DGM(MAT)-Purchase IOCL GUJARAT REFINERY VADODARA
DGM(MAT)-Purchase IOCL GUJARAT REFINERY VADODARA
Supply and Installation Testing Commissioning (ITC) of Battery bank and buyback of existing battery bank
2021_JR_130009_2
JRMM205051
Open Tender
Electrical - All
Supply
120 days
GUJARAT REFINERY, PO. JAWAHARNAGAR, VADODARA GUJAR
Please refer Tender documents.
5 documents required · 5 mandatory
Exempted
8 Apr 2021
3 Feb 2021
5 Mar 2021
3 Feb 2021
4 Mar 2021
4 Feb 2021
list of items
BATTERY BANK TECHNICAL DETAILS Rating : 100 AH, 110 V,1 no. KPH-100P 1 battery bank : No. of Cell : 87 + 5 nos. Spare cells Battery Bank : 110 Volts Nominal Cell Voltage : 1.2 Volts Battery bank to be supplied as per above specification and specifications attached as Annexure A "TECHNICAL SPECIFICATION FOR STATIONARY NICKEL CADMIUM BATTERIES" above specification along with standard accessories. SPECIFICATION OF THE EXISTING BATTERY BANK (To be taken by vendor under buy back) LOCATION OF BATTERY BANK : 1)9030-1014-BB-BC-CRTL(SRU-CETP) Specifications : 90AH,110V,Ni-Cd(SAB-NIFE),KPH-90P, 87 cell PURPOSE : 110 V DC for Battery Charger
BATTERY BANK TECHNICAL DETAILS 1 battery bank : Rating : 75 AH, 110 V, KPH-75P No. of Cell : 87 + 5 nos. Spare cells Battery Bank : 110 Volts Nominal Cell Voltage : 1.2 Volts Battery bank to be supplied as per above specification and specifications attached as Annexure A "TECHNICAL SPECIFICATION FOR STATIONARY NICKEL CADMIUM BATTERIES" above specification along with standard accessories. SPECIFICATION OF THE EXISTING BATTERY BANK (To be taken by vendor under buy back) LOCATION OF BATTERY BANK : 1)9030-1014-BB-BC-INST(SRU-CETP) Specifications : 60AH,110V,Ni-Cd(SAB-NIFE),KPH-60P,87 cell PURPOSE : 110 V DC for Battery Charger
BATTERY BANK TECHNICAL DETAILS 1 battery bank : Rating : 210 AH, 110 V,KPM-210P No. of Cell : 87 + 5 nos. Spare cells Battery Bank : 110 Volts Nominal Cell Voltage : 1.2 Volts Battery bank to be supplied as per above specification and specifications attached as Annexure A "TECHNICAL SPECIFICATION FOR STATIONARY NICKEL CADMIUM BATTERIES" above specification along with standard accessories. SPECIFICATION OF THE EXISTING BATTERY BANK (To be taken by vendor under buy back) LOCATION OF BATTERY BANK : 1)9030-0008-BB-BC(SRU-CETP) Specifications : 210AH,110V,Ni-Cd(SAB-NIFE),KPM-210P,87 cell PURPOSE : 110 V DC for Battery Charger
BATTERY BANK TECHNICAL DETAILS 1 battery bank : Rating : 150 AH, 110 V, KPL-150P : 1 No. of Cell : 87 + 5 nos. Spare cells Battery Bank : 110 Volts Nominal Cell Voltage : 1.2 Volts Battery bank to be supplied as per above specification and specifications attached as Annexure A "TECHNICAL SPECIFICATION FOR STATIONARY NICKEL CADMIUM BATTERIES" above specification along with standard accessories. SPECIFICATION OF THE EXISTING BATTERY BANK (To be taken by vendor under buy back) LOCATION OF BATTERY BANK : 1)9030-0010-BB-BC-INST(SRU-CETP) Specifications : 155AH,110V,Ni-Cd(SAB-NIFE),KPL-155P,85 cell PURPOSE : 110 V DC for Battery Charger
BATTERY BANK TECHNICAL DETAILS 1 battery bank : Rating : 42 AH, 120 V, SMF type No. of Cell : 10 nos. Battery Bank : 120 Volts Nominal Cell Voltage : 12 Volts Battery bank to be supplied as per above specification along with standard accessories. SPECIFICATION OF THE EXISTING BATTERY BANK (To be taken by vendor under buy back) LOCATION OF BATTERY BANK : 1)9030-TS-BB-BC-SS7B(Township) Specifications : 42AH,12V,SMF type,9 no. SMF battery PURPOSE : 110 V DC for Battery Charger
BATTERY BANK TECHNICAL DETAILS 1 battery bank : Rating : 34 AH, 360 V, KPH-34P No. of Cell : 288 + 5 nos. Spare cells Battery Bank : 360 Volts Nominal Cell Voltage : 1.2 Volts Battery bank to be supplied as per above specification and specifications attached as Annexure A "TECHNICAL SPECIFICATION FOR STATIONARY NICKEL CADMIUM BATTERIES" above specification along with standard accessories. SPECIFICATION OF THE EXISTING BATTERY BANK (To be taken by vendor under buy back) LOCATION OF BATTERY BANK : 1)9030-0008-BB-UPS(SRU-CETP) Specifications : 34AH,360V,Ni-Cd(AMCO),KPH-34P,288 cell
BATTERY BANK TECHNICAL DETAILS 1 battery bank : Rating : 26 AH, 120 V, SMF type No. of Cell : 10 nos. Battery Bank : 120 Volts Nominal Cell Voltage : 12 Volts Battery bank to be supplied as per above specification along with standard accessories. SPECIFICATION OF THE EXISTING BATTERY BANK (To be taken by vendor under buy back) LOCATION OF BATTERY BANK : 1)9030-TS-BB-BC-SS7D(Township) Specifications : 26AH,120V,SMF type, 10 no. SMF battery PURPOSE : 120 V DC for Battery Charger
BATTERY BANK TECHNICAL DETAILS Rating : 300 AH, 110 V,KPM-300P 2 battery bank : No. of Cell : 87 + 5 nos. Spare cells Battery Bank : 110 Volts Nominal Cell Voltage : 1.2 Volts Battery bank to be supplied as per above specification and specifications attached as Annexure A "TECHNICAL SPECIFICATION FOR STATIONARY NICKEL CADMIUM BATTERIES" above specification along with standard accessories. SPECIFICATION OF THE EXISTING BATTERY BANK (To be taken by vendor under buy back) LOCATION OF BATTERY BANK : 1)9030-0103-BB-BC-DCEMG(AU3) Specifications : 300AH,110V,Pb-Acid,55 cell,HBL Power System 2)9030-0103-BB-BC(AU3) Specifications : 300AH,110V,Pb-Acid,55 cell,Exide
BATTERY BANK TECHNICAL DETAILS Rating : 190 AH, 110 V,KPH-190P 1 battery bank : No. of Cell : 87 + 5 nos. Spare cells Battery Bank : 110 Volts Nominal Cell Voltage : 1.2 Volts Battery bank to be supplied as per above specification and specifications attached as Annexure A "TECHNICAL SPECIFICATION FOR STATIONARY NICKEL CADMIUM BATTERIES" above specification along with standard accessories. SPECIFICATION OF THE EXISTING BATTERY BANK (To be taken by vendor under buy back) LOCATION OF BATTERY BANK : 1)AU-I/II/CRU Instrument Supply Specifications : 170AH,110V,Ni-Cd,87 cell,SNPS
SAFT INDIA PVT LTD
Pratik Engineering Services
stage.html
html • 0.03 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .