling of 46 nos. 12 mm dia holes on the GI pipe. (For LT panels)
Supplying & fixing earth busbar of galvanized (Hot dip) MS flat 40 mm x 6 mm on wall having clearance of 6 mm from wall including providing drilled holes on the busbar complete with GI bolts, nuts, washers, spacing insulators etc. as required.
Connecting the equipments to earth busbar including S & F no. 8 SWG solid GI (Hot dip) wire on wall/floor with staples buried inside wall/floor as required and making connection to equipments with bolts, nuts, washers, cable lugs etc. as required and mending good damages.
Supplying & fixing of perforated GI cable tray with perforation not more than 17.5% suspended from ceiling incl. S & F GI connector, 6 mm dia MS suspender, bolts & nuts, steel fastener etc. as required of size: (300 x 50 x 1.25) mm (18 SWG) with (25 x 25 x 3) mm angle iron support incl. Al painting of MS support.
Supplying & fixing of perforated GI cable tray bend with perforation not more than 17.5% suspended from ceiling with two (02) nos. suspenders & (25 x 25 x 3) mm angle iron for supporting the cross member incl. S & F GI connector, 6 mm dia MS suspender, bolts & nuts, steel fastener etc. as required of size: (300 x 50 x 1.25) mm (18 SWG) incl. Al painting of MS support.
Supply & fixing of perforated GI cable tray tee with perforation not more than 17.5 % suspended from ceiling with two nos. suspenders & (25 x 25 x 3) mm angle iron for supporting the cross member incl. S & F GI connector, 6 mm dia MS suspender, bolts & nuts, steel fastener etc. as required of size: (300 x 50 x 1.25) mm (18 SWG) incl. Al painting of MS support.
Supplying & fixing 415 V TPN SFU with sheet steel enclosure on angle iron frame on wall with nuts, bolts etc. incl. S & F 3 nos. DIN type HRC fuse as per rating. (L&T/Siemens/ABB) 200A
Supplying and fixing 240 V, 16 A sheet steel main switch (DP with fuse on L & N) on flat iron frame on wall. (L&T/ Havells/ Siemens).
Supplying & fixing 8 way, 160 A double door Vertical TPN MCB Distribution Board for MCCB incomer with IP-42/43 protection, on angle iron frame on wall & mending good the damages to original finish incl. interconnection with suitable size of copper wire & neutral link & provision for earthing attachment. incl. S & F 1) Incomer: 415 V, 160 A, FP MCCB of breaking capacity 25 KA/35 KA with fixed thermal & fixed magnetic/adjustable thermal & fixed magnetic setting in DB & necessary connections - 01 no., 2) Outgoings: 415 V TP MCB of breaking capacity 10 KA & C characteristics: i) 63 A - 05 nos., ii) 32 A - 03 nos. on DIN rail of DBs & necessary connections, incl. S & F 02 nos. 8 way vertical double door sheet steel (16 SWG), powder coated cable end boxes for TPN DB vertical enclosure with IP-42/43 protection, on angle iron frame on wall & mending good the damages to original finish with nuts, bolts etc. incl. provision for earthing attachment. (Legrand/ Siemens/ ABB).
Supplying and fixing 4 way double door Horizontal TPN MCB Distribution board with IP-42/43 protection, concealed in wall after cutting the wall & mending good the damages to original finish incl. Inter connection with suitable size of copper wire and neutral link & provision for earthing attachment incl. S & F 01 no. 415 V, 63 A FP MCB isolator as incomer & 12 nos. 240 V, 6-32 A SP MCB of breaking capacity 10 KA & C characteristics as outgoings as DIN rail of existing DB & necessary connections. (Legrand/Siemens/ABB).
Supplying and fixing 6 way double door Horizontal TPN MCB Distribution board with IP-42/43 protection, concealed in wall after cutting the wall & mending good the damages to original finish incl. Inter connection with suitable size of copper wire and neutral link & provision for earthing attachment incl. S & F 01 no. 415 V, 63 A FP MCB isolator as incomer & 18 nos. 240 V, 6-32 A SP MCB of breaking capacity 10 KA & C characteristics as outgoings as DIN rail of existing DB & necessary connections. (Legrand/Siemens/ABB).
Supplying and fixing 2+12 way double door SPN MCB Distribution board with IP-42/43 protection, concealed in wall after cutting the wall & mending good the damages to original finish incl. Inter connection with suitable size of copper wire and neutral link & provision for earthing attachment incl. S & F 01 no. 240 V, 40 A DP MCB isolator as incomer & 12 nos. 240 V, 6-32 A SP MCB of breaking capacity 10 KA & C characteristics as outgoings as DIN rail of existing DB & necessary connections. (Legrand/Siemens/ABB).
Finishing of the PVC insulated wire ends by socketting with pin/ ring type copper sockets and insulated tapes etc., including supplying sockets, tapes. 2.5 sqmm
Supply & delivery of Single LED Fitting (20 watt, 230 V AC, 50 Hz with CCT (5700K -6500K, THD< 10%, built in 2.5 KV SPD) with all accessories and 1 no. polycarbonate LED Tubelight as directed by EIC, Luminious efficacy > 105 & <120 Lumen/watt. The LED luminaves & accessories shall have BEE certification. (Make- Philips (Signify)/ Crompton/ Wipro)
Supply & delivery of Twin LED Fitting (20 watt, 230 V AC, 50 Hz with CCT (5700K - 6500K), THD< 10%, built in 2.5 KV SPD) with all accessories and 2 nos. polycarbonate LED Tubelight as directed by EIC, Luminious efficacy > 105 & <120 Lumen/watt. The LED luminaves & accessories shall have BEE certification. (Make- Philips (Signify)/ Crompton/ Wipro)
Fixing only single/twin fluorescent light fitting suspended 25 cm below the ceiling with 2 No. 20 mm dia EI conduit (14 SWG) supports fixed with “L” type MS clamp whose one side fixed on ceiling with sutable size 4 nos. fastener and other side connected with the conduit with suitable size of bolts and nuts incl. S&F EI conduit, “L” type (125mmx125mm) 6mm thick and 25mm with MS clamps and connecting the length of PVC insulated wire and mending good damages to original finish and painting etc. by 2x24/0.20 mm (1.5sqmm.) flexible copper wire of 1.10 mt. length.
Extra for suspension exceeding 25 cm with S&F additional 2 no. 20 mm dia EI conduit (14 SWG) supports & necy. PVC insulated wire and painting etc. as required by 2x24/0.20 mm (1.5sqmm.) flexible copper wire of 1.10 mt. length
Supply & Fixing angular batten holder (Anchor) on 75mm dia PVC round block / round bakelite on wall/ceiling.
Supply & delivery of 1400mm sweep 230V AC Ceiling fan complete with all accessories with safety wire & PS 2 type capacitor etc. as directed by EIC. (Make- Crompton Greaves/ Orient/ Usha)
Fixing only ceiling fan complete with blades, canopy, fork, rubber bush etc. incl. S&F connecting wire for down rod upto 30 cm incl. painting the rod with approved paint and making necessary connection as required by 2x1.5 sqmm flexible copper wire.
Extra for supplying additional wire for down rod & painting the rod exceeding 30 cm by 2x1.5 sqmm flexible copper wire.
Supply & Fixing Socket type fan regulator (Step type) (Make- Anchor) on existing sheet metal switchboard with bakelite / perspex top cover by screw after making housing for regulator knob by cutting bakelite/perspex top cover incl. making necy. connections etc.
Supplying & Fixing MS fan clam of two piece type for RC ceiling as per approved specification, fabricated from 40 mm x 9 mm MS flat including making good damages to building roof with satisfactory finishing and painting – (As per Drawing no. 475 of PWD Specification Book – May 1991)
Supply & delivery of 12" sweep, 1370 r.p.m. heavy duty Metal Body Exhaust fan complete with all accessories having the following Model/ Cat No. [Make - EPC Electrical Pvt. Ltd.]
Fixing only above exhaust fan after making hole in wall and making good damages and smooth cement finish etc. as practicable as possible and providing necy. length of PVC insulated wire and making connection for exhaust
Supply & Fixing Al louver shutter on wall with necy. bolts & nuts (6 mm dia x 62 mm long) for above exhaust fan.
Supply & Fixing 240 V, 6A, plug socket with separate 6 A Piano key type switch (Anchor) on sheet metal switch board embedded in wall incl. S & F 150x100x65mm MS (16SWG) switch board and bakelite/perspex top cover of 3mm thick by Brass screws after making housing for switch by cutting bakelite/perspex cover and making necessary connections as required.
Supply & Fixing 240 V, 20A, plug socket with separate 20 A Piano key type switch (Anchor) on sheet metal switch board embedded in wall incl. S & F 150x100x65mm MS (16SWG) switch board and bakelite/perspex top cover of 3mm thick by Brass screws after making housing for switch by cutting bakelite/perspex cover and making necessary connections as required.
Distn. wiring in 22/0.3 (1.5 sqmm) single core stranded 'FR' PVC insulated & unsheathed single core stranded copper wire (Finolex/Polycab/RR) in 19 mm bore, 3 mm thick polythen pipe complete with all accessories embedded in wall to light/fan/call bell points with Piano key type switch (Anchor make) fixed on sheet metal (16 SWG) switch board with bakelite/perspex (wall matching colour) top cover (3 mm thick) flushed in wall incl. mending good damages to original finish. Average run 12 mtr
Distn. wiring in 22/0.3 (1.5 sqmm) single core stranded 'FR' PVC insulated & unsheathed single core stranded copper wire (Brand approved by EIC) in 19 mm bore, 3 mm thick polythen pipe complete with all accessories embedded in wall to 240 V 5A 3 pin plug point incl. S&F 240 V 5A 3 pin flush type plug socket & piano key type switch (Anchor make) incl. S&F earth continuity wire, fixed on sheet metal (16 SWG) switch board with bakelite/perspex (wall matching colour) top cover (3 mm thick) flushed in wall incl. mending good damages to original finish. On Board.
Distn. wiring with 2 x 36/0.3 (2.5 sqmm) single core stranded copper conductor PVC insulated and unsheathed copper wire (Finolex/Polycab/RR) in 19mm dia 3 mm thick polythene pipe with 1x22/0.3 (1.5sqmm) PVC insulated and unsheathed coper wire as ECC, complete with all accessories embedded in wall.
Supplying and drawing 1.1 KV single core stranded 'FR' PVC insulated & unsheathed single core stranded copper wire (Make: Finolex/Havells/Polycab/Gloster/RR Kabel/KEI/Mescab) of the following sizes in the prelaid polythene pipe and by the prelaid GI fish wire and making necessary connections as required after cutting channel of size (40 mm x 40 mm) on masonry wall by Electric operated cutting machine incl. supplying & fixing heavy gauge 19 mm dia, 3 mm thick polythene pipe without earth continuity wire by means of anchoring chemical (Hilti/Sika) and GI 'U' hooks of 8 SWG incl. supplying and drawing 18 SWG GI wire as fish wire and mending good damages to original finish by using own tools and tackles. 2 x 84/0.3 (6 sq. mm) + 1 x 56/0.3 (4 sq. mm) ECC (HTPN DB to 02 nos. SPN DB)
2 x 22/0.3 (1.5 sq. mm) + 1 x 22/0.3 (1.5 sq. mm) as ECC. (SPN DB to 06 nos. 6 A plug point)
stage.html
html • 0.03 MB
tech_bid_open.pdf
cancelled_1.pdf
pdf • 0.14 MB
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 2.01 MB
Tendernotice_2.pdf
PDF • 0.28 MB
BOQ_2485743.xls
BOQ • 0.42 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .