Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹1.1 CrAdmitted-Finance ASHOKA PARK PALLAVA PARK BVT INS VISHWAKARMA INDIAN NAVY OF GE ND VISAKHAPATNAM | BAPATLA | ANDHRA PRADESH | 504214 | ₹1.1 Cr | L1 | Admitted-Finance |
| 2 | L2₹1.3 Cr+₹17.3 L (15.4%)Admitted-Finance | ₹1.3 Cr+₹17.3 L (15.4%) | L2 | Admitted-Finance |
| 3 | L3₹1.4 Cr+₹23.2 L (20.7%)Admitted-Finance 9 EZRA STREET KOLKATA 700 001 | KOLKATA | KOLKATA | WEST BENGAL | 700001 | ₹1.4 Cr+₹23.2 L (20.7%) | L3 | Admitted-Finance |
| 4 | L4₹1.4 Cr+₹25.0 L (22.3%)Admitted-Finance D NO 35 14 13 1 R P PETA KANCHARAPALEM VISAKHAPATNAM 530 008 | VISAKHAPATANAM | ANDHRA PRADESH | 530008 | ₹1.4 Cr+₹25.0 L (22.3%) | L4 | Admitted-Finance |
| 5 | L5₹1.4 Cr+₹26.1 L (23.3%)Admitted-Finance 65 6 518 B 1 HIMACHAL NAGAR GAJUWAKA VISAKHAPATNAM 530 026 | VISAKHAPATANAM | ANDHRA PRADESH | 530026 | ₹1.4 Cr+₹26.1 L (23.3%) | L5 | Admitted-Finance |
| Sl No | Description | Qty | Unit | M/S SRI VENKATA BHAVANI CONSTRUCTIONS L1 | M/S CHANDRA ENGINEERS AND CONTRACTORS L4 | GAGANSRI INFRA L2 | S.M.Electricals L7 | Prasur Electricals & Engineering Co. L3 | LALITHA SAI INFRA L5 | bholanath bera L6 |
|---|---|---|---|---|---|---|---|---|---|---|
| 1.00 | Supplying, Installing, Commissioning and Testing of CPRI Prototype tested, Factory made, as per IEC-61349, Platform Mounted, Dust and Vermin proof LT Feeder Panel Board, cubical type, Compartmentalised, fabricated with 3.15mm thick CRCA Sheet duly powder coated, out door canopy type with lifting hooks, consisting of Aluminium bus bar 400 Amps rating (04 Nos) for R-Y-B Phase and Neutral of high conductivity Aluminium and shall be provided with colour coded heat shrinkable sleeves mounted on porcelain/ SMC insulator supports, suitable double Compression Copper Cable Glands and panel shall be provided with separate compartments for each switch, with gland plates, lifting hooks, shutter type ventilating louver at both top & bottom duly internally secured with wire mesh, with suitable internal wiring with copper cable of suitable size etc with double stud hinged door, front and back opening, handles on each door with locking arrangement and shall be given pre-treatment for degreasing, phosphatising etc. in seven tank process and shall be powder coated with RAL7035 shade, The panel shall be mounted on and including 150mm thick PCC 1:3:6, type C-2 and panel fixed with legs minimum 450mm long made of angle iron frame of size 50x50x5mm including connecting up with existing incoming and outgoing cables, disconnecting and dismantling old panel board complete including and comprising of the following:- | 1 | EACH JOB | 1,80,000 ₹1,80,000 | 2,00,000 ₹2,00,000 | 1,80,000 ₹1,80,000 | 3,65,826 ₹3,65,826 | 1,78,500 ₹1,78,500 Lowest | 2,07,000 ₹2,07,000 | 2,00,000 ₹2,00,000 |
| 1.10[a] Onload Changeover switch I-O-II open execution, 4 Pole, 200 Amps – 01 No. [To be fixed after incomer] [b] MCCB, 200 Amps, TMD type 4 Pole, 415 V, 25 KA, adjustable thermal release- 02 Nos as incomers [Mains+DG] [d] MCCB, 100 Amps, TMD type 4 Pole, 415 V, 25 KA, adjustable thermal release- 04 Nos [Outgoing] [e] Three line multifunction meter having LCD display - 01 No [f] Current Transformer and Potential Transformer - 01 Set [g] Colour Coded LED Phase Indicating Lamps for each Phase – 03 Nos (R, Y, B) | ||||||||||
| 2.00 | Supplying, Installing, Commissioning and Testing of CPRI Prototype tested, Factory made, as per IEC-61349, Platform Mounted, Dust and Vermin proof LT Feeder Panel Board, cubical type, Compartmentalised, fabricated with 3.15mm thick CRCA Sheet duly powder coated, out door canopy type with lifting hooks, consisting of Aluminium bus bar 1500 Amps rating (04 Nos) for R-Y-B Phase and Neutral of high conductivity Aluminium and shall be provided with colour coded heat shrinkable sleeves mounted on porcelain/ SMC insulator supports, suitable double Compression Copper Cable Glands and panel shall be provided with separate compartments for each switch, with gland plates, lifting hooks, shutter type ventilating louver at both top & bottom duly internally secured with wire mesh, with suitable internal wiring with copper cable of suitable size etc with double stud hinged door, front and back opening, handles on each door with locking arrangement and shall be given pre-treatment for degreasing, phosphatising etc. in seven tank process and shall be powder coated with RAL7035 shade, The panel shall be mounted on and including 150mm thick PCC 1:3:6, type C-2 and panel fixed with legs minimum 450mm long made of angle iron frame of size 50x50x5mm including connecting up with existing incoming and outgoing cables, disconnecting and dismantling old panel board complete including and comprising of the following:- | 2 | EACH JOB | 3,00,000 ₹6,00,000 | 3,00,000 ₹6,00,000 | 3,15,000 ₹6,30,000 | 4,04,172 ₹8,08,344 | 2,59,500 ₹5,19,000 Lowest | 3,33,333 ₹6,66,666 | 3,20,000 ₹6,40,000 |
| 2.10[a] MCCB, 630 Amps, TMA type 4 Pole, 415 V, 36 KA, adjustable thermal release- 01 No [Incomer] [b] MCCB, 400 Amps, TMA type 4 Pole, 415 V, 36 KA, adjustable thermal release - 0 No [Outgoing] [c] MCCB, 250 Amps, TMD type 4 Pole, 415 V, 25 KA, adjustable thermal release - 02 Nos [Outgoing] [d] MCCB, 200 Amps, TMD type 4 Pole, 415 V, 25 KA, adjustable thermal release - 01 No [Outgoing] [e] MCCB, 100 Amps, TMD type 4 Pole, 415 V, 25 KA, adjustable thermal release - 02 Nos [Outgoing] [f] Three line multifunction meter having LCD display - 01 No [g] Current Transformer and Potential Transformer - 01 Set [h] Colour Coded LED Phase Indicating Lamps for each Phase – 03 Nos (R, Y, B) | ||||||||||
| 3.00 | Supplying, Installing, Commissioning and Testing of CPRI Prototype tested, Factory made, as per IEC-61349, Platform Mounted, Dust and Vermin proof LT Feeder Panel Board, cubical type, Compartmentalised, fabricated with 3.15mm thick CRCA Sheet duly powder coated, out door canopy type with lifting hooks, consisting of Aluminium bus bar 850 Amps rating (04 Nos) for R-Y-B Phase and Neutral of high conductivity Aluminium and shall be provided with colour coded heat shrinkable sleeves mounted on porcelain/ SMC insulator supports, suitable double Compression Copper Cable Glands and panel shall be provided with separate compartments for each switch, with gland plates, lifting hooks, shutter type ventilating louver at both top & bottom duly internally secured with wire mesh, with suitable internal wiring with copper cable of suitable size etc with double stud hinged door, front and back opening, handles on each door with locking arrangement and shall be given pre-treatment for degreasing, phosphatising etc. in seven tank process and shall be powder coated with RAL7035 shade, The panel shall be mounted on and including 150mm thick PCC 1:3:6, type C-2 and panel fixed with legs minimum 450mm long made of angle iron frame of size 50x50x5mm including connecting up with existing incoming and outgoing cables, disconnecting and dismantling old panel board complete including and comprising of the following:- | 3 | EACH JOB | 2,00,000 ₹6,00,000 | 1,80,000 ₹5,40,000 Lowest | 2,05,000 ₹6,15,000 | 3,02,922 ₹9,08,766 | 1,89,500 ₹5,68,500 | 2,07,000 ₹6,21,000 | 2,00,000 ₹6,00,000 |
| 3.10[a] MCCB, 400 Amps, TMA type 4 Pole, 415 V, 36 KA, adjustable thermal release- 01 No [Incomer] [b] MCCB, 250 Amps, TMD type 4 Pole, 415 V, 25 KA, adjustable thermal release - 01 No [Outgoing] [c] MCCB, 100 Amps, TMD type 4 Pole, 415 V, 25 KA, adjustable thermal release - 04 Nos [Outgoing] [d] Three line multifunction meter having LCD display - 01 No [e] Current Transformer and Potential Transformer - 01 Set [f] Colour Coded LED Phase Indicating Lamps for each Phase – 03 Nos (R, Y, B) | ||||||||||
| 4.00 | Supplying, Installing, Commissioning and Testing of CPRI Prototype tested, Factory made, as per IEC-61349, Platform Mounted, Dust and Vermin proof LT Feeder Panel Board, cubical type, Compartmentalised, fabricated with 3.15mm thick CRCA Sheet duly powder coated, out door canopy type with lifting hooks, consisting of Aluminium bus bar 1250 Amps rating (04 Nos) for R-Y-B Phase and Neutral of high conductivity Aluminium and shall be provided with colour coded heat shrinkable sleeves mounted on porcelain/ SMC insulator supports, suitable double Compression Copper Cable Glands and panel shall be provided with separate compartments for each switch, with gland plates, lifting hooks, shutter type ventilating louver at both top & bottom duly internally secured with wire mesh, with suitable internal wiring with copper cable of suitable size etc with double stud hinged door, front and back opening, handles on each door with locking arrangement and shall be given pre-treatment for degreasing, phosphatising etc. in seven tank process and shall be powder coated with RAL7035 shade, The panel shall be mounted on and including 150mm thick PCC 1:3:6, type C-2 and panel fixed with legs minimum 450mm long made of angle iron frame of size 50x50x5mm including connecting up with existing incoming and outgoing cables, disconnecting and dismantling old panel board complete including and comprising of the following:- | 1 | EACH JOB | 2,80,000 ₹2,80,000 | 3,00,000 ₹3,00,000 | 2,75,000 ₹2,75,000 | 3,81,168 ₹3,81,168 | 2,49,500 ₹2,49,500 Lowest | 3,60,000 ₹3,60,000 | 3,00,000 ₹3,00,000 |
| 4.10[a] MCCB, 630 Amps, TMA type 4 Pole, 415 V, 36 KA, adjustable thermal release- 01 No [Incomer] [b] MCCB, 250 Amps, TMD type 4 Pole, 415 V, 25 KA, adjustable thermal release - 02 Nos [Outgoing] [c] MCCB, 200 Amps, TMD type 4 Pole, 415 V, 25 KA, adjustable thermal release - 02 Nos [Outgoing] [d] MCCB, 100 Amps, TMD type 4 Pole, 415 V, 25 KA, adjustable thermal release - 02 Nos [Outgoing] [f] Three line multifunction meter having LCD display - 01 No [g] Current Transformer and Potential Transformer - 01 Set [h] Colour Coded LED Phase Indicating Lamps for each Phase – 03 Nos (R, Y, B) | ||||||||||
| 5.00 | Supplying, Installing, Commissioning and Testing of CPRI Prototype tested, Factory made, as per IEC-61349, Platform Mounted, Dust and Vermin proof LT Feeder Panel Board, cubical type, Compartmentalised, fabricated with 3.15mm thick CRCA Sheet duly powder coated, out door canopy type with lifting hooks, consisting of Aluminium bus bar 850 Amps rating (04 Nos) for R-Y-B Phase and Neutral of high conductivity Aluminium and shall be provided with colour coded heat shrinkable sleeves mounted on porcelain/ SMC insulator supports, suitable double Compression Copper Cable Glands and panel shall be provided with separate compartments for each switch, with gland plates, lifting hooks, shutter type ventilating louver at both top & bottom duly internally secured with wire mesh, with suitable internal wiring with copper cable of suitable size etc with double stud hinged door, front and back opening, handles on each door with locking arrangement and shall be given pre-treatment for degreasing, phosphatising etc. in seven tank process and shall be powder coated with RAL7035 shade, The panel shall be mounted on and including 150mm thick PCC 1:3:6, type C-2 and panel fixed with legs minimum 450mm long made of angle iron frame of size 50x50x5mm including connecting up with existing incoming and outgoing cables, disconnecting and dismantling old panel board complete including and comprising of the following:- | 1 | EACH JOB | 2,00,000 ₹2,00,000 | 2,00,000 ₹2,00,000 | 1,95,000 ₹1,95,000 Lowest | 3,25,935 ₹3,25,935 | 2,15,000 ₹2,15,000 | 2,07,000 ₹2,07,000 | 2,00,000 ₹2,00,000 |
| 5.10[a] MCCB, 400 Amps, TMA type 4 Pole, 415 V, 36 KA, adjustable thermal release- 01 No [Incomer] [b] MCCB, 100 Amps, TMD type 4 Pole, 415 V, 25 KA, adjustable thermal release - 03 Nos [Outgoing] [c] MCCB, 63 Amps, TMD type 4 Pole, 415 V, 25 KA, adjustable thermal release - 04 Nos [Outgoing] [d] Three line multifunction meter having LCD display - 01 No [e] Current Transformer and Potential Transformer - 01 Set [f] Colour Coded LED Phase Indicating Lamps for each Phase – 03 Nos (R, Y, B) | ||||||||||
Tender Value
₹1.4 Cr
EMD Value
₹2.2 L
Closing Date
16 Jan 2026, 6:00 pmClosed
Col Shinde SS
Commander Works Engineers, Station Road, Visakhapatnam - 530 004
SPECIAL REPAIRS FOR CONVERSION OF OVERHEAD LINES TO UNDERGROUND CABLES OF NAD COLONY UNDER GE U I VISAKHAPATNAM
2025_MES_744085_1
82631/E8
Open Tender
Civil Works
Item Rate
180 days
Visakhapatnam
As per NIT documents
9 documents required · 9 mandatory
₹1,000
GE UTILITY I
₹2.2 L
Yes
6 Feb 2026
11 Dec 2025
19 Jan 2026
11 Dec 2025
16 Jan 2026
2 Jan 2026
11 Dec 2025 - 18 Dec 2025
[a] MCCB, 200 Amps, TMD type 4 Pole, 415 V, 36 KA, adjustable thermal release- 01 No [Incomer] [b] MCCB, 100 Amps, TMD type 4 Pole, 415 V, 25 KA, adjustable thermal release - 01 No [Outgoing] [c] MCCB, 63 Amps, TMD type 4 Pole, 415 V, 25 KA, adjustable thermal release - 04 Nos [Outgoing] [d] Three line multifunction meter having LCD display - 01 No [e] Current Transformer and Potential Transformer - 01 Set [f] Colour Coded LED Phase Indicating Lamps for each Phase – 03 Nos (R, Y, B)
[a] MCCB, 630 Amps, TMA type 4 Pole, 415 V, 36 KA, adjustable thermal release- 01 No [Incomer] [b] MCCB, 400 Amps, TMA type 4 Pole, 415 V, 36 KA, adjustable thermal release - 0 No [Outgoing] [c] MCCB, 250 Amps, TMD type 4 Pole, 415 V, 25 KA, adjustable thermal release - 02 Nos [Outgoing] [d] MCCB, 200 Amps, TMD type 4 Pole, 415 V, 25 KA, adjustable thermal release - 01 Nos [Outgoing] [e] MCCB, 100 Amps, TMD type 4 Pole, 415 V, 25 KA, adjustable thermal release - 02 Nos [Outgoing] [f] Three line multifunction meter having LCD display - 01 No [g] Current Transformer and Potential Transformer - 01 Set [h] Colour Coded LED Phase Indicating Lamps for each Phase – 03 Nos (R, Y, B)
[a] MCCB, 400 Amps, TMA type 4 Pole, 415 V, 36 KA, adjustable thermal release- 01 No [Incomer] [b] MCCB, 250 Amps, TMD type 4 Pole, 415 V, 25 KA, adjustable thermal release - 01 No [Outgoing] [c] MCCB, 100 Amps, TMD type 4 Pole, 415 V, 25 KA, adjustable thermal release - 04 Nos [Outgoing] [d] Three line multifunction meter having LCD display - 01 No [e] Current Transformer and Potential Transformer - 01 Set [f] Colour Coded LED Phase Indicating Lamps for each Phase – 03 Nos (R, Y, B)
[a] MCCB, 630 Amps, TMA type 4 Pole, 415 V, 36 KA, adjustable thermal release- 01 No [Incomer] [b] MCCB, 250 Amps, TMD type 4 Pole, 415 V, 25 KA, adjustable thermal release - 02 Nos [Outgoing] [c] MCCB, 200 Amps, TMD type 4 Pole, 415 V, 25 KA, adjustable thermal release - 02 Nos [Outgoing] [d] MCCB, 100 Amps, TMD type 4 Pole, 415 V, 25 KA, adjustable thermal release - 02 Nos [Outgoing] [f] Three line multifunction meter having LCD display - 01 No [g] Current Transformer and Potential Transformer - 01 Set [h] Colour Coded LED Phase Indicating Lamps for each Phase – 03 Nos (R, Y, B)
[a] MCCB, 400 Amps, TMA type 4 Pole, 415 V, 36 KA, adjustable thermal release- 01 No [Incomer] [b] MCCB, 100 Amps, TMD type 4 Pole, 415 V, 25 KA, adjustable thermal release - 03 Nos [Outgoing] [c] MCCB, 63 Amps, TMD type 4 Pole, 415 V, 25 KA, adjustable thermal release - 04 Nos [Outgoing] [d] Three line multifunction meter having LCD display - 01 No [e] Current Transformer and Potential Transformer - 01 Set [f] Colour Coded LED Phase Indicating Lamps for each Phase – 03 Nos (R, Y, B)
[a] MCCB, 250 Amps, TMD type 4 Pole, 415 V, 36 KA, adjustable thermal release- 01 No [Incomer] [b] MCCB, 63 Amps, TMD type 4 Pole, 415 V, 25 KA, adjustable thermal release - 07 Nos [Outgoing] [c] Three line multifunction meter having LCD display - 01 No [d] Current Transformer and Potential Transformer - 01 Set [e] Colour Coded LED Phase Indicating Lamps for each Phase – 03 Nos (R, Y, B)
, disconnecting and dismantling old panel board complete including and comprising of the following:-
Supplying, laying and testing LT UG cable, XLPE insulated, screened insulated, steel strip armoured and pressure extruded PVC bedded, 1100 Volts grade [heavy duty] with aluminium conductor of size 3.5 Core 35 Sqmm laid in trenches, fixed to walls or passing through pipes and connecting up complete all as specified and as directed.
Supplying, laying and testing LT UG cable, XLPE insulated, screened insulated, steel strip armoured and pressure extruded PVC bedded, 1100 Volts grade [heavy duty] with aluminium conductor of size 4 Core 16 Sqmm laid in trenches, fixed to walls or passing through pipes and connecting up complete all as specified and as directed.
[a] Onload Changeover switch I-O-II open execution, 4 Pole, 200 Amps – 01 No. [To be fixed after incomer] [b] MCCB, 200 Amps, TMD type 4 Pole, 415 V, 25 KA, adjustable thermal release- 02 Nos [Mains+DG] [d] MCCB, 100 Amps, TMD type 4 Pole, 415 V, 25 KA, adjustable thermal release- 04 Nos [Outgoing] [e] Three line multifunction meter having LCD display - 01 No [f] Current Transformer and Potential Transformer - 01 Set [g] Colour Coded LED Phase Indicating Lamps for each Phase – 03 Nos (R, Y, B)
Supplying, laying and testing LT UG cable, XLPE insulated, screened insulated, steel strip armoured and pressure extruded PVC bedded, 1100 Volts grade [heavy duty] with aluminium conductor of size 4 Core 25 Sqmm laid in trenches, fixed to walls or passing through pipes and connecting up complete all as specified and as directed.
Supplying, laying and testing LT UG cable, XLPE insulated, screened insulated, steel strip armoured and pressure extruded PVC bedded, 1100 Volts grade [heavy duty] with aluminium conductor of size 3.5 Core 70 Sqmm laid in trenches, fixed to walls or passing through pipes and connecting up complete all as specified and as directed.
Supplying, laying and testing LT UG cable, XLPE insulated, screened insulated, steel strip armoured and pressure extruded PVC bedded, 1100 Volts grade [heavy duty] with aluminium conductor of size 3.5 Core 120 Sqmm laid in trenches, fixed to walls or passing through pipes and connecting up complete all as specified and as directed.
Supplying, laying and testing LT UG cable, XLPE insulated, screened insulated, steel strip armoured and pressure extruded PVC bedded, 1100 Volts grade [heavy duty] with aluminium conductor of size 3.5 Core 150 Sqmm laid in trenches, fixed to walls or passing through pipes and connecting up complete all as specified and as directed.
Supplying, laying and testing LT UG cable, XLPE insulated, screened insulated, steel strip armoured and pressure extruded PVC bedded, 1100 Volts grade [heavy duty] with aluminium conductor of size 3.5 Core 185 Sqmm laid in trenches, fixed to walls or passing through pipes and connecting up complete all as specified and as directed.
Supplying, laying and testing LT UG cable, XLPE insulated, screened insulated, steel strip armoured and pressure extruded PVC bedded, 1100 Volts grade [heavy duty] with aluminium conductor of size 3.5 Core 240 Sqmm laid in trenches, fixed to walls or passing through pipes and connecting up complete all as specified and as directed.
Supplying, laying and testing LT UG cable, XLPE insulated, screened insulated, steel strip armoured and pressure extruded PVC bedded, 1100 Volts grade [heavy duty] with aluminium conductor of size 3.5 Core 300 Sqmm laid in trenches, fixed to walls or passing through pipes and connecting up complete all as specified and as directed.
Excavation in trenches not exceeding 1.5m wide and not exceeding 10 Sq.m on plan area and not exceeding 1.5m deep in soft/ loose soil complete all as specified and as directed.
Removing excavated material /soil to a distance not exceeding 50m and depositing where directed at a level not exc 1.5m above the starting point complete all as specified and directed
Returning filling in, including spreading, levelling,watering and well ramming in layers not exc 25cm thickness as in soil complete all as specified and directed.
M & L for laying sub class 'B' bricks of old size 230mm x 115mm x 75mm for cable protection laid across alignment of cable in trenches complete all as specified and directed.
M&L for Sand filling in trenches using dry river sand as cushioning to under ground cable including spreading, levelling and consolidation complete all as specified and directed. [Note: Punned thickness of sand shall only be measured.]
Supplying, laying and testing LT UG cable, XLPE insulated, screened insulated, steel strip armoured and pressure extruded PVC bedded, 1100 Volts grade [heavy duty] with aluminium conductor of size 3.5 Core 400 Sqmm laid in trenches, fixed to walls or passing through pipes and connecting up complete all as specified and as directed. [Note for item Nos. 8 to 14 above: Quoted rate is deemed to be inclusive for providing Brass glands at terminals and MS cable route indicators at 50m intervals as directed by the Engineer-in-Charge]
S & F in repairs PVC insulated 3 core 1.5 Sqmm stranded copper conductor cable for connecting junction box to street light fitting including testing and commissioning complete all as directed
M & L for laying 40mm dia GI pipe light grade laid for cable protection at road crossings or fixed on walls / poles secured with clamps complete all as directed
M & L for laying 50mm dia GI pipe light grade laid for cable protection at road crossings or fixed on walls / poles secured with clamps complete all as directed
M & L for laying 80mm dia GI pipe light grade laid for cable protection at road crossings or fixed on walls / poles secured with clamps complete all as directed
Supplying, Installing, Commissioning and Testing of CPRI Prototype tested, Factory made, as per IEC-61349, Platform Mounted, Dust and Vermin proof LT Feeder Panel Board, cubical type, Compartmentalised, fabricated with 3.15mm thick CRCA Sheet duly powder coated, out door canopy type with lifting
hooks, consisting of Aluminium bus bar 200 Amps rating (04 Nos) for 3 phase 4 wire system of high conductivity Aluminium and shall be provided with colour coded heat shrinkable sleeves mounted on porcelain/ SMC insulator supports, suitable double Compression Copper Cable Glands and panel shall be provided with separate compartments for each switch, with gland plates, lifting hooks, shutter type ventilating louver at both top & bottom duly internally secured with wire mesh, with suitable internal wiring with copper cable of suitable size etc with double stud hinged door, front and back opening, handles on each door with locking arrangement and shall be given pre-treatment for degreasing, phosphatising etc. in seven tank process and shall be powder coated with RAL7035 shade, The panel shall be mounted on and including 150mm thick PCC 1:3:6, type C-2 and panel fixed with legs minimum 450mm long made of angle iron frame of size 40x40x4mm including connecting up with existing incoming and outgoing cables, disconnecting and dismantling old feeder panel complete including and comprising of the following:- [a] MCCB, 100 Amps, TMD type 4 Pole, 415 V, 25 KA, adjustable thermal release- 01 No [Incomer] [b] MCCB, 40 Amps, 4 Pole, 415 V, 16 KA, fixed thermal and magnetic thermal release - 06 Nos [Outgoing] [c] MCCB, 63 Amps, 4 Pole, 415 V, 16 KA, fixed thermal and magnetic thermal release - 01 No [Outgoing] [d] Current Transformer with Ammeter - 01 No [e] Colour Coded LED Phase Indicating Lamps for each Phase – 03 Nos (R, Y, B)
Supplying, Installing, Commissioning and Testing of CPRI Prototype tested, Factory made, as per IEC-61349, Platform Mounted, Dust and Vermin proof LT Feeder Panel Board, cubical type, Compartmentalised, fabricated with 3.15mm thick CRCA Sheet duly powder coated, out door canopy type with lifting hooks, consisting of Aluminium bus bar 200 Amps rating (04 Nos) for 3 phase 4 wire system of high conductivity Aluminium and shall be provided with colour coded heat shrinkable sleeves mounted on porcelain/ SMC insulator supports, suitable double Compression Copper Cable Glands and panel shall be provided with separate compartments for each switch, with gland plates, lifting hooks, shutter type ventilating louver at both top & bottom duly internally secured with wire mesh, with suitable internal wiring with copper cable of suitable size etc with double stud hinged door, front and back opening, handles on each door with locking arrangement and shall be given pre-treatment for degreasing, phosphatising etc. in seven tank process and shall be powder coated with RAL7035 shade, The panel shall be mounted on and including 150mm thick PCC 1:3:6, type C-2 and panel fixed with legs minimum 450mm long made of angle iron frame of size 40x40x4mm including connecting up with existing incoming and outgoing cables, disconnecting and dismantling old feeder panel complete including and comprising of the following:- [a] MCCB, 100 Amps, TMD type 4 Pole, 415 V, 25 KA, adjustable thermal release- 01 No [Incomer] [b] MCCB, 40 Amps, 4 Pole, 415 V, 16 KA, fixed thermal and magnetic thermal release - 06 Nos [Outgoing] [c] Current Transformer with Ammeter - 01 No [d] Colour Coded LED Phase Indicating Lamps for each Phase – 03 Nos (R, Y, B)
e size etc with double stud hinged door, front and back opening, handles on each door with locking arrangement and shall be given pre-treatment for degreasing, phosphatising etc. in seven tank process and shall be powder coated with RAL7035 shade, The panel shall be mounted on and including 150mm thick PCC 1:3:6, type C-2 and panel fixed with legs minimum 450mm long made of angle iron frame of size 40x40x4mm including connecting up with existing incoming and outgoing cables, disconnecting and dismantling old feeder panel complete including and comprising of the following:- [a] MCCB, 100 Amps, TMD type 4 Pole, 415 V, 25 KA, adjustable thermal release- 01 No [Incomer] [b] MCCB, 40 Amps, 4 Pole, 415 V, 16 KA, fixed thermal and magnetic thermal release - 04 Nos [Outgoing] [c] MCCB, 63 Amps, 4 Pole, 415 V, 16 KA, fixed thermal and magnetic thermal release - 01 No [Outgoing] [d] Current Transformer with Ammeter - 01 No [e] Colour Coded LED Phase Indicating Lamps for each Phase – 03 Nos (R, Y, B)
Earthing complete with Galvanised Steel Earth Plate Electrode 600 X 600 X 6 mm thick burried directly in ground [earth pit not less than 2.25 m deep below ground level] with top edge of Plate not less than 1.50 m below normal ground level connected to galvanised earth strip 25x4mm [Earth Lead] and GI pipe 40 mm dia light Grade for earthing lead protection to the extent of maximum 7.5m, earth plate electrode surrounded by 150mm thick packed layers of charcoal and common salt filled in alternate layers, connected to the plate by means of GI bolts & nuts complete all as per Electrical plate No. 3 of SSR Part – I, connected to earthing test point including testing on completion including PCC [1:2:4, Type B1] Pit with RCC 1:2:4, Type B1 Cover 50 mm thick with 6 Nos, 8 mm dia TMT bars in both ways, MS frame made with 40 X 40 X 6 mm angle iron, MS funnel with 20 mm bore medium grade GI Watering pipe, wire mesh, earth work excavation, returning filling, removal of surplus soil etc. including removing old unserviceable earthing set complete all as specified and as directed.
Dismantling cross arms of MS channel or angle sections, etc complete all as directed
QUINTAL
Dismantling insulators any type and size complete all as directed
S & F Street light fitting LED type of minimum 90 Watt, pressure die cast aluminium housing LED street light luminaires with IP66 with accessories including bracket made of 40mm bore GI medium grade pipe of 1.5m long bent to shape fixed with Two Nos of MS clamps of suitable size, bolts, nuts and washers duly painted with two coats of aluminium paint over a coat of red ixide zinc chrome primer on steel surfaces including taking down old fittings alongwith brackets complete all as specified and as directed by the Engineer-in-Charge.
S & F FRP Moulded / Polycarbonate cable looping box of minimum size 250x250x115mm complete with electrolytic aluminium bus bar of suitable size and capacity for 3 phase and neutral fixed on ebonite insulator and one MCB 6 Amps complete all as directed
EACH SET
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.58 MB
82631Tenderdoc.pdf
Tender Documents • 0.92 MB
BOQ_833191.xls
BOQ • 0.32 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .