Vadodara station: Electrical works in connection with improvement of passenger amenities, facade, circulating area, up- gradation of passenger interface areas and augmentation of parcel office facilities for passengers.
BRC-EL-P-17-2508-09-58-26
BRC-EL-P-17-2508-09-58-26
Open
Works - General
12 Months
Vadodara, Gujarat
₹0
₹9.4 L
25 Jul 2026
25 Jul 2026
10 Aug 2026
A- Electrical Power Supply Arrangements
Wiring of light/fan/exhaust fan point in concealed manner with modular accessories - The price shall cover for concealed wiring of light/fan/exhaust fan point with 1.5 sq. mm PVC insulated, unsheathed, multi-stranded, FRLS copper conductor of 1100 Volt grade, ISI marked, 1 conforming to IS: 694/1990 with 1.0 sq. mm PVC insulated, unsheathed, multi-stranded, FRLS copper conductor of 1100 Volt grade, ISI marked, conforming to IS: 694/1990 as earthing wire with all accessories in concealed type of wiring in medium grade PVC conduit and accessories of Precision/Modi/Prestoplast/Gerard make. The accessories shall be of modular type of C&S/MK/North West/L&T/Crabtree/Siemens/Anchor/Legrand/ Havells/Luminous make.
Providing plug point, 6 Amp in concealed manner on existing board with modular accessories - The price shall cover for providing plug point with modular type universal socket and switch, 6 Amp, 230 Volt, AC on existing board. The accessories shall be of modular type of C&S/MK/North West/L&T/ Crabtree/Siemens/Anchor/Legrand/Havells/Luminous make.
Providing plug point, 16 Amp in concealed manner on existing board with modular accessories - The price shall cover for providing plug point with modular type universal socket and switch, 16 Amp, 230 Volt, AC on existing board. The accessories shall be of modular type of C&S/MK/North West/L&T/ Crabtree/Siemens/Anchor/Legrand/Havells/Luminous make.
Providing power plug point, 16 Amp in concealed manner on separate board with modular accessories - The price shall cover for providing power plug point with modular type universal socket and switch, 16 Amp, 230 Volt, AC on separate board with modular accessories. The accessories shall 4 be of modular type of C&S/MK/North West/L&T/Crabtree/Siemens/Anchor/Legrand/Havells/Luminous make. The price shall also cover for concealed wiring of plug point with 2.5 sq. mm, PVC insulated, unsheathed, multi-stranded, FRLS copper conductor of 1100 Volt grade, ISI marked, conforming to IS: 694/1990 with 1.5 sq. mm, PVC insulated, unsheathed, multi-stranded, FRLS copper conductor of 1100 Volt grade, ISI marked, conforming to IS: 694/1990 as earthing wire with all accessories in concealed type of wiring in medium grade PVC conduit and accessories of Precision/Modi/Prestoplast/Gerard make.
Providing board with two switches and two sockets, 6 Amp in concealed manner with modular accessories - The price shall cover for providing multi-plug point board (switch, 6 Amp - 2 Nos and universal socket, 6 Amp - 2 Nos) with modular type universal five-pin socket and switch, 6 5 Amp, 230 Volt, AC with modular accessories. The accessories shall be of modular type of C&S/MK/North West/L&T/ Crabtree/Siemens/Anchor/Legrand/ Havells/Luminous make. The price shall also cover for concealed wiring of board with 1.5 sq. mm, PVC insulated, unsheathed, multi-stranded, FRLS copper conductor of 1100 Volt grade, ISI marked, conforming to IS: 694/1990 with 1.0 sq. mm, PVC insulated, unsheathed, multi-stranded, FRLS copper conductor of 1100 Volt grade, ISI marked, conforming to IS: 694/1990 as earthing wire with all accessories in concealed type of wiring in medium grade PVC conduit and accessories of Precision/Modi/ Prestoplast/Gerard make.
Providing board with four switches and four sockets, 6 Amp in concealed manner with modular accessories - The price shall cover for providing multi-plug point board (switch, 6 Amp - 4 Nos and universal socket, 6 Amp - 4 Nos) with modular type universal five-pin socket and switch, 6 6 Amp, 230 Volt, AC with modular accessories. The accessories shall be of modular type of C&S/MK/North West/L&T/ Crabtree/Siemens/Anchor/Legrand/Havells/Luminous make. The price shall also cover for concealed wiring of board with 1.5 sq. mm, PVC insulated, unsheathed, multi-stranded, FRLS copper conductor of 1100 Volt grade, ISI marked, conforming to IS: 694/1990 with 1.0 sq. mm, PVC insulated, unsheathed, multi-stranded, FRLS copper conductor of 1100 Volt grade, ISI marked, conforming to IS: 694/1990 as earthing wire with all accessories in concealed type of wiring in medium grade PVC conduit and accessories of Precision/Modi/ Prestoplast/Gerard make.
Concealed wiring of sub-main with 2.5 sq. mm copper wire, single-core in PVC conduit - The price shall cover for concealed wiring of sub 7 main with two-wire single core 2.5 sq. mm PVC insulated, unsheathed, multi-stranded, FRLS copper conductor of 1100 Volt grade, ISI marked, conforming to IS: 694/1990 and one wire of 1.5 sq. mm PVC insulated, unsheathed, multi-stranded, FRLS copper conductor of 1100 Volt grade, ISI marked, conforming to IS: 694/1990 in concealed manner as per site requirement in PVC conduit.
Concealed wiring of sub-main with 4.0 sq. mm copper wire, single-core in PVC conduit - The price shall cover for concealed wiring of sub 8 main with two-wire single core 4.0 sq. mm PVC insulated, unsheathed, multi-stranded, FRLS copper conductor of 1100 Volt grade, ISI marked, conforming to IS: 694/1990 and one wire of 2.5 sq. mm PVC insulated, unsheathed, multi-stranded, FRLS copper conductor of 1100 Volt grade, ISI marked, conforming to IS: 694/1990 in concealed manner as per site requirement in PVC conduit.
Providing electronic fan regulator, modular type - The price shall cover for supply, fixing, testing and commissioning of hum-free modular 9 type electronic fan regulator suitable for 80/100-Watt ceiling fan of step type with 'OFF' position, surface/flush type on existing board and its connection from existing supply. Miniature switch type regulators shall not be accepted. The regulator shall be of Anchor-Roma/Cona/ Leader/Crabtree/Legrand/C&S/HPL/Indo Asian/Havells/Standard/Bentec/Elleys/Precision make.
Wiring of sub-main with copper wire, single-core, 4.0 sq. mm - 4 Nos and 2.5 sq. mm - 1 No in PVC conduit with junction box - The price 10 shall cover for wiring of four wire sub-main with 4.0 sq. mm PVC insulated, unsheathed, multi-stranded, FRLS copper conductor of 1100 Volt grade, ISI marked, conforming to IS: 694/1990 with one wire of 2.5 sq. mm PVC insulated, unsheathed, multi-stranded, FRLS copper conductor of 1100 Volt grade, ISI marked, conforming to IS: 694/1990 in existing PVC casing-capping or medium grade PVC conduit of not less than 19 mm diameter, ISI marked of make Prestoplast/Precision/ Modi/Gerard as per site conditions with junction boxes at suitable intervals as per requirement.
Tapping of light/fan point with 1.5 sq. mm copper wire with connector from existing catenary/PVC trunking - The price shall cover for 11 tapping of light/fan point with heavy duty connector with two wires of 1.5 sq. mm, PVC insulated, unsheathed, multi-stranded, FRLS copper conductor of 1100 Volt grade, ISI marked, conforming to IS: 694/1990 and one wire of 1.0 sq. mm, PVC insulated, unsheathed, multi-stranded, FRLS copper conductor of 1100 Volt grade, ISI marked, conforming to IS: 694/1990 in green colour as earthing wire in PVC flexible pipe from existing catenary/PVC trunking.
Fixing, testing and commissioning of ceiling fan - The price shall cover for fixing, testing and commissioning of ceiling fan on existing hook and its connection by FRPVC insulated, flexible copper cord, 1100Volt grade, 24/0.20mm from existing ceiling rose with earth connection. A suitable suspension clamp made from G.I. flat of 40 x 6 mm with MS 'S' shaped hook of diameter not less than 10 mm shall be provided as per site requirement if fan hook is not available and is included in the scope of work. The ceiling fans shall be supplied by railways at site in-charge's office/store.
Providing Exhaust Fan, 300 mm sweep, heavy duty with louver/bird guard - The price shall cover for supply of heavy duty, industrial 13 Exhaust Fan of metal body, 300 mm sweep with bird guard operating on 230 Volt, 50 Hz AC supply complete with all accessories of make Crompton Greaves/GEC/ Almonard/Usha/Bajaj. The colour of the Exhaust Fan shall be as per the site requirement as per the decor of the building. The price shall also cover for fixing, testing and commissioning of the Exhaust Fan on existing pocket with rake bolts/Anchor fasteners of suitable size as per site condition, and its connection from existing ceiling rose with three-core, 24/0.20 mm size, FRPVC insulated, flexible copper wire of 1100 Volt grade.
Providing Exhaust Fan, 380/400 mm sweep, industrial heavy duty with louver/bird guard - The price shall cover for supply of heavy duty, 14 industrial Exhaust Fan of metal body, 380/400 mm sweep with bird guard operating on 230 Volt, 50 Hz AC supply complete with all accessories of make Crompton Greaves/GEC/ Almonard/Usha/Bajaj. The price shall also cover for fixing, testing and commissioning of the Exhaust Fan on existing pocket with rake bolts/Anchor fasteners of suitable size as per site condition, and its connection from existing ceiling rose with three-core, 24/0.20 mm size, FRPVC insulated, flexible copper wire of 1100 Volt grade.
Providing decorative wall bracket fan, 400 mm sweep - The price shall cover for supply of decorative wall mounted bracket fan, 400 mm 15 sweep, operating on 230 Volt, 50 Hz AC supply, oscillating type, 90° swing with three-speed regulator, three aerodynamically balanced blades made of aluminium and base made of MS pipe/plate. Make - Crompton Greaves/Usha/Orient/Bajaj/GEC/Almonard. The price shall also cover for fixing, testing and commissioning of bracket fan on wall by suitable size of MS clamps and its connection from existing socket/supply point as per site requirement. The wall bracket fan shall be got approved from site engineer before supply.
Providing energy efficient, BLDC pedestal fan, 400 mm sweep - The price shall cover for supply of energy efficient, BLDC pedestal fan, 400 mm sweep, operating on 230 Volt, 50 Hz AC supply. The pedestal fan should offer high air delivery (75 CMM), speed of 1500 RPM, low noise level ( 57dB) 16 and aerodynamically balanced blades. The fan should be supplied with IR remote control for effortless control, allowing to adjust speed, activate boost mode, set timers, enable sleep mode with a single click or enable oscillation/swing mode. The remote control shall be universal across all the pedestal fans and not needed to be paired, allowing easy operation. The fan should feature 90 degree swing (controlled by remote control/button) to ensure higher coverage across the room. Additionally, it should be manually tilted up to 30 degree allowing directing the airflow precisely for maximum comfort. The pedestal fan shall be of ATOMBERG/HAVELLS/ORIENT/CROMPTON/USHA or any other make approved by Sr. DEE (Power) Vadodara.
Providing Air circulator fan, 750 mm sweep, heavy-duty, industrial type complete with all accessories - The price shall cover for supply of heavy duty, wall mounted, Air Circulator fan, 750 mm sweep (approximately) having aluminium alloy one piece blade, double ball bearing, 90° oscillation, 17 sturdy, closed mesh guard, single phase motor, to work on 230 Volt, 50 Hz single phase AC supply. The air circulator fan shall be of ALMONARD/USHA/GEC/Crompton Greaves make and shall be got approved by site engineer before supply. The Air Circulator fan shall be provided with three core FRPVC copper flexible cord 48/0.20 mm size of suitable length. The Air Circulator shall be fitted on the structure/wall/pillar by providing M.S. clamp of 50 x 5 mm made from M. S. flat duly painted with two coats of anti-corrosive red oxide and two coats of silver enamel paint by providing proper rake bolts. The circulator shall be connected with existing supply point as per site conditions.
Providing MCB and starter with three-pin plug point for Air Conditioner unit - The price shall cover for supply, erection, testing and commissioning of power unit for Air Conditioner in enclosure with MCB DP 20/25 Amp, 3 KA breaking capacity, DOL starter of 16 - 25 Amp capacity 18 suitable for 1.5/2.0 TR A.C. unit, one No 16/20/25 Amp socket and three-pin plug top, 16/25 Amp of ANCHOR-ROMA/CRABTREE/ NORTH-WEST make with 4.0 sq. mm single core multi-stranded, PVC insulated, unsheathed FRLS copper conductor and 2.5 sq. mm single core multi-stranded, PVC insulated, unsheathed FRLS copper conductor in green colour as earthing wire of 1100 Volt grade, ISI marked, conforming to relevant and latest IS in medium grade PVC casing-capping, double lock type, ISI marked of Modi/Precision/Gerard/Prestoplast make at an approximate distance up to 3 meter or as per site requirement. The colour of enclosure should be in sync with the decor of the room and as decided by site engineer.
Providing four-core, multi-stranded, flexible copper cable, 2.5 sq. mm from indoor to outdoor unit of Split Air Conditioner - The price shall 19 cover for supply, fixing, testing and commissioning of PVC insulated, multi-stranded, four-core, copper conductor cable, 2.5 sq. mm, 1100 Volt grade, ISI marked, conforming to IS: 694 or latest of make Neocab/Polycab/Finolex/R.R. Cable. The cable shall be connected from the indoor and outdoor units of split A.C. along with 8 SWG earth wire in PVC sleeve of good quality for earthing the equipments from existing nearby earth point/electrode. The copper wire and earth wire shall be laid in PVC conduit of suitable size and properly fixed.
Providing copper piping for suction and discharge lines of Air Conditioner unit - The price shall cover for supply, fixing, testing and commissioning of refrigerant copper piping suitable for R-22, R-134 A, R-407 refrigerant and conforming to IS: 10773/2006 (latest) from indoor unit to 20 outdoor unit. The copper piping shall be insulated with polyurethane foam tubing duly covered with weather protection. The copper refrigerant pipe shall be suitable for bearing 350 PSI pressure and the thickness should be 19 SWG and diameter should be suitable for handling of refrigerant for capacity 3.5 TR of refrigerant quantity without creating any extra pressure due to quantity of refrigerant and as per manufacturer's recommendations. The exposed copper piping shall be suitably concealed as per site requirement.
Providing rigid PVC drain piping - The price shall cover for supply and fixing of rigid uPVC pipe medium grade of required diameter from indoor unit to main drain hole for draining of condensed water from cooling coil (Indoor unit) to main drain discharge point.
Supply and fixing of MS stand for outdoor unit of Split Air Conditioner - The price shall cover for fabrication, supply, fixing and 22 commissioning of MS angle frame/stand made from MS angle for outdoor unit of split AC. The size of angle shall be 40 x 40 x 6 mm painted with two coats of red oxide primer and finished with one coat of black enamel paint. The angle stand shall be fixed at site with anchor bolts. Necessary civil works involved are included in the scope of work.
Installation, testing and commissioning of Split Air Conditioner - The price shall cover for installation, fixing, testing and commissioning of 23 the split AC as per the site-engineer's instructions/requirements with all associated wiring, copper piping, existing drain piping, existing MS outdoor stand. This shall also cover for making a hole of suitable diameter in the existing brick masonry/RCC wall for laying of cables, pipes etc from indoor to outdoor unit in a neat and aesthetic manner. The hole shall be sealed with plaster of Paris to prevent entry of insects, rain water, lizards etc. Manufacturer's recommendations/instructions shall be strictly followed. Split AC shall be supplied by railways from the site engineer's office/stores.
Providing three-phase ray roll socket 32 Amp with MCB TPN, 32 Amp in SS enclosure - The price shall cover for supply of three-phase power plug and socket as per below mentioned specifications - (i) Three phase, 415 Volt power plug and three-pin socket, 32 Amp of BCH make, Cat. No. MPSEU202 or similar model of L&T/SIEMENS/HPL with MCB DP, 20 Amp -- 1No (ii) MCB TPN, 10 KA breaking capacity, 32 Amp of 24 ABB/L&T/HPL/GE/MDS/Siemens/BCH/C&S/CGL/ Schneider/Havells make --- 1 No (iii) Outdoor type enclosure fabricated from 18 SWG CRCA sheet steel, powder coated with grey enamel, wall/pillar mounted, dust and vermin proof, water resistant confirming to relevant IS. The enclosure shall fabricated for three-phase, four-wire, 440 Volt AC, 50 Hz supply system. (iv) The enclosure shall be internally wired by suitable size FRPVC insulated, single core flexible copper multi-stranded wires with crimped copper lugs. The price shall also cover for fixing testing and commissioning of the enclosure securely on cover shed pillars/rails/wall with necessary M.S. clamps, nuts, bolts etc. The drawing, design of plug socket, switchgears with make and model shall be got approved from site-engineer before fabrication and supply.
Supply, fixing, testing and commissioning of three-phase, 415 Volt, complete with MCCB, three-pole, 63 Amp, heavy duty plug-socket, 63 Amp, MCB DP, 20 Amp and ray roll plug and socket, 20 Amp in SS outdoor type enclosure for pre cooling point - The price shall cover for supply of three- phase power plug and socket as per below mentioned specifications - (i) Three-phase, 415 Volt power plug and five-pin socket, 63 Amp of BCH make, Cat. No. DS6A7A1 or similar model of L&T/SIEMENS/HPL --- 1 No (ii) Single phase, 230 Volt power plug and three-pin socket, 20 Amp of BCH make, Cat. No. MPSEU202 or similar model of L&T/SIEMENS/HPL --- 1No (iii) MCCB, four-pole, 63 Amp, with thermal-magnetic release range 50 - 63 Amp, Ics = 100% Icu 25 having 35 KA breaking capacity and conforming to IS/IEC 60947-2 with adjustable overload and short circuit settings and inbuilt instantaneous protection. The MCCB shall be supplied with spreader terminals and rotary handle. The MCCB shall be of ABB/L&T/HPL/GE/MDS/Siemens/BCH/C&S/CGL/ Schneider/Havells make --- 1 No (iv) MCB DP, 10 KA breaking capacity, 20 Amp of ABB/L&T/HPL/GE/MDS/Siemens/BCH/C&S/CGL/ Schneider/Havells make -- - 1 No (v) Outdoor type enclosure fabricated from 18 SWG CRCA sheet steel, powder coated with grey enamel, wall/pillar mounted, dust and vermin proof, water resistant confirming to relevant IS. The enclosure shall fabricated for three-phase, four-wire, 440 Volt AC, 50 Hz supply system. (vi) The enclosure shall be internally wired by suitable size FRPVC insulated, single core flexible copper multi-stranded wires with crimped copper lugs. The price shall also cover for fixing testing and commissioning of the enclosure securely on cover shed pillars/rails/wall with necessary M.S. clamps, nuts, bolts etc. The drawing, design of plug socket, switchgears with make and model shall be got approved from site-engineer before fabrication and supply.
Supply, installation, testing and commissioning of MCB TPN, 40 Amp with outdoor type MS enclosure - The price shall cover for supply, fixing, testing and commissioning of MCB TPN, 40 Amp of 10 KA breaking capacity in sheet steel enclosure or pre-fabricated double-door enclosure of same make as the MCB as far as possible. The enclosure should be suitable for outdoor installation conforming to IP: 65 protection for mounting the MCB with DIN rail. The MCB shall be of ABB/L&T/HPL/GE/MDS/Siemens/BCH/ C&S/CGL/Schneider/Havells make.
Supply, installation, testing and commissioning of RCBO, two-pole, 25 Amp with outdoor type MS enclosure - The price shall cover for 27 supply, fixing, testing and commissioning of RCBO, two-pole, 25 Amp, 30 mA sensitivity conforming to IS 12640 (Part 1) / IEC 61008-1. The RCBO shall be installed in the existing panel and shall be compatible with the existing panel. The RCBO shall be of ABB/ L&T/HPL/GE/MDS/Siemens/BCH/C&S/CGL/Schneider/Havells make.
Supply, installation, testing and commissioning of MCCB, four-pole, 100 Amp with outdoor type MS enclosure - The price shall cover for supply, fixing, testing and commissioning of MCCB, four-pole, 63 Amp, with thermal-magnetic release range 80 - 100 Amp, Ics = 100% Icu having 35 KA 28 breaking capacity and conforming to IS/IEC 60947-2 with adjustable overload and short circuit settings and inbuilt instantaneous protection of ABB/L&T/HPL/GE/MDS/Siemens/BCH/C&S/CGL/Schneider/Havells make. The MCCB shall be supplied with spreader terminals and rotary handle in sheet steel modular enclosure or pre-fabricated double-door enclosure of same make as the MCCB as far as possible. The enclosure should be suitable for outdoor installation conforming to IP: 65 protection.
Providing double-door Distribution Board with incomer MCB DP, 16/32 Amp - 1 No, RCBO, two-pole, 25 Amp - 1 No and outgoing MCB DP, 6/10/16 Amp - 4 Nos - The price shall cover for supply, fixing, testing and commissioning of pre-fabricated, double door, MCB distribution board fabricated from CRCA sheet steel, powder coated with grey finish, dust and vermin proof, water resistant with metallic door complete with MCBs of 10 KA breaking 29 capacity. The DB shall be equipped with incomer MCB DP, 16/32 Amp - 1 No, RCBO, two-pole, 30 mA sensitivity, 25 Amp - 1 No and outgoing MCB DP, 6/10/16 Amp - 4 Nos. The MCBs/RCBOs shall be of ABB/L&T/HPL/GE/MDS/Siemens/BCH/C&S/CGL/Schneider/Havells make. The board shall be completely wired with multi-stranded copper wire of suitable capacity and shall be provided with heavy duty connectors of suitable capacity for termination of incoming and outgoing wires and shall be provided with two nos of earthing terminals on each side of the board and riveted metallic caution board in three languages. The Distribution Board shall be suitable for surface/recessed installation.
Providing Distribution Board, double-door with incomer MCB TPN, 63 Amp - 1 No and outgoing MCB DP, 10/16/32 Amp - 6 Nos - The price shall cover for supply, fixing, testing and commissioning of pre-fabricated, double door, MCB distribution board fabricated from CRCA sheet steel, powder coated with grey finish, dust and vermin proof, water resistant with metallic door complete with MCBs of 10 KA breaking capacity. The DB shall be 30 equipped with incomer MCB TPN, 63 Amp - 1 No and outgoing MCB DP, 10/16/32 Amp - 6 Nos. The MCBs shall be of ABB/L&T/HPL/GE/MDS/Siemens/BCH/C&S/CGL/ Schneider/Havells make. The board shall be completely wired with multi-stranded copper wire of suitable capacity and shall be provided with heavy duty connectors of suitable capacity for termination of incoming and outgoing wires and shall be provided with two nos of earthing terminals on each side of the board and riveted metallic caution board in three languages. The Distribution Board shall be suitable for surface/recessed installation.
Providing Distribution Board with incomer MCB TPN, 32 Amp - 1 No, RCBO, three-pole, 25 Amp - 1 No and outgoing MCB DP, 10/16 Amp - 8 Nos - The price shall cover for supply, fixing, testing and commissioning of pre-fabricated, double door, MCB distribution board fabricated from CRCA sheet steel, powder coated with grey finish, dust and vermin proof, water resistant with metallic door complete with MCBs of 10 KA breaking capacity. The 31 DB shall be equipped with incomer MCB TPN, 32 Amp - 1 No, RCBO, four-pole, 30 mA sensitivity, 25 Amp - 1 No and outgoing MCB DP, 10/16 Amp - 8 Nos. The MCBs/RCBOs shall be of ABB/L&T/HPL/GE/MDS/Siemens/BCH/C&S/CGL/Schneider/Havells make. The board shall be completely wired with multi- stranded copper wire of suitable capacity and shall be provided with heavy duty connectors of suitable capacity for termination of incoming and outgoing wires and shall be provided with two nos of earthing terminals on each side of the board and riveted metallic caution board in three languages. The Distribution Board shall be suitable for surface/recessed installation.
Providing Distribution Board with incomer MCCB, four-pole, 63 Amp - 1 No, RCBO, four-pole, 63 Amp - 1 No and outgoing MCB DP, 16/20/32 Amp - 8 Nos complete with bus-bar arrangement, indication lamps, earthing terminals and all accessories - The price shall cover for fabrication, supply, fixing, testing and commissioning of Distribution Board fabricated from 18 SWG CRCA sheet steel, powder coated with grey enamel, double door, wall/floor mounted, dust and vermin proof, water resistant, outdoor type confirming to relevant IS and complete with MCCBs and MCBs. The Distribution Board shall be suitable for surface/concealed mounting. The board shall be fabricated for three-phase, four-wire, 440 Volt AC, 50 Hz supply system and shall consist of the following switchgears/accessories - (a) Incomer - MCCB, four-pole, 63 Amp, with thermal-magnetic release range 50 - 63 Amp, Ics = 100% Icu having 35 KA breaking capacity and conforming to IS/IEC 60947-2 with adjustable overload and short circuit settings and inbuilt instantaneous 32 protection. The MCCB shall be supplied with spreader terminals and rotary handle. The MCCB shall be of ABB/L&T/HPL/GE/MDS/Siemens/BCH/C&S/CGL/ Schneider/Havells make --- 1 No RCBO, four-pole, 30 mA sensitivity, 63 Amp capacity of ABB/L&T/GE/MDS/Siemens/BCH/C&S/ HPL/Schneider/Havells make --- 1 No (b) Outgoing - MCB DP, 10 KA breaking capacity, 16/20/32 Amp of ABB/L&T/HPL/GE/MDS/Siemens/BCH/C&S/ CGL/Schneider/Havells make ---- 8 Nos (c) Bus bar for main circuit and neutral shall have uniform cross section and made from electrolytic tinned copper as per relevant standards with colour coded, heat shrinkable, PVC insulated and having current density of 1.6 Amp/sq. mm cross sectional area --- 1 set (d) Multi LED type indication lamp for three-phases (Red, Yellow and Blue) of L&T/Schneider/Siemens/ C&S/ABB/BCH make with protection fuses --- 1 Set (e) Cable glands of required sizes --- LOT (f) Two earth terminals of 12 mm diameter G.I. nut/bolt with washers shall be provided in the LT panel and all sheet steel section shall be electrically connected with a separate G.I. earth strip of 50 x 6 mm size across the panel at bottom. (g) Metallic Caution Board in three languages riveted to the panel board --- 2 Nos
Providing Distribution Board with incomer MCCB, four-pole, 63 Amp - 1 No, RCBO, four-pole, 40 Amp - 1 No and outgoing MCB TPN, 32 Amp - 2 Nos and MCB DP, 16/32 Amp - 8 Nos complete with bus-bar arrangement, indication lamps, earthing terminals and all accessories - The price shall cover for fabrication, supply, fixing, testing and commissioning of Distribution Board fabricated from 18 SWG CRCA sheet steel, powder coated with grey enamel, double door, wall/floor mounted, dust and vermin proof, water resistant, outdoor type confirming to relevant IS and complete with MCCBs and MCBs. The Distribution Board shall be suitable for surface/concealed mounting. The board shall be fabricated for three-phase, four-wire, 440 Volt AC, 50 Hz supply system and shall consist of the following switchgears/accessories - (a)Incomer - MCCB, four-pole, 63 Amp, with thermal-magnetic release range 50 - 63 Amp, Ics = 100% Icu having 35 KA breaking capacity and conforming to IS/IEC 60947-2 with adjustable overload and short circuit settings and 33 inbuilt instantaneous protection. The MCCB shall be supplied with spreader terminals and rotary handle. The MCCB shall be of ABB/L&T/HPL/GE/MDS/Siemens/BCH/C&S/CGL/ Schneider/Havells make --- 1 No RCBO, four-pole, 30 mA sensitivity, 40 Amp capacity of ABB/L&T/HPL/GE/MDS/Siemens/BCH/C&S/ CGL/Schneider/Havells make --- 1 No (b)Outgoing - MCB TPN, 10 KA breaking capacity, 32 Amp of ABB/L&T/HPL/GE/MDS/Siemens/BCH/C&S/CGL/ Schneider/Havells make ---- 2 Nos MCB DP, 10 KA breaking capacity, 16/32 Amp of ABB/L&T/HPL/GE/MDS/Siemens/BCH/C&S/ CGL/Schneider/Havells make ---- 8 Nos (c)Bus bar for main circuit and neutral shall have uniform cross section and made from electrolytic tinned copper as per relevant standards with colour coded, heat shrinkable, PVC insulated and having current density of 1.6 Amp/sq. mm cross sectional area --- 1 set (d)Multi LED type indication lamp for three-phases (Red, Yellow and Blue) of L&T/Schneider/Siemens/ C&S/ABB/BCH make with protection fuses --- 1 Set (e)Cable glands of required sizes --- LOT (f)Two earth terminals of 12 mm diameter G.I. nut/bolt with washers shall be provided in the LT panel and all sheet steel section shall be electrically connected with a separate G.I. earth strip of 50 x 6 mm size across the panel at bottom. (g)Metallic Caution Board in three languages riveted to the panel board --- 2 Nos
Providing Distribution Board with incomer MCCB, four-pole, 125 Amp - 1 No and outgoing MCCB, four-pole, 63 Amp - 4 Nos and MCB DP, 32 Amp - 12 Nos complete with bus-bar arrangement, multi-function meter, indication lamps, earthing terminals and all accessories - The price shall cover for fabrication, supply, fixing, testing and commissioning of Distribution Board fabricated from 18 SWG CRCA sheet steel, powder coated with grey enamel, double door, wall/floor mounted, dust and vermin proof, water resistant, suitable for outdoor installation and confirming to relevant IS and complete with MCCBs and MCBs. The board shall be fabricated for three-phase, four-wire, 440 Volt AC, 50 Hz supply system and shall consist of the following switchgears/ accessories - (a) Incomer - MCCB, four-pole, 125 Amp, with thermal-magnetic release range 100 - 125 Amp, Ics = 100% Icu having 35 KA breaking capacity and conforming to IS/IEC 60947-2 with adjustable overload and short circuit settings and inbuilt instantaneous protection. The MCCB shall be supplied with spreader terminals and rotary handle. The MCCB shall be of ABB/L&T/HPL/GE/MDS/Siemens/BCH/C&S/ CGL/Schneider/Havells make - 34 -- 2 Nos (b) Outgoing - MCCB, four-pole, 63 Amp, with thermal-magnetic release range 50 - 63 Amp, Ics = 100% Icu having 35 KA breaking capacity and conforming to IS/IEC 60947-2 with adjustable overload and short circuit settings and inbuilt instantaneous protection. The MCCB shall be supplied with spreader terminals and rotary handle. The MCCB shall be of ABB/L&T/HPL/GE/MDS/Siemens/BCH/C&S/ CGL/Schneider/Havells make --- 4 Nos MCB DP, 10 KA breaking capacity, 32 Amp of ABB/L&T/HPL/GE/MDS/Siemens/BCH/C&S/CGL/ Schneider/Havells make ---- 12 Nos (c) Bus bar for main circuit and neutral shall have uniform cross section and made from electrolytic tinned copper as per relevant standards with colour coded, heat shrinkable, PVC insulated and having current density of 1.6 Amp/sq. mm cross sectional area --- 1 set (d) Digital multifunction meter for measurement of Voltage, Current, Frequency, KW, PF, KVAR, KVA, KVAH, KWH, KVARH with required capacity of CT. The multifunction meter shall be of L&T/Siemens /Schneider/HPL/Secure Meters Ltd/Anchor/Panasonic/El measure make --- 1 No (e) Multi LED type indication lamp for three-phases (Red, Yellow and Blue) of L&T/Schneider/Siemens/ C&S/ABB/BCH make with protection fuses --- 1 Set (f) Cable glands of required sizes --- LOT (g) Two earth terminals of 12 mm diameter G.I. nut/bolt with washers shall be provided in the LT panel and all sheet steel section shall be electrically connected with a separate G.I. earth strip of 50 x 6 mm size across the panel at bottom. (h) Metallic Caution Board in three languages riveted to the panel board --- 2 Nos
Providing Distribution Board, outdoor type, double-door, wall/floor mounted with incomer MCCB, four-pole, 125 Amp - 2 Nos and outgoing MCCB, four-pole, 100 Amp - 2 Nos, MCCB, four-pole, 63 Amp - 2 Nos, MCB TPN, 32 Amp - 8 Nos complete with bus-bar arrangement, indication lamps, earthing terminals and all accessories - The price shall cover for design, supply, installation, testing and commissioning L.T. distribution board fabricated from 2.0 mm thick M.S. sheet, standard angles, channels etc. as required in design. The drawing, design, switch gears with make and model of the LT panel shall be submitted by the contractor in three copies and got approved from site engineer before fabrication. The LT panel shall be rectangular- cubicle type, dust and vermin proof suitable outdoor installation for three-phase, four-wire, 415 Volt, 50 Hz AC supply system. Detailed technical specifications are given in Annexure-XXI of tender document.
Providing Distribution Board, outdoor type, double-door, wall/floor mounted with incomer MCCB, four-pole, 250 Amp - 1 No and outgoing MCCB, four-pole, 125 Amp - 2 Nos, MCCB, four-pole, 100 Amp - 2 Nos, MCCB, four-pole 63 Amp - 2 Nos and MCCB, four-pole, 32 Amp - 2 Nos complete 36 with bus-bar arrangement, multi-function meter, indication lamps, earthing terminals and all accessories - The price shall cover for design, supply, installation, testing and commissioning L.T. distribution board fabricated from 2.0 mm thick M.S. sheet, standard angles, channels etc. as required in design. The drawing, design, switch gears with make and model of the LT panel shall be submitted by the contractor in three copies and got approved from site engineer before fabrication. The LT panel shall be rectangular-cubicle type, dust and vermin proof suitable outdoor installation for three-phase, four-wire, 415 Volt, 50 Hz AC supply system. Detailed technical specifications are given in Annexure-XXI of tender document.
Providing Distribution Board, outdoor type, floor mounted with incomer SFU, four-pole, 125 Amp - 2 Nos, RCBO, four-pole, 100 Amp - 2 Nos and outgoing SFU, four-pole, 100 Amp - 2 Nos and SFU, four-pole, 63 Amp - 6 Nos complete with bus-bar arrangement, multi-function meter, indication 37 lamps, earthing terminals and all accessories - The price shall cover for design, supply, installation, testing and commissioning L.T. distribution board fabricated from 2.0 mm thick M.S. sheet, standard angles, channels etc. as required in design. The drawing, design, switch gears with make and model of the LT panel shall be submitted by the contractor in three copies and got approved from site engineer before fabrication. The LT panel shall be rectangular-cubicle type, dust and vermin proof suitable outdoor installation for three-phase, four-wire, 415 Volt, 50 Hz AC supply system. Detailed technical specifications are given in Annexure-XXI of tender document.
Supply, installation, testing and commissioning of three phase, energy efficient, star rated, horizontal, mono block submersible pump set of capacity 15.0 HP with all standard accessories and discharge of approximately 1000 to 1500 LPM at a head of approximately 36 to 40 meters at duty point - The price shall cover for supply of energy efficient, star-rated, horizontal, mono-block, submersible pump set of capacity 15.0 HP with delivery of 38 approximately 1000 to 1500 LPM at a speed of 2880 RPM and at a total head (inclusive of all losses) of 36 to 40 meters (at duty point) for clean drinking water. The pump shall conform to IS: 14220- 1994 with latest amendments and should be guaranteed for the pump discharge for the range of head between -25% and +10% of the specified head. The submersible pump motor shall be continuously rated for operation on 415 Volt, 50 Hz, three-phase AC supply. The motor shall be squirrel cage induction type with winding of 'wet' type and should conform strictly to the relevant clause of IS: 14220- 1994 with latest amendments. The motor should be of adequate capacity to provide pumping discharge within the range of -25% to +10% of specified head. The pump set shall be of Johnson/Falcon/Duke/CGL/KSB/CRI/ Waterman/Uneel/Kirloskar/Jeet/Shakti make.
Supply of three phase, energy efficient, star rated, submersible pump set of capacity 20.0 HP with all standard accessories and discharge of approximately 900 LPM at a head of approximately 75 meters at duty point - The price shall cover for supply of energy efficient, star-rated, vertical submersible pump set of capacity 20.0 HP with delivery of approximately 900 LPM at a speed of 2880 RPM and at a total head (inclusive of all losses) of 39 75 meters (at duty point) for clean drinking water. The pump shall conform to IS: 8034 - 2002 with latest amendments and should be guaranteed for the pump discharge for the range of head between -25% and +10% of the specified head. The submersible pump motor shall be continuously rated for operation on 415 Volt, 50 Hz, three-phase AC supply. The motor shall be squirrel cage induction type with winding of 'wet' type and should conform strictly to relevant clause of IS: 8034 - 2002 with latest amendments. The motor should be of adequate capacity to provide pumping discharge within the range of -25% to +10% of specified head. The pump set shall be of Johnson/Falcon/Duke/CGL/KSB/CRI/ Waterman/Uneel/Kirloskar/Jeet/Shakti make.
Providing pump control panel with automation and suitable rating of power factor improvement capacitor and energy meter for up to 20.0 HP pump and removal of old control panel - The price shall cover for supply, fixing, testing and commissioning of pump motor control panel for 20.0 HP 40 pump as per the details given below - Pump Motor Control Panel, wall mounted type, fabricated from 16 SWG CRCA sheet steel totally enclosed, dust and vermin proof, water resistant and provided with double coating of red oxide and final coating of Siemens grey powder coating. The approximate size of panel shall be 800 x 700 x 300 mm (H x W x D). The pump control panel shall be suitable for operation on 415 Volt, three-phase, 50 Hz, AC supply and shall consist of the switchgears/accesories given in the detailed technical specification in Annexure-XXI of tender document.
Providing pump control panel with automation and suitable rating of power factor improvement capacitor and energy meter for up to 25.0 HP pump - The price shall cover for supply, fixing, testing and commissioning of pump motor control panel for 25.0 HP pump as per the details given 41 below - Pump Motor Control Panel, wall mounted type, fabricated from 16 SWG CRCA sheet steel totally enclosed, dust and vermin proof, water resistant and provided with double coating of red oxide and final coating of Siemens grey powder coating. The approximate size of panel shall be 800 x 700 x 300 mm (H x W x D). The pump control panel shall be suitable for operation on 415 Volt, three-phase, 50 Hz, AC supply and shall consist of the switchgears/accesories given in the detailed technical specification in Annexure-XXI of tender document.
Providing uPVC, non-corrosive, hi-tech, high tensile column pipe, 75 mm diameter - The price shall cover for supply, erection, testing and commissioning of uPVC Column pipe having nominal bore of 75 mm diameter, socket type, heavy grade, non-corrosive, Hi-tech, Hi-tensile of approximate 42 length 3 meters (10 feet) with coupling at one end with square thread, 'O' ring with SS key locking facility. The uPVC pipe shall be of Godavari/Captain/Duke/Jeet/Vivon/Finolex/Ashirvaad/Supreme/Falcon make. Note - One set of the following accessories shall be supplied by the contractor for maintenance of the pumps, suitable for 75 mm diameter uPVC column pipes - 1. Bottom adapter/connector - 1 No 2. Top adapter/connector- 1 No 3. Pump guard- 2 Nos 4. Inner jig- 1 No 5. Outer jig- 1 No 6. Lowering Fixture- 1 No
Providing accessories like non return valve, sluice valve, pressure gauge with siphon cock, bend, coupler, pipe fittings, top bottom set, rubber packing, clamps set, nuts, bolts etc for 75 mm diameter pipe - The price shall cover for supply and fixing of following accessories for the above pumps - 1. 75 mm diameter non-return valve, heavy duty, ISI marked with MS flange heavy duty and gasket conforming to IS: 5312 (latest), for collar thickness along with test certificate of make Karan/Kartar/BVI with nuts, bolts and washers ----- 1 No 2. 75 mm diameter C.I. Sluice valve heavy duty ISI 43 marked with MS heavy duty flange and gasket conforming to IS: 780 (latest), along with test certificate with nuts bolts and washers ---- 1 No 3. Heavy duty 90° bend 70 mm diameter with coupling at one end and M.S. heavy duty flange at other end ---- 2 Nos 4. ISI marked, pressure gauge of suitable capacity with siphon, stop cock, bend and coupler as per relevant IS ---- 1 No. 5. Supply and fixing of 75 mm diameter, M.S. supporting clamps set not less than 450 mm long with 4 holes fabricated from M.S. flat of size 100 x 10 mm for column pipe complete with 4 Nos of M.S. full threaded nut bolts washers of 16 mm diameter ---- 2 Set 6. Provision of information board of size 900 x 600 mm made from black anodized 18 SWG metal sheet with pump details printed on it as per site engineer's instructions ---- 1 No
Supply of three-core, copper conductor, flat cable, 4.0 sq. mm - The price shall cover for supply, laying, testing and commissioning of flat 44 submersible, PVC insulated and sheathed cable with multi-stranded copper conductor having three cores of size 4.0 sq. mm conforming to IS: 694 (Part- I) or latest for submersible motor of Finolex/R.R. Kabel/Neocab/Jeet/Falcon make. A copy of Test Certificate along with the invoice of authorized dealer should be submitted along with the delivery challan.
Supply of three-core, copper conductor, flat cable, 6.0 sq. mm - The price shall cover for supply, laying, testing and commissioning of flat 45 submersible, PVC insulated and sheathed cable with multi-stranded copper conductor having three cores of size 6.0 sq. mm conforming to IS: 694 (Part- I) or latest for submersible motor of Finolex/R.R. Kabel/Neocab/Jeet/Falcon make. A copy of Test Certificate along with the invoice of authorized dealer should be submitted along with the delivery challan.
Supply of three-core, copper conductor, flat cable, 10.0 sq. mm - The price shall cover for supply, laying, testing and commissioning of flat 46 submersible, PVC insulated and sheathed cable with multi-stranded copper conductor having three cores of size 10.0 sq. mm conforming to IS: 694 (Part- I) or latest for submersible motor of Finolex/R.R. Kabel/Neocab/Jeet/Falcon make. A copy of Test Certificate along with the invoice of authorized dealer should be submitted along with the delivery challan.
Erection, testing and commissioning of new submersible pump after removing old pumps with all accessories - The price shall cover for 47 erection, testing and commissioning of submersible pumps complete with all standard accessories. The price shall also cover for removal of the existing pump and associated accessories from the bore/sump in a safe and secure manner and handing over the same to site in-charge at his office/stores on challan.
Providing online UPS, 2.0 KVA cap with 120 minutes backup - Supply, fixing, testing and commissioning of Online UPS, 2.0 KVA capacity with isolation transformer and 120 minutes backup complete with all accessories, IGBT PWM based system suitable for single phase, 230 Volt 50 Hz AC input and single phase 230 Volt, sine wave, 50 Hz AC output, floor mounting type with indicative backup time of 120 minutes with minimum 6400 VAH, SMF VRLA batteries. Specifications are as under - Capacity - 2.0 KVA Input Voltage - 160 - 260 Volt, Single-phase, 50 Hz AC PF - Minimum 0.9 at full load Overall efficiency - 90% at Rated Load Overload capacity - Deliver a minimum overload at 125% for 10 minutes and 150% for 30 seconds. Operating temperature - 0 to 40 deg C Total harmonic distortion - Maximum 3% for linear loads and 5% for Non linear loads Crest factor - 3.1 Noise level - Maximum 55 db Battery - SMF type battery, 42 AH, 12 Volt - 8 Nos Make - HBL/Amara Raja/Exide/CSB/Panasonic/Hitachi/Yuasa Warranty - Minimum five (5) years for UPS and 2 years for batteries
Digging of cable trench 450/600 mm wide and 900 mm deep in all types of soil including hard, rocky etc - The price shall cover for digging of 450/600 mm wide and 900 mm deep trench in all types of soil including soft, rocky as per cable route plan and filling back the trench after laying of cables. This also includes clearing of roots of trees and bushes and other temporary obstructions on the selected route.
Digging of cable trench 100 mm wide and 200 mm deep in concrete/tar road/platform and refilling to its original position after laying of 50 cable in 50 mm diameter HDPE pipe - The price shall cover for digging of cable trench of size 100 x 200 mm deep in concrete/tar road/platform surface and its refilling/plastering after laying of cable in 50 mm diameter HDPE pipe of Tijaria/Himalyan/Koncept/Poddar /Unique/Dutron/Reliance/Baba/Shivam make in existing trench. Supply and laying of HDPE pipe, 50 mm diameter is included in the scope of work.
Digging of cable trench 200 mm wide and 200 mm deep in concrete/tar road/platform and refilling to its original position after laying of 51 cable in 110 mm diameter HDPE pipe - The price shall cover for digging of cable trench of size 200 x 200 mm deep in concrete/tar road/platform surface and its refilling/plastering after laying of cable in 110 mm diameter HDPE pipe of Tijaria/Himalyan/Koncept/ Poddar/Unique/Dutron/Reliance/Baba/Shivam make in existing trench. Supply and laying of HDPE pipe, 110 mm diameter is included in the scope of work.
Supply and laying of DWC pipe, 63 mm diameter - The price shall cover for supply of Double Wall Corrugated (DWC) HDPE pipe of 63 mm diameter. DWC HDPE pipe shall have corrugation on outer wall but inner wall shall be plain conforming to IS: 14930 Part I and II amended from time to time. The pipes shall be "ISI" marked. Accessories like HDPE snap fit coupler with neoprene 'O' ring shall be part of supply to make the joints water/damp 52 proof. The strength and stiffness class of the pipe shall be SN4 and SN8 respectively. The price shall also cover for laying the DWC pipes in the ground below the tracks/road by push through method at a depth below the formation level as indicated in the drawing supplied by railway. The term "formation" level means the earth surface just below the bedding of the ballast. In case of any hard/stony soil, contractor should adopt new technology method in push through method. Each length of the pipes shall be joined together properly using proper size of socket and aligned in a straight line, keeping an inclination to facilitate the draining of water.
Supply and laying of DWC pipe, 120 mm diameter - The price shall cover for supply of Double Wall Corrugated (DWC) HDPE pipe of 120 mm diameter. DWC HDPE pipe shall have corrugation on outer wall but inner wall shall be plain conforming to IS: 14930 Part I and II amended from time to time. The pipes shall be "ISI" marked. Accessories like HDPE snap fit coupler with neoprene 'O' ring shall be part of supply to make the joints 53 water/damp proof. The strength and stiffness class of the pipe shall be SN4 and SN8 respectively. The price shall also cover for laying the DWC pipes in the ground below the tracks/road by push through method at a depth below the formation level as indicated in the drawing supplied by railway. The term "formation" level means the earth surface just below the bedding of the ballast. In case of any hard/stony soil, contractor should adopt new technology method in push through method. Each length of the pipes shall be joined together properly using proper size of socket and aligned in a straight line, keeping an inclination to facilitate the draining of water.
Providing PVC maxi trunking of size 50 x 50 mm - The price shall cover for supply, fixing, testing and commissioning of ISI marked PVC 54 Maxi Trunking of size 50 x 50 mm with all accessories of make Precision/Gerard/Modi/Prestoplast. The PVC Maxi trunking shall be fixed at site by fabricated clamp of 18 SWG GI sheet at a distance not more than 1.5 meters by machine screw/GI nut bolts, washers etc. The existing power cables shall be laid in the PVC Maxi trunking properly dressed and secured by means of suitable clamps/fasteners etc.
Providing PVC maxi trunking of size 100 x 50 mm - The price shall cover for supply, fixing, testing and commissioning of ISI marked PVC 55 Maxi Trunking of size 100 x 50 mm with all accessories of make Precision/Gerard/Modi/Prestoplast. The PVC Maxi trunking shall be fixed at site by fabricated clamp of 18 SWG GI sheet at a distance not more than 1.5 meters by machine screw/GI nut bolts, washers etc. The existing power cables shall be laid in the PVC Maxi trunking properly dressed and secured by means of suitable clamps/fasteners etc.
Supply and erection of G.I. perforated cable tray of size 150 mm x 100 mm x 100 mm on MS frame with cover - The price shall cover for fabrication, supply and fixing of M.S. perforated cable tray, hot dip galvanized as per latest ISS/BSS of size 150 x 100 x 100 mm and 2.0 mm approximate 56 thickness with appropriate cover of thickness 1.6 mm. The cable tray shall be fixed horizontally or vertically at site and the existing LT cables shall be laid/shifted in the cable tray by disconnecting from the panel/switch end and reconnecting as per site requirement duly tied with suitable clamps with GI nuts, bolts and washers in a safe and secure manner. The fixing clamps shall be fabricated from 50 x 50 x 6 mm MS angle or 50 x 6 mm MS flat duly painted and fixed at approximate distance of 1.5 to 2.0 meter apart with 2" long dowel/fisher rack bolts. The tray shall be fabricated in lengths of 2.0 m and couplers shall be provided at joints. The cable tray cover shall be fixed with GI screws.
Providing uPVC pipe, 50 mm diameter - The price shall cover for supply of uPVC pipe of 50 mm nominal bore diameter and working pressure of 14 kg/sq. cm along with coupling, elbow, tee etc for protection of cable. The upright cable shall be encased in uPVC pipes for mechanical 57 protection. The pipe shall be clamped with flat MS clamp at each location on upright cable length. uPVC Pipe shall be as per ASTM-D:1785, Sch-80 of PARIXIT/SWASTIK/ASHIRWAD/ASTRAL/DOLPHIN/POLYTECH/FALCON/DUKE make. The price shall also cover for laying the uPVC pipes in ground/road and under the track by digging open trench method. Each length of the pipes shall be joined together using proper size of uPVC coupler and properly aligned in a straight line, keeping an inclination to facilitate the draining of water.
Providing 'B' Class G.I. Pipe of 75 mm diameter - The price shall cover for supply and fixing of G.I. pipe, 'B' class, medium grade, ISI 58 marked, 75 mm diameter as per IS: 1239/1990 or latest for protection of cables at wall/cover shed/FOB and poles and its fixing by clamps made from 40 x 6 mm M.S. flat duly painted along with required GI nuts-bolts and washers fixed at a distance of 1.0 meter. The GI pipe shall be of Tata/Zenith/Jindal/Surya/Swastik make.
Supply and laying of HDPE pipe, 110 mm diameter, by pushing method under track/road - The price shall cover for supply of HDPE (High Density Polyethylene) pipe of 110 mm nominal diameter as per IS 4984-1995 of make Tijaria/Himalyan/Koncept/Poddar/Unique with accessories required 59 for laying such as coupler, bend etc. as per the details given in technical specification in Annexure-XXI of tender document. The price shall also cover for laying the HDPE pipes in the ground below the tracks/road by push through method at a depth below the formation level as indicated in the drawing supplied by railway. The term "formation" level means the earth surface just below the bedding of the ballast. In case of any hard/stony soil, contractor should adopt new technology method in push through method. Each length of the pipes shall be joined together properly using proper size of socket and aligned in a straight line, keeping an inclination to facilitate the draining of water.
Laying of cable in trench - The price shall cover for laying, testing and commissioning of LTUG armoured cable in existing trench/pipe and 60 its connection at both ends. The cable shall be tested with 500 Volt Megger earth tester before laying it in the trench. The cable cores shall be tested for continuity, absence of cross phasing, Insulation Resistance between conductors to earth/armour and between conductors. The results should be recorded in presence of railways' representative. A composite cable layout plan on ferro-print or computerized print duly laminated in A-4 size should be submitted by the contractor to this office as well as site in-charge after laying of cable. Cables shall be supplied by railways at site engineer's stores.
Laying of cable on wall/cover shed/existing tray with MS clamp - The price shall cover for laying, testing and commissioning of LTUG armoured cable on wall/cover shed/in existing tray and its connection at both ends. The cable shall be tested with 500 Volt Megger before laying it in the 61 tray. The cable cores shall be tested for continuity, absence of cross phasing, Insulation Resistance between conductors to earth/armour and between conductors. The results should be recorded in presence of railways' representative. A composite cable layout plan on ferro-print or computerized print duly laminated in A-4 size should be submitted by the contractor to site engineer and Divisional Office after laying of cable. Cables shall be supplied by railways at site engineer's stores.
Providing polyurethane painted, decorative single arm bracket fabricated from "B" Class MS pipe of 42 mm diameter - The price shall cover 62 for supply and fixing of decorative single arm bracket fabricated from "B" Class MS pipe of 42 mm diameter. The pole cap shall be 200 mm long and the diameter shall be suitable for fixing on the existing octagonal street light poles. The length of the arm shall be 1000 mm. The bracket shall be PU painted as per relevant Indian standards. The shade of PU paint shall be decided by railways as per the site scheme. The design of the bracket shall be got approved by the site engineer before fabrication.
Providing polyurethane painted, decorative double arm bracket fabricated from "B" Class MS pipe of 42 mm diameter - The price shall cover for supply and fixing of decorative double arm bracket fabricated from "B" Class MS pipe of 42 mm diameter. The pole cap shall be 200 mm long and the diameter shall be suitable for fixing on the existing octagonal street light poles. The length of the arm shall be 1000 mm on each side. The bracket shall be PU painted as per relevant Indian standards. The shade of PU paint shall be decided by railways as per the site scheme. The design of the bracket shall be got approved by the site engineer before fabrication.
Supply, fixing, testing and commissioning of 5.0-meter height G.I. Street Light octagonal pole, double arm complete with all accessories and foundation - The price shall cover for supply, erection and commissioning of 5.0-meter height double arm, G.I. Street light octagonal pole as per the specifications mentioned in Annexure-XXI of tender document.
Providing decorative round pole, 3.0/3.5 meter height, complete with foundation, suitable bracket for mounting LED fittings and all accessories - The price shall cover for supply of Mild Steel Decorative Pole of 3.0/3.5 meter length with cast aluminium mounting ring at top. The pole shall be conical in design with a round cross-section. The diameter shall be approximately 70 mm at bottom and 50 mm at top. The thickness of pole shall be 1.5 mm. The pole shall be supplied with a mounting base (suitable for grouting) of thickness 6.0 mm and 130 mm diameter. The mounting base shall be provided with four nos of mounting holes. Holes of suitable diameter with rubber grommet for cable entry shall be provided at top and bottom of the pole. The price shall also cover for erection of the pole, including digging of pole pit of suitable depth and casting of foundation with cement, sand and metal in 65 the ratio of 1:3:6. The foundation shall be of 250 mm diameter of suitable depth and 300 mm height above ground level. The pole foundation top surface above ground level shall have a smooth finish and straight alignment. All items such as cement, sand, metal, foundation bolts, nuts etc. required for execution of this item shall be arranged by the contractor. The price shall also cover for supply, fixing, testing and commissioning of pole mounted junction of SMC model No. GSJB-3020 of SINTEX or similar make for terminating the incoming and outgoing cables and connecting wire of street lights. Junction box shall be complete with suitable connectors and fuse unit for streetlight. Complete unit shall be mounted on the pole by means of suitable hardware, terminal strips, cable glands, clamps etc. After erection of the pole in truly vertical position, it shall be painted with two coats of red oxide paint and one coat of enamel paint as per the colour decided by Railways. Enamel paint shall be of make Asian/Nerolac/ Berger. The coping/foundation above the ground level shall be white washed.
Providing LED based station name board in English, Hindi and Guajarati languages with controlling board, time switch and contactor - The price shall cover for design, fabrication, supply, installation, testing and commissioning of LED Station Name Boards at various stations in English, Hindi and Gujarati languages as per following description - The letters for the Station Name Board in English, Hindi and Gujarati languages shall be designed in separate boards at suitable locations with superior quality of acrylic sheet of Mitshubishi/Astari or equivalent make of minimum 2.0 mm thickness in red colour. The embossed height of the letter should be minimum 50 mm. The height of the letters should be 450 mm and the width shall be proportionate to the height. All the letters shall be fixed on white-coloured ACP sheet of minimum 3.0 mm thickness and the entire sheet shall be supported on a suitable 66 size of MS angle/Square Pipe frame from the back side to withstand wind pressure as advised by the site in-charge. The letters shall be illuminated from inside by providing Super Flux LED of low heat with extra bright light. The LED modules shall be made air tight, water proof and shock proof. One module of three LEDs shall be taken for every 9 square inch space approximately. The power LEDs shall be duly fixed in cups by silica gel or fusing gum. The LEDS shall be of Cree/Nichia/Osram/Phillips/Lumiled/Avago/Lednium/ADS/Seoul make. The LEDs are to be glued with the base of the acrylic letters along with appropriate wiring. The wiring shall be done carefully to avoid fusing. The LED modules shall be electrically connected with proper polarity. The SMPS, Drivers and Controllers for the LED module of suitable capacity and quantity shall be suitably selected and provided in weather proof, insect free box with proper ventilation. The input voltage to the drivers should be 230 Volt AC and the output voltage shall be 12/24 Volt DC. The SMPS are installed to regulate the voltage and wattage in the whole circuit which is to be precisely regulated. This shall be designed as per the site requirement. The acrylic sheet, LED modules, SMPS power supply, ACP sheet etc shall be got approved from site in-charge before fabrication.
Providing LED based "INDIAN RAILWAYS" logo board in Hindi and English languages of size 8 feet x 6 feet - The price shall cover for providing LED illuminated Glow Signage Logo Board. The scope of work involves design, fabrication, installation, testing and commissioning of LED illuminated Logo of INDIAN RAILWAYS and WESTERN RAILWAYS in Hindi and English as per the following specifications - The size of board shall be 8 feet x 6 feet. The board shall read as "INDIAN RAILWAYS" in Hindi and English on the periphery of the logo. The logo board shall be of box type fabricated from G.I. sheet of 22 SWG with a opening of suitable size with water tight gaskets at a suitable location for maintenance and connection purpose. The size of letter i.e. width and height shall be proportionate to the size of board size and the letters and stars shall be illuminated by providing super flux LED of low heat with extra bright light. One module of three LEDs shall be taken for every 9 square inch (approximately). The power LEDs shall be duly fixed in cups by silica gel or fusing gum. The LEDs shall be of Osram/Philips/GE/Lumiled/Wipro/Lednium make. The LEDs are to be glued with base of the acrylic letters along with wiring of appropriate size of flexible copper wire. The wiring has to be carefully done so as to avoid fusing. The LED module should be electrically connected with proper polarity. The SMPS, drivers and controllers for colour LED module shall be of suitable capacity and quantity and shall be 67 provided in a weather and vermin proof box with efficient ventilation and heat dissipation. The input voltage to the drivers shall be 230 Volt, 50 Hz AC and the output voltage shall be 24 Volt DC. The SMPS are installed to regulate the voltage and wattage of the complete circuit. The SMPS input voltage shall be in the range of 190 to 260 Volt, 50 Hz, AC and the output voltage shall be 9 to 24 Volt at Wattage of 48 to 150 Watt. This shall be designed as per the site requirement. All the letters and seventeen Stars shall be fixed on ACP sheet and the entire sheet shall be supported on a suitable size of MS angle frame from the backside to withstand the maximum wind pressure or as advised by site-in-charge. The logo shall be digitally printed using high quality vinyl sheet of 2 mm thickness or unbreakable polycarbonate sheet and shall be illuminated with LED tube lights of suitable rating and quantity to have uniform brightness. The LED Logo Sign Board shall be connected to electric supply in a proper manner and one Time Switch of daily dial type and Contactor of make L&T/BCH/C&S shall be provided to operate the board automatically. The Time Switch and the Contactor shall be fixed in a waterproof MS box provided with hinged door and pad locking arrangement. The box and M.S. angle frame structure shall be painted with two coats of red oxide primer and enamel paint of reputed make. The LED Logo Sign Board shall be fixed a suitable location on M.S angle frame of size 40 x 40 x 5 mm with requisite hardware to withstand gusty winds and storm. Before manufacturing of supporting structure the drawing shall be approved from the site supervisor. The entire structure shall be earthed properly. The colour code of LEDs, Letters and Stars shall be as per latest Railway Board norms. The Logo Board shall be provided at top of station building.
Design, manufacture, display, installation of wall/hanging/floor mounting type signage/directional boards in flat/half elliptical/ Parabolic/Triangular shape. The display sheet shall be of unbreakable 040 translucent polycarbonate sheet of 2.0 mm thickness. The text/graphics matter visibility shall not be less than 160 deg. The approved colour text and graphics shall be printed/router cut on monomeric calendared vinyl of 70 um thickness and shall be firmly pasted on display sheets/Retro Reflective Boards. The mounting arrangement shall be hanging, wall mounting, ceiling 68 mounting, pole mounting or floor mounting and as per site requirement to be provided by the contractor with their own materials, labour, all Tools & Plants, lead, lift, transportation etc including all applicable taxes. The signage shall have the integral mounting arrangements with sturdy structural frame and ACP cladding on the back side of the signage to avoid rusting and entry of dust. The scope of work covers Vadodara railway station. 1.0The work shall be carried out as per the "Guidelines on Standard Signages at Stations on Indian Railways, 2023" issued by the Ministry of Railways, Government of India. The work shall be executed strictly as per the specifications given in the document which is attached as Annexure. Colour scheme, font sizes, directional arrows, materials, fabrication, text, pictogram shall be as given in the document.
Providing PVC insulated and sheathed, single core, multi-stranded, Aluminium conductor cable, 10.0 sq. mm - The price shall cover for 69 supply of single core, PVC insulated and sheathed, stranded, Aluminium conductor of 10 sq. mm cross sectional area conforming to IS 1554 - Part-1. The cable shall be flame retardant, should not support combustion and shall be self-extinguishing and shall be of Johnson/Neo-cab/Nicco/Finolex/R.R. Kabel/Asian/Ecotek/L&T/Havell's/Polycab/Avocab make. The price shall also cover for laying of the cable for earth continuity from different points as advised by site engineer.
Providing GI earthing strip, 25 x 4 mm with PVC sleeve - The price shall cover for supply and laying of G.I. earthing strip of 25 x 4 mm size covered with black coloured PVC sleeve of superior quality from earth pit to control/distribution panel board. The earthing strip when laid on wall shall be fixed by means of suitable size of GI clamps and screws.
Providing maintenance free earthing - The price shall cover for providing maintenance free earthing as per the following specifications - 1. High tensile-low carbon steel rod having diameter not less than 17 mm complying with requirements of BS 4360 Grade 43A or EN10025:2-004 S275JR, molecularly bonded by 99.99% pure high conductivity copper on outer surface with copper coating thickness of 250 micron or more, Length 3000 mm (minimum). Certificates from NABL approved labs shall be submitted with test results. 2. Copper earth bus-bar of size 250 mm x 50 mm x 6 mm having electrical conductivity of 101% IACS, minimum 99.9% copper content shall be exothermically welded to rod with 4 holes of 12 mm diameter (two on each side) for connecting earthing conductor. 3. Earth Enhancement compound should have characteristics as mentioned in the RDSO specifications. It should have low resistivity preferably below 0.2 Ohm-meter, supplied in sealed bags (minimum 75 kg per pit for 5' x 5' x 10' size pit and minimum 50 kg per pit for 300 mm bore type pit. The bags shall be marked with manufacturer's name or trade name, quality, Batch No. and date of manufacture. Certificates from NABL approved labs shall be submitted with test results, for at least following parameters - i) Composition of Earth Enhancement compound ii) Resistivity - < 2 Ohm-meter iii) pH value - > 7 but < 9 iv) Moisture retaining capacity - > 10% at 105 degrees Celsius v) Water solubility - < 5% 4. Backfill material - Good quality soil or excavated soil free from sand, gravel and stones shall be used for backfilling. 5. Earth pit of size 5 feet x 5 feet x 10 feet or min 300 mm bore up to 10 feet using earth auger shall be made. 6. Inspection chamber - A concrete box of 300 x 300 x 300 mm (inside dimensions) and 50 mm thickness of wall, with smooth cement plaster finish shall be provided on the top of the pit. A concrete lid, painted black, approximately 50 mm thick with pulling hooks shall be provided to cover the earth pit. PVC sleeve shall be provided in concrete wall to take out earthing connections. 7. On backside of the cover, date of the testing and average resistance value shall be written with yellow paint on black background. 8. Instead of copper bus- bar and strips mentioned in the drawing, a GI main bus-bar of minimum size 300 mm x 75 mm x 8 mm to be installed on nearby wall etc. It shall be connected to earthing with two GI strips of 50 mm x 6 mm size each, up to a distance of 10 meters from earth bus-bar (minimum 3 meters x 2 Nos GI strips to be supplied). 9. Earthing shall generally be carried out in accordance with the requirement of I.E. Rules, 1956, as amended from time to time and shall confirm to IS: 3043 of 1987 with latest amendment. 10. The earth value shall be measured and recorded at the site by painting on earth pit or nearest wall along with date of testing. It shall be less than 2 Ohms and neutral to earth voltage shall be less than 3 Volt. 11. Earthing performance after a year of installation shall be jointly checked and measured. It should be less than 2 Ohm. 12. General arrangement of the earth system shall be as per the drawing given in Annexure-XXI of tender document.
Removal of unused existing redundant rail/round poles complete with over head line spans and other accessories and shifting the released 72 materials - The price shall cover for removal of existing rail/tubular poles and complete structure and other accessories by digging pole from base with required tools, tackles and manpower in a safe and secure manner. The dismantled rail/round poles, cross-arms, insulators, M.S. clamps, G.I. pipes and released fittings if any shall be segregated, transported and handed over to the site engineer at his office/stores with delivery challan. Above/
B- Facade Lighting Works
Supply, installation, testing and commissioning of exterior BIS standard RGBW LED linear Wall Washer luminary, 40 Watt for facade lighting with extruded aluminium housing, powder-coated finish, clear toughened glass of 4.0 mm thickness, die-cast end caps complete with dedicated 1 lens and all accessories - The price shall cover for supply, installation, testing and commissioning of high quality long through multi colour with RGBW four-in-one LED, DMX-RDM based linear wash light. Protection Rating - IP-66, complying to BIS standard "IS: 10322 (Part 5/Sec 1) - 2012" and having CE certification against standard "Low Voltage Directive and Protective Equipment - EN 60598 (Part 2/Sec 1) - 2020" and "Electromagnetic Compatibility Directive - EN 61547 - 2020". Detailed specifications are given in Annexure-XXI of tender document.
Supply, installation, testing and commissioning of exterior BIS standard RGBW LED Flood Lighting luminary, 40 Watt for facade lighting with die-cast aluminium housing, powder-coated finish, clear toughened glass of 4.0 mm thickness complete with all necessary accessories required for 2 proper working of fixture including weather-proof connection cables, water proof connectors etc. as required - The price shall cover for supply, installation, testing and commissioning of high quality long through multi colour with RGBW four-in-one LED, DMX-RDM based wash light. Protection Rating - IP-66, complying to BIS standard "IS 10322 (Part 5/Sec 1) - 2012" and having CE certification against standard "Low Voltage Directive and Protective Equipment - EN 60598 (Part 2/Sec 1) - 2020", and "Electromagnetic Compatibility Directive - EN 61547:2020". Detailed specifications are given in Annexure-XXI of tender document.
Supply, installation, testing and commissioning of exterior BIS standard RGBW LED Flood Lighting luminary, 130 Watt for facade lighting 3 with die-cast aluminium housing, powder-coated finish, clear toughened glass of 4.0 mm thickness. Luminary shall conform to IS: 10322 (Part 5/Sec 5) and shall be complete with all necessary accessories required for proper working of fixture including weatherproof connection cables, water proof connectors etc. as required. Detailed specifications are given in Annexure-XXI of tender document.
Supply, installation, testing and commissioning of Digital Multiplex (DMX) Controller for the facade lighting system including all other accessories required for the smooth running of the system. The facade lighting products and DMX controller should be of same/single make with IP: 66 enclosures. Detailed specifications are given in Annexure-XXI of tender document.
Providing Digital Multiplex (DMX) supply cable, 1.0 meter long, four-pin (male) - The price shall cover for supply, fixing, testing and commissioning of Digital Multiplex supply cable of 1.0 meter length, four-pin (male) to reliably transmit digital control signals and low-voltage power to 5 specific stage lighting fixtures. Core Specifications - Cable Length - 1.0 meter, Connector Type - four-pin XLR (male), Characteristic Impedance - 110 nominal (standard for DMX512), Conductor Material - Stranded Oxygen-Free Copper (OFC), Shielding - Braided tinned copper and aluminum/mylar foil to prevent electromagnetic interference, Jacket Material - Flexible, durable, and weather-resistant PVC. Standard Pinout Configuration - In a 4-pin DMX configuration, the pins are typically allocated as follows - Pin 1 - Data Common/Shield (Ground), Pin 2 - Data (Primary Data Complement), Pin 3 - Data + (Primary Data True) and Pin 4 - Secondary Data/Secondary Return/Low-Voltage Power.
Providing Digital Multiplex (DMX) supply cable, 1.0 meter long, four-pin (female) - The price shall cover for supply, fixing, testing and commissioning of Digital Multiplex supply cable of 1.0 meter length, four-pin (female) for advanced LED stage lighting and color-changing fixtures to 6 transmit DMX512 data and low-voltage power along the same cable. Core Specifications - Cable Length - 1.0 meter, Connector Type - four-pin XLR (female), Characteristic Impedance - 110 nominal (standard for DMX512), Conductor Material - Stranded Oxygen-Free Copper (OFC), Shielding - Braided tinned copper and aluminum/mylar foil to prevent electromagnetic interference, Jacket Material - Flexible, durable, and weather-resistant PVC. Standard Pinout Configuration - In a 4-pin DMX configuration, the pins are typically allocated as follows - Pin 1 - Data Common/Shield (Ground), Pin 2 - Data (Primary Data Complement), Pin 3 - Data + (Primary Data True) and Pin 4 - Secondary Data/Secondary Return/Low-Voltage Power.
Providing Digital Multiplex (DMX) extension cable, 1.0 meter long, four-pin - The price shall cover for supply, fixing, testing and commissioning of four-pin Digital Multiplex extension cable of 1.0 meter length for specialized lighting setups and connecting specific LED fixtures to carry both low-voltage power and DMX data signals in a single cable. Core Specifications - Cable Length - 1.0 meter, Connector Type - four-pin XLR (male 7 to female), Characteristic Impedance - 110 - 120 nominal (Optimized for digital AES/EBU and DMX512 signal transmission to prevent signal reflection), Conductor Material - Stranded Oxygen-Free Copper (OFC), Shielding - Braided shielding + Aluminum/Mylar foil (to block electromagnetic and radio frequency interference), Jacket Material - Flexible, durable, and weather-resistant PVC, Signal Protocol - EIA-485 and DMX512 standard. Pinout Configuration - Pin 1 - Data Ground / Signal Common, Pin 2 - Data (Primary Data Complement), Pin 3 - Data + (Primary Data True) and Pin 4 - Secondary Data/ Power.
Providing Digital Multiplex (DMX) extension cable, 3.0 meter long, four-pin - The price shall cover for supply, fixing, testing and commissioning of four-pin Digital Multiplex extension cable of 3.0 meter length for specialized lighting setups and connecting specific LED fixtures to carry both low-voltage power and DMX data signals in a single cable. Core Specifications - Cable Length - 3.0 meter, Connector Type - four-pin XLR (male 8 to female), Characteristic Impedance - 110 - 120 nominal (Optimized for digital AES/EBU and DMX512 signal transmission to prevent signal reflection), Conductor Material - Stranded Oxygen-Free Copper (OFC), Shielding - Braided shielding + Aluminum/Mylar foil (to block electromagnetic and radio frequency interference), Jacket Material - Flexible, durable, and weather-resistant PVC, Signal Protocol - EIA-485 and DMX512 standard. Pinout Configuration - Pin 1 - Data Ground / Signal Common, Pin 2 - Data (Primary Data Complement), Pin 3 - Data + (Primary Data True) and Pin 4 - Secondary Data/ Power.
Supply, installation, testing and commissioning of exterior BIS registered RGBW flexible LED Strip. The LED Strip should have 60 Nos LEDs per meter. Wattage - 14.4 Watt per meter - The price shall cover for supply, installation, testing and commissioning of exterior BIS registered RGBW flexible LED Strip as per the specifications mentioned below - General and Physical Specifications - • LED Type - SMD 5050 4-in-1 (RGB + White in a single chip) • LED Density - 60 LEDs per meter (300 LEDs per 5-meter reel) • Wattage - 14.4 Watts per meter • Operating Voltage - DC 12 Volt or DC 24 Volt • 9 Ingress Protection - IP67 (Silicone tube or extruded sheath, suitable for outdoor/exterior installations) • Strip Width - Typically 10 mm to 12 mm • Backing - 3M Double-sided adhesive tape for easy installation Optical and Performance Specifications - • Light Color - Millions of possible RGB colors + dedicated White (typically Warm White 2700K-3000K or Cool White 6000K) • Beam Angle - 120° • System Lumen Efficacy - 80 Lumens per Watt • System Lumens - 1200 Lumens per meter • Lifespan - L70B50 at 35,000 to 50,000 burning hours • Cut Interval - Cuttable every 3 LEDs (typically every 50 mm for 12 Volt or 100 mm for 24 Volt strips) Safety and Compliance - • BIS Certification - Registered under BIS CRS (Compulsory Registration Scheme) mandatory for LED lighting in India. • Operating Temperature - -20°C to +50°C • Certifications: CE, RoHS, and ISO Certified (vendor-dependent)
Providing Digital Multiplex (DMX) RGBW decoder, 12/24 Volt, 480 Watt capacity - The price shall cover for supply, installation, testing and commissioning of Digital Multiplex (DMX) four-channel RGBW decoder rated for 12/24Volt and 480 Watt to convert standard DMX512 signals into PWM (Pulse Width Modulation) for LED strips. The 480 Watt capacity shall generally operate as four channels running at 5 Amp per channel at 24 Volt as per 10 the specifications mentioned below - Core Specifications - • Input Voltage - 12 Volt DC to 24 Volt DC (automatically adaptable) • Maximum Total Power Capacity - 240 Watt at 12 Volt, 480 Watt at 24 Volt • Channels - Four Channels (Red, Green, Blue, White) • Maximum Output Current - 20 Amp (5 Amp per channel) Control and Dimming - • Input Signal - DMX512/1990 standard • Output Signal - Constant Voltage PWM • Dimming Range - 0 to 100% smooth dimming • Grayscale Levels - 256 levels per channel Physical and Connections - • Data Connections - Standard RJ45 or XLR-3 ports, with terminal blocks • Address Settings - Usually configured via side-mounted DIP switches or digital numeric display screen • Enclosure - Typically IP-20 rated for indoor use, housed in rugged metal or heavy-duty plastic Operating Environment - • Working Temperature - -20°C to 50°C or 60°C • Cooling - Relies on natural convection, requires good ventilation if operated at maximum 480 Watt load
Providing Instruction Forwarder Ranger and Compass / AC Strip - The price shall cover for supply, installation, testing and commissioning of 11 Instruction Forwarder Ranger and Compass / AC strip high-powered, high-performance, architectural RGBW LED wall washers and floodlights designed for professional facade and landmark illumination for outdoor, long-distance illumination, color-washing and highlighting architectural structures. The unit shall feature intelligent logarithmic control technology and polarized light design operated via DMX systems for dynamic colour changing as per the specifications mentioned in Annexure-XXI of tender document.
Providing RGBW female connector with five-pin 1.0 meter wire, IP-67 rated - The price shall cover for supply, fixing, testing and 12 commissioning of RGBW female connector with five-pin 1.0 meter wire, IP-67 rated designed for outdoor, marine and wet-location LED lighting installations (like decking and landscape lighting) to ensure safe, dust-tight and waterproof power and signal transmission as per the specifications mentioned in Annexure-XXI of tender document.
Providing RGBW extension wire, five-pin ,1.0 meter length, IP: 67 rated - The price shall cover for supply, fixing, testing and commissioning of RGBW 1.0-meter extension wire designed for color-changing LED strips and outdoor spotlights, providing waterproof, solder-less power routing as per 13 the specifications mentioned below - Length - 1.0 meter IP Rating - IP-67 (Waterproof and dust-tight, suitable for both indoor and outdoor/garden use) Pin Configuration - Five-Pin (supports Red, Green, Blue, White, and common positive/ground) Connector Type - Includes male-to-female waterproof screw-on or plug-and-play connectors on both ends Wire Material - High-quality UL2464 or PVC-insulated exterior with tin-plated copper wire internally Voltage and Wattage Rating - Supports 12 Volt to 24 Volt DC systems (up to 72 Watt capability) Certifications - CE and RoHS compliant
Providing CS junction box, three-way - The price shall cover for supply, fixing and commissioning of Fire retardant, waterproof junction box/cable termination box for LED driver, outdoor type, weatherproof and shockproof, UV Resistant, Ingress protection - IP-67, Impact resistance - IK-08, Material - High grade thermo plastic/Glass Fiber reinforced polyester, Sealing - Durable Polyurethane, Cover screw - Stainless steel V2A, Corrosion 14 resistant. The cable/conduit entry shall be via metric knockouts for easy termination with suitable capacity terminal block having heavy duty moulded nylon encased connectors that use screw compression to secure the copper conductors, suitable for internal terminations and external outgoing connecting points with required PVC/ brass glands of suitable size, suitable size MCB fitted for controlling outgoing circuits. Boxes shall be certified in accordance with IEC-60670, IEC-60998 with latest amendments. Make of junction boxes - Hensel/Cape Electric or similar. Material shall be procured from OEM/Authorized Distributer of OEM and proof of purchase shall be submitted along with copy of Test Certificate.
Providing LED constant voltage driver, 250 Watt, 24 Volt, 10.5 Amp capacity - The price shall cover for supply, fixing, testing and 15 commissioning of 250 Watt/10.5 Amp capacity, 24 Volt DC LED Driver, Constant Voltage Design, Input voltage range within 140 to 270 Vrms. Operating input voltage - 240 Vrms AC. Protection - Short Circuit/Over Load/Over Voltage/Over Temperature. Cooling by free air convection. Waterproof - IP-66 or more. The driver card shall withstand 440 Volt normal and 3 KV ±3% surge protection. Driver shall be of isolated type. BIS certificate must be submitted along with the supply. Driver should be UL/ CE/RoHS certified.
Providing Colorscape universal address writer - The price shall cover for supply, fixing, testing and commissioning of dedicated handheld programming tool Colorscape Universal Address Writer to assign digital DMX512 addresses to individual RGB/RGBW architectural lighting nodes on building facades to enable localized control and allow uniform dynamic color sequencing as per the specifications mentioned below - Purpose - Single-key, wireless/wired DMX512 address assignment and testing Compatibility - Shall work directly with DMX drivers, LED facade lights, wall washers, and pixel 16 nodes Display - High-contrast LCD/OLED screen for reading and writing data Programming - Supports both automatic incremental addressing and manual keypad entries Connectivity - Standard DMX input/output terminals (usually 3-pin or 4-pin waterproof connectors) Power - Rechargeable Lithium-ion battery for portability, with USB-C or DC charging Material - ABS/Polycarbonate rugged enclosure, suitable for construction sites DMX Compatibility - The address writer shall be used alongside a Master DMX512 Controller and DMX software. It gives every lighting fixture a specific channel so the controller knows exactly where it is on the building. Setup Requirements - To complete the facade setup, this writer shall be used in combination with DMX Decoders, DMX Amplifiers, and IP-rated LED fixtures (like wall grazers and linear lights).
Providing Digital Multiplex (DMX) amplifier, four-pin, M-12 - The price shall cover for supply, fixing, testing and commissioning of DMX amplifier for improving/amplifying input signals through long distances. The scope of work includes supply of DIN Rail DMX Signal Amplifier to amplify, distribute, and insulate the signal that comes from the lighting system equipment when it is connected to the bus of DMX512 (or RS-485), 1CH input - 2CH 17 output designed for signal shaping amplification for DMX512 (485) signal which attenuates after a long-distance transmission, realize extending the signal transmission distance, using the multiple signals expansion output control, increase DMX (485) signal amplifier to distribute multi-channel control, 1CH input - 2CH distributed output. There shall be photoelectric insulation between input and output terminals so as to avoid the expensive equipment such as luminaries, 485 communications equipment, DMX driver, precise digital lighting controller etc being burnt by possible high voltage which may be caused due to the wrong wire connection or a broken equipment which can also avoid the signal interference between each DMX equipment so as to ensure that it works safely. Input Voltage - 12 to 24 Volt DC, Photoelectric Insulation Voltage - 1 KV.
Supply, installation, testing and commissioning of Digital Multiplex (DMX) Splitter with input voltage range of 190 to 240 Volt AC, Power Consumption - 5 Watt (maximum) - The price shall cover for supply, fixing, testing and commissioning of DMX isolator or splitter to provide eight (8) 18 outputs from one (1) input. Product features - Group 1 and group 8 DMX signal change. DMX Splitter and booster, Input Power - 12 to 24 Volt, 100 to 240 Volt with 24 Volt DC plug-in power adaptor included. Power Consumption - 5 Watt (maximum). Housing shall be made of polycarbonate, surface mount or DIN-rail mountable, operating temperature range - 0° to 50°C, Output - Six three-pin terminal sockets, Connections - Two piece compression screw terminals, Protection Rating - IP-20 for Interior applications. UL/cUL /CE Certification. The unit shall be provided with IP-67 enclosure if installed in external environment.
Supply, installation, testing and commissioning of signal amplifier to boost the signal - The price shall cover for supply, fixing, testing and commissioning of Signal Amplifier to boost the signal to prevent voltage drops, signal distortion and flickering. Signal Amplifiers are essential for long cable runs. 1. General Electrical Specifications - • Input Voltage - DC 5/12/24 Volt (must match with the LED driver and strip operating voltage) • Output Current Capacity - 10 to 24 Amp • Output Power - Maximum 288 Watt for 12 Volt systems and 576 Watt for 24 Volt systems. 2. Protocol-Specific 19 Specifications - • DMX512 Systems (Architectural Buildings): o Features - Optically isolated data lines to prevent ground loops and protect controllers from power surges. o Compatibility - RS-485 differential signals. o Repeater Distance - Extends the DMX signal by up to 100 to 120 meters per amplifier without latency. • SPI / Pixel Systems (Media Facades and Video Walls) - o Features - Must support specific IC types like WS2811, WS2812B, UCS1903, or TM1804. o Output Channels - Multi-channel outputs (4 or 8 channels) to drive multiple parallel strings or clock/data lines. • PWM Systems (Static/Single-Color or basic RGB) - o Features - Synchronizes the Pulse Width Modulation (PWM) signal perfectly with the main controller to ensure color uniformity across the entire facade. 3. Environmental and Physical Specifications - • Ingress Protection (IP) Rating - IP-65 to IP-67 for outdoor weatherproof installations. • Enclosure Material - Aluminum housing for superior heat dissipation. • Operating Temperature - -20° C to 60° C to withstand regional weather fluctuations.
Providing Address writer - The price shall cover for supply, fixing, testing and commissioning of DMX address writer (or coder) for facade lighting. The DMX address writer shall be a handheld or portable programming tool used to assign individual DMX512 addresses to LED fixtures (like wall washers and nodes). It shall ensure that the main controller sends the correct data to each specific light on the building as per the specifications mentioned below - Compatible Protocols - DMX512, RDM, UCS512, TM512, SM16512, UCS512C, etc Display Type - OLED or LCD Touch Screen (for clear 20 visibility in direct sunlight) Data Interface / Ports - Three-Pin/Four-Pin XLR, RJ45, or specialized waterproof terminals (ADD, DAT, GND, VCC) Data Input Method - Built-in keypad, SD Card (for batch programming/test effects) or mobile app via Bluetooth Operating Voltage - 5 to 24 Volt DC (usually charged via standard USB or directly from the fixture's power line) Housing Material - Impact-resistant ABS plastic or lightweight aluminum alloy Operating Environment - -10°C to +50°C Key Functions One-Key Addressing - Instantly writes start address codes to decoding driver ICs without needing to configure them manually. Parameter Setting - Adjusts channel modes (e.g. setting RGB v/s RGBW light), brightness modulation and pixel groupings. System Testing - Contains built-in test effects (jump, gradual change, chasing, flow) to ensure the fixture's LEDs are wired correctly before connecting to the central master controller.
Service charges for Digital Multiplex (DMX) programming and commissioning - The price shall cover for providing service charges for Digital Multiplex (DMX) programming and commissioning which involves the technical configuration, custom coding and real-time mapping of lighting systems. Typical Specifications - Protocol Standards - Conforms to USITT DMX512-A protocols for flicker-free control. System Integration - Mapping of dynamic color changes, dimming, and standalone devices (such as PA systems or architectural scheduling). Device Addressing - Assigning individual start addresses to LED fixtures and configuring decoders/drivers. Custom Sequencing - Programming static presets, dynamic effects, and time-based show events (seasonal, holiday, or architectural timelines).
Supply, installation, testing and commissioning of BIS Registered LED wall washer suitable for outdoor environment with IP 65 protection IS: 10322 (Part 5 - Sec 1) and IS: 15885 (Part 2 - Sec 13) LED Brilliant Round wall washer 4 Watt, CTI 3000° K, 320 Lumens, dark grey color, length - 69 mm and width - 69 mm. Detailed specifications are given in Annexure-XXI of tender document.
Providing M-15, three-pin female supply cable, 1 meter long - The price shall cover for supply, fixing, testing and commissioning of M-15, female supply cable, three-pin, outdoor-rated, waterproof extension cord designed to bridge power from drivers or controllers to LED luminaries. It shall feature a threaded locking mechanism and durable weatherproof construction to withstand harsh environments as per the specifications mentioned below 23 - • Cable Length - 1.0 meter • Connector Type - M15, three-pin female (Circular thread-lock) • Pin Configuration - three-pins (Line / Phase, Neutral, Ground/Earth) Electrical and Mechanical Properties - • Rated Voltage - Up to 300 Volt AC/DC • Rated Current - 8 to 10 Amp (depending on the manufacturer's model) • Wire Gauge - 0.5 sq. mm to 1.5 sq. mm depending on current drawing requirements • Mechanical Life - Typically rated for 1500 to 3000 mating cycles Materials and Environmental Ratings - • Waterproof Rating - IP-67 or IP-68 • Operating Temperature - -40°C to +105°C • Housing Material - Flame-retardant Nylon (PA66) • Contact Material - Gold-plated or tin-plated brass/copper alloy.
Providing M-15, three-pin extension cable, 1 meter long - The price shall cover for supply, fixing, testing and commissioning of M-15, heavy-duty, outdoor-rated interconnect designed, three-pin extension cable for LED facade lighting and wall washers. It shall feature weather-resistant, threaded, screw-lock connections that ensure secure power and data transmission while protecting lighting systems from extreme environmental 24 conditions. Core Specifications - • Cable Length - 1.0 meter • Pin Configuration - Three-pin (Live, Neutral, and Earth/Ground) • Waterproof Rating -IP-67 to IP-68 (Fully submersible and dust-tight) • Rated Voltage - 300V AC/DC • Rated Current - 8A to 10A (depending on the wire gauge) • Operating Temperature - -40°C to +105°C (handles harsh, sun-baked exterior environments) Materials and build - • Connector Shell - Flame-retardant Nylon PA66 • Contacts/Pins - Gold-plated or tin-plated brass/copper • Cable Jacket - UV-stabilized, flame-retardant PVC or rubber • Wire Gauge - Typically utilizes multi- core 18AWG to 16AWG conductors for low voltage drops across your facade • Coupling Style - Threaded / Screw-lock with silicone sealing rings
Providing M15, three-pin extension cable, 3 meter long - The price shall cover for supply, fixing, testing and commissioning of M-15, heavy- duty, outdoor-rated interconnect designed, three-pin extension cable for LED facade lighting and wall washers. It shall feature weather-resistant, threaded, screw-lock connections that ensure secure power and data transmission while protecting lighting systems from extreme environmental 25 conditions. Core Specifications - • Cable Length - 3.0 meter • Pin Configuration - Three-pin (Live, Neutral, and Earth/Ground) • Waterproof Rating -IP-67 to IP-68 (Fully submersible and dust-tight) • Rated Voltage - 300V AC/DC • Rated Current - 8A to 10A (depending on the wire gauge) • Operating Temperature - -40°C to +105°C (handles harsh, sun-baked exterior environments) Materials and build - • Connector Shell - Flame-retardant Nylon PA66 • Contacts/Pins - Gold-plated or tin-plated brass/copper • Cable Jacket - UV-stabilized, flame-retardant PVC or rubber • Wire Gauge - Typically utilizes multi- core 18AWG to 16AWG conductors for low voltage drops across your facade • Coupling Style - Threaded / Screw-lock with silicone sealing rings Above/
C- LED Fittings
Providing four-feet long, 18/20 Watt LED fitting complete with all accessories and LED tube - The price shall cover for supply of 1 x 18/20 Watt LED batten fitting. The fixture shall be of CRCA channel finished with white polyester powder coating with high UV and corrosion resistance. The fixture shall be equipped with end caps, push fit type lamp holders and mains connector to directly fix 4 feet long LED tube. The LED lamp shall be of 1 18/20 Watt. The fitting shall conform to Western Railways' specification no. WR/CCG/Specification/P/001 (Rev. 01) - 2018. The tube shall be of polycarbonate material. The entire fixture shall be of reputed quality and make. The price shall also cover for fixing testing and commissioning of the complete fitting at site by means of bracket made from GI flat of 25 x 3 mm with nuts, bolts and washers or on heavy duty, ISI marked PVC square box as per site requirement. Connection shall be given by means of 24/0.2 mm three-core flexible copper wire through connector and heavy duty flexible PVC conduit. Removal of existing fittings along with brackets and handing over the same to the site in-charge is included in the scope of work.
Supply and fixing of 15/18 Watt LED down lighter - The price shall cover for supply, fixing, testing and commissioning of 15/18 Watt LED luminary operating on 230 Volt, 50 Hz AC supply. The fitting shall conform to Western Railways' specification no. WR/CCG/Specification/P/001 (Rev. 01) - 2018 and shall be of reputed quality and make. The fitting shall be of pressure die cast aluminum suitable for surface/recessed mounting with high 2 efficiency Polycarbonate diffuser. Luminous flux - 2000 lumen, rated luminous efficacy - 110 lumen/Watt, CCT - 6500 deg K, Colour rendering index (CRI) - 80, SDCM - < 5, iTHD - < 10%, Power Factor - 0.95, Median useful life L70B50 @ Ta - 45° C 50,000 burning hours, surge protection level - 2.5 kV with aluminum die cast housing. The fitting shall be fixed at site by means of suitable size of GI Clamps/PVC block as decided by site engineer. The connection shall be given by means of 24/0.2 mm three-core flexible copper wire through proper connector. The fitting arrangement shall be as per the aesthetics of the room. Removal of existing fittings and handing over the same to the site engineer at his store is included in the scope of work.
Supply, fixing, testing and commissioning of LED fitting 2 feet x 2 feet, 36/38 Watt recessed/surface mounted complete with all accessories - The price shall cover for supply, fixing, testing and commissioning of eco-friendly, maintenance free and energy efficient LED module, 2 feet x 2 feet of 36/38 Watt ±3 Watt made from CRCA housing with high efficiency diffuser for full glow and constant current electronic driver suitable for 220 - 3 240 Volt, 50 Hz AC supply. The fitting shall conform to Western Railways' specification no. WR/CCG/Specification/P/001 (Rev. 01) - 2018 and shall be of reputed quality and make. The fitting shall be suitable for recessed/surface mounting arrangement. The fitting shall be fixed at site by means of suitable size of GI Clamps/PVC block as decided by site engineer. The connection shall be given by means of 24/0.2 mm three-core flexible copper wire through proper connector. The fitting arrangement shall be as per the aesthetics of the room. Removal of existing fittings and handing over the same to the site engineer at his store is included in the scope of work.
Supply, fixing, testing and commissioning of LED street light luminary, 45 Watt ±10% complete with all accessories - The price shall cover for supply of 45 Watt LED Street Light fitting made from pressure die-cast LM6/ADC12/ LM24 housing with optimal heat sink for better thermal dissipation and toughened glass or UV stabilized polycarbonate cover with high transmission index for superior light output. The fitting shall conform to Western Railways' specification no. WR/CCG/Specification/P/001 (Rev. 01) - 2018 and shall be of reputed quality and make. The fitting shall be designed for IP: 65 4 class protection for pole/bracket mounting. The fitting shall be provided with special moisture proof vent. The price shall also cover for fixing, testing and commissioning of the above street light fitting on pole/truss/roof/wall by fabrication and supply of 'B' class G.I. pipe of required length, diameter and shape and fixed with M.S. clamps made from M.S. flat of 40 x 5 mm size duly painted with nut, bolts and washers of 12 mm diameter. The connection to the luminary shall be carried out through three-core, 1.0 sq. mm, FRLS PVC insulated, ISI marked, flexible copper wire through connector and heavy-duty flexible PVC conduit as per site conditions from the existing overhead line/catenary/junction box as per site conditions. The connection cord shall be protected by suitable size of heavy duty, flexible PVC conduit. Removal of existing fittings along with pipe and clamps and handing over the same to the site in-charge is included in the scope of work.
Supply, fixing, testing and commissioning of 70 Watt LED street light fitting - The price shall cover for supply of energy efficient LED Area light/flood light luminary 60 to 70 Watt capacity with luminous efficacy of 100. The luminary shall be made from pressure die cast aluminium housing, toughened front glass cover, fitted with secondary optics, heat sink and integrated electronic driver for long life with IP: 65 protection suitable for working on 240 Volt, 50 Hz AC supply. The fitting shall conform to Western Railways' specification no. WR/CCG/Specification/P/001 (Rev. 01) - 2018 and shall be of 5 reputed quality and make. The price shall also cover for fixing, testing and commissioning of LED street light fitting on existing pole/wall by supply of 'B' class G.I. pipe of suitable size and length duly fixed with M.S. fabricated clamps made from 40 x 6 mm M.S. flat with G.I. nuts-bolts as per site condition. The connection to the luminary shall be carried out through three-core, 1.0 sq. mm, FRLS PVC insulated, ISI marked, flexible copper wire through connector and heavy-duty, flexible PVC conduit as per site conditions from the existing overhead catenaries/pole mounted junction box or as per site condition in medium grade PVC conduit. Supply of PVC wire, PVC conduit, bakelite connector etc. is inclusive in the scope of work. Removal of existing fittings and handing over the same to the site in-charge is included in the scope of work.
Supply, fixing, testing and commissioning of four-feet suspended linear light, IP-20 with 50 mm width - The price shall cover for supply, installation, testing and commissioning of four-feet suspended linear light with system lumen output of 2500 lumens @ 6500 deg K CCT and CRI - >80. The luminary shall be supplied with LED Driver with operating voltage range of 140 to 270 Volt AC, PF - >0.95, iTHD - <10% and 4 KV surge protection 6 inbuilt inside the driver. The luminary should conform to Western Railways' Specification No. WR/CCG/ Specification/P/001 (Rev. 01) - 2018 or latest. The fitting shall be of reputed quality and make. The fitting shall be fixed at site by means of suitable size of GI Clamps/PVC block as decided by site engineer. The connection shall be given by means of 24/0.2 mm three-core flexible copper wire through proper connector as per site requirement. The fitting arrangement shall be as per the aesthetics of the room. Removal of existing fittings and handing over the same to the site engineer at his store is included in the scope of work.
Supply, fixing, testing and commissioning of Extruded Aluminium Linear LED luminary with IP 54/65 protection - The price shall cover for supply, installation, testing and commissioning of Extruded Aluminum Linear LED luminary, IP 54/65 as per site condition (in case of indoor installation the fitting shall be IP 54 and in case of outdoor installation the fitting shall be IP 65) to be decided by railways. Depth of the luminaire (without driver) should not be greater than 35 mm. The housing shall be constructed of extruded aluminum. System lumen output of 4000 lumens @ 6500 deg K, CCT and CRI - >80. The luminary shall be supplied with LED Driver with operating voltage 140 to 270 Volt AC, iTHD - <10%, P.F. - >0.95 and inbuilt 4 KV protection inside the driver. The luminary should conform to Western Railways' Specification No. WR/CCG/Specification/P/001 (Rev. 01) - 2018 and shall be of reputed quality and make. The fitting shall be fixed at site by means of suitable size of GI Clamps/PVC block as decided by site engineer. The connection shall be given by means of 24/0.2 mm three-core flexible copper wire through proper connector as per site requirement. The fitting arrangement shall be as per the aesthetics of the room. Removal of existing fittings and handing over the same to the site engineer at his store is included in the scope of work.
Supply, fixing, testing and commissioning of energy efficient, LED post top luminary, 45 Watt with luminous efficacy of 100 Lumens/Watt, IP: 65/66 protection, complete with all accessories - The price shall cover for supply, fixing, testing and commissioning of outdoor type LED post top light fittings complete with all accessories on pole. The LED fixture shall have following design criteria - • Main Housing: Cast Aluminium metal in PU painted finish • LED: LM80 certified LED • Heat sink: Aluminium section. • Lumen maintenance: 50,000 Hrs @ L70 • Rated voltage & frequency: 240V, 50Hz AC • LED Make: Cree/Nichia/Osram/Lumileds/Philips Post top luminary shall confirm to model No. SLE PT 40W RIGEL of Surya or equivalent of HPL/Phillips/CG/ 8 Bajaj/Wipro/Jaguar/Havells make. The make and model No. of the luminary shall be got approved from Sr. DEE (Power) BRC before supply. Post top luminary shall be mounted on powder coated, 'B' Class M.S. pipe of 75 mm diameter. The colour and shade shall be decided by Railways. The length of the pole shall be 3.5 meter above the ground level. Junction box for termination of incoming and outgoing cables on each pole shall be provided at a height of 300 mm from ground level. Holes shall be provided in the pipe to accommodate incoming and outgoing cables. The junction box shall be fitted with four-way heavy-duty connector, 15 Amp -1 No, MCB SP, 6 Amp -1 No and rubber gasket and grommets for proper sealing. The foundation having ratio of 1:2:4 of 0.125 cubic meter volume provided with partially threaded 4 No, 175 mm x 12 mm size MS bolt with nut grouted in foundation. Pole shall be fixed with foundation bolts of appropriate size. The connection to the luminary shall be carried out through ISI marked, PVC insulated, flexible, three- core copper wire of size 24/0.20 mm from the existing junction box. Above/
D- Supply, Installation, Testing and Commissioning of Luggage Lift
Supply, erection, testing and commissioning of Luggage Elevator (Lift), Ground + 1 as per CPWD's specifications - The price shall cover for 1 Supply, erection, testing and commissioning of Luggage Elevators (Lifts) of 2000 kg capacity, Ground + 1, minimum speed 1.00 meter per second, having openings at single/both sides as per site conditions and as per CPWD's General Specification for Electrical Works (Part III - Lifts and Escalators), 2003. The Elevators shall be of machine room-less and gear-less design. Details are given in Annexure-XXI of tender document. CPWD's General Specification for Electrical Works (Part III - Lifts and Escalators), 2003 is enclosed in the list of documents.
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
HTML
nit.pdf
NIT
SignagesStandardSizesPtI.pdf
ATTACHMENT
SignagesStandardSizesPtII.pdf
ATTACHMENT
TenderDocument-BRC-EL-P-17-2508-09-58-26-27NEWGCC_1.pdf
ATTACHMENT
BankGuaranteeverification.pdf
ATTACHMENT
WesternRailwaysSpecificationsforACBLTPanelsMCCBandMCB.pdf
ATTACHMENT
RailwayBoardsletterNo.2018_CE-I_CT_9dated04.06.18.pdf
ATTACHMENT
TechSpecsofEnergyEfficientLEDBasedLuminaire.pdf
ATTACHMENT
2024_06_03InstructionforincorporatingtheJPOCircularetc_ProvisionsintheTenderDocumentforallworksrequiringdiggingworksclosetoRly1.pdf for cable
ATTACHMENT
2024_06_03InstructionforincorporatingtheJPOCircularetc_ProvisionsintheTenderDocumentforallworksrequiringdiggingworksclosetoRly1.pdf
ATTACHMENT
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at [email protected].