Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹36.7 LAccepted-AOC 9 8 B THENGUMTHARAVIL MLA ROAD PANANGAD PO KOCHI 682506 | KOCHI | ERNAKULAM | KERALA | 682506 | ₹36.7 L Quoted ₹37.6 L | L1 | Accepted-AOC L1 |
| 2 | L2₹37.7 LRejected-AOC DOOR NO 68 2963 E3 MANDAKKARA ROAD AYYAPPANKAVU ERNAKULAM KERALA 682 018 | ERNAKULAM | ERNAKULAM | KERALA | 682018 | ₹37.7 L | L2 | Rejected-AOC L2 |
| 3 | L3₹44.1 LRejected-AOC N A | ₹44.1 L | L3 | Rejected-AOC L3 |
| 4 | L4₹48.2 LRejected-AOC DOOR NO 42 2237 KRISHNA BEHIND ERNAKULAM MEDICAL CENTRE CENTURY CLUB ROAD VENNALA KOCHI 682028 | KOCHI | ERNAKULAM | KERALA | 682028 | ₹48.2 L | L4 | Rejected-AOC L4 |
| Sl No | Description | Qty | Unit | SKYLIGHT INNOVATIONS L3 | AAG INDIA PVT LTD L4 | T.I.John and Sons L1 | ELAN ENGINEERS L2 |
|---|---|---|---|---|---|---|---|
| 1.00 | Material and labour for annual maintenance contract for fire hydrants, fire alarm & gas suppression system installed at DHRUV(Bridgeman shIp simulator) building for one year Minimum one visit in every three months period shall be carried out and the scope include following works : | 4 | Each Job | 60,000 ₹2.4 L | 1,94,000 ₹7.8 L | 2,80,000 ₹11.2 L | 2,85,000 ₹11.4 L |
| 2.00(a) AMC for fire alarm system (Bosch) :- (i) Testing of entire fire alarm system during site visit such as General servicing of manual call points including cleaning, checking etc. once in three months. (ii) General servicing of hooter including cleaning. (iii) General servicing of fire alarm panel including cleaning, checking & clearance of false alarm and reprogramming of panel complete all as specified and directed | |||||||
| 3.00(b) AMC for fire fighting & hydrant system:- (i) Testing of entire fire fighting system , once in three month. (ii) General checking and servicing of Pumps and Diesel engine set etc which includes cleaning, painting, greasing, battery checking filling of distilled water etc. (iii) General servicing of hydrants valves, butterfly valves, NRV's, pressure gauges,sprinklers,pipes, pressure switches etc including cleaning , polishing, replacement of washers (if required) etc. (iv) General servicing of hose box including cleaning, painting replacement of beading (if required) etc. (v) servicing of fire hose Set, including cleaning, drying and etc. (vi) servicing of hose reel including cleaning, cheaking of hose , shutt off nozzle (vii) Major spare parts and components of equipments, overhauling of pumps & engine, coil changing, rewinding of motors, battery etc will be provided additionally. (viii) Cleaning and painting of fire fighting tank of 3.5 lakh ltr capacity. | |||||||
| 4.00(c) AMC for gas suppression system(Siemens):- (i) Includes checking of gas suppression system during site visit, once in every three months. (ii) General checking and simulation of suppresion system using spare cylinders. (iii) Checking of discharge lines, working of electromagnetic devices / solenoid valves, directional valves, nozzels, gauges etc, and cleaning of components etc. (iv) General servicing of manual release switches, abort switches tec include cleaning, checking etc. (v) General servicing of gas release panel and device including cleaning, checking & clearance of false alarm and reprogramming of panel complete all as specified. . Note:- Every break down complaints/ calls shall be attended within 48 hrs. | |||||||
| 5.00 | Material and labour for removing the unserviceable winding from the induction motor 10-15hP capacity including cleaning the starter slots,rewinding with appropriate size and or existing super enamelled copper winding wire and insulating to the existing class of insulation, cleaning the starter assembly including fixing of terminal,copper lugs etc.testing and assembling complete all as specified and as directed. | 1 | Each Job | 18,000 ₹18,000 | 43,500 ₹43,500 | 15,000 ₹15,000 | 18,000 ₹18,000 |
| 6.00 | Supply and replace of detectors base for addressable type multisensor detector with heat and smoke combination complete all as specified and directed. | 260 | Each | 650 ₹1.7 L | 300 ₹78,000 | 150 ₹39,000 | 200 ₹52,000 |
| 7.00 | Supply and replace of detectors complying with addressable type multisensor detector with heat and smoke combination complete all as specified and directed. | 96 | Each | 3,900 ₹3.7 L | 5,500 ₹5.3 L | 4,800 ₹4.6 L | 4,500 ₹4.3 L |
| 8.00 | Supply and replace of heat detectors complying with and type certified to EN-45 addressable type heat detector with base with rate of rise cum fixed temperature as per IS: 2175 complete all as specified and directed. | 4 | Each | 3,800 ₹15,200 | 5,300 ₹21,200 | 4,500 ₹18,000 | 4,300 ₹17,200 |
| 9.00 | Supply and replace of remote response indicators complete all as specified and directed. | 10 | Each | 200 ₹2,000 | 500 ₹5,000 | 100 ₹1,000 | 150 ₹1,500 |
| 10.00 | Supply and replace of Intelligent analog addressable mutisensory /Flasher cum speaker (ceiling mounted) having inbuilt CPU and in line Isolator. Programmable sound output goes upto 92dB. There shall be 19 diff tones to select complete all as specified and directed.global approval - EN54/ VdS | 2 | Each | 9,800 ₹19,600 | 18,550 ₹37,100 | 10,000 ₹20,000 | 8,900 ₹17,800 |
Tender Value
Refer Docs
EMD Value
₹99,960
Closing Date
1 Aug 2025, 6:00 pmClosed
GE NS KOCHI
Military Engineer Services Garrison Engineer (Naval Services) Kataribagh, Naval Base Post Kochi 682004.
COMPREHENSIVE MAINTENANCE / REPAIR AND SERVICING OF GSFFSYSTEM, FIRE ALARM, FIRE FIGHTING AND SPRINKLER SYSTEM INSTALLED AT ISC DHRUV (BLDG NO. P-409), NAVAL BASE KOCHI AND REPAIR AND MAINTENANCE
2025_MES_717979_1
8525/E8
Open Tender
Electrical and Maintenance Works
330 days
KOCHI
Please refer Tender documents.
7 documents required · 7 mandatory
₹500
GE NS KOCHI
₹99,960
Yes
12 Feb 2026
2 Jul 2025
4 Aug 2025
2 Jul 2025
1 Aug 2025
17 Jul 2025
2 Jul 2025 - 3 Jul 2025
Amount
Material and labour for annual maintenance contract for fire hydrants, fire alarm & gas suppression system installed at DHRUV(Bridgeman shIp simulator) building for one year Minimum one visit in every three months period shall be carried out and the scope include following works :
(a) AMC for fire alarm system (Bosch) :- (i) Testing of entire fire alarm system during site visit such as General servicing of manual call points including cleaning, checking etc. once in three months. (ii) General servicing of hooter including cleaning. (iii) General servicing of fire alarm panel including cleaning, checking & clearance of false alarm and reprogramming of panel complete all as specified and directed
(b) AMC for fire fighting & hydrant system:- (i) Testing of entire fire fighting system , once in three month. (ii) General checking and servicing of Pumps and Diesel engine set etc which includes cleaning, painting, greasing, battery checking filling of distilled water etc. (iii) General servicing of hydrants valves, butterfly valves, NRV's, pressure gauges,sprinklers,pipes, pressure switches etc including cleaning , polishing, replacement of washers (if required) etc. (iv) General servicing of hose box including cleaning, painting replacement of beading (if required) etc. (v) servicing of fire hose Set, including cleaning, drying and etc. (vi) servicing of hose reel including cleaning, cheaking of hose , shutt off nozzle (vii) Major spare parts and components of equipments, overhauling of pumps & engine, coil changing, rewinding of motors, battery etc will be provided additionally. (viii) Cleaning and painting of fire fighting tank of 3.5 lakh ltr capacity.
(c) AMC for gas suppression system(Siemens):- (i) Includes checking of gas suppression system during site visit, once in every three months. (ii) General checking and simulation of suppresion system using spare cylinders. (iii) Checking of discharge lines, working of electromagnetic devices / solenoid valves, directional valves, nozzels, gauges etc, and cleaning of components etc. (iv) General servicing of manual release switches, abort switches tec include cleaning, checking etc. (v) General servicing of gas release panel and device including cleaning, checking & clearance of false alarm and reprogramming of panel complete all as specified. . Note:- Every break down complaints/ calls shall be attended within 48 hrs.
Material and labour for removing the unserviceable winding from the induction motor 10-15hP capacity including cleaning the starter slots,rewinding with appropriate size and or existing super enamelled copper winding wire and insulating to the existing class of insulation, cleaning the starter assembly including fixing of terminal,copper lugs etc.testing and assembling complete all as specified and as directed.
Supply and replace of detectors base for addressable type multisensor detector with heat and smoke combination complete all as specified and directed.
Supply and replace of detectors complying with addressable type multisensor detector with heat and smoke combination complete all as specified and directed.
Supply and replace of heat detectors complying with and type certified to EN-45 addressable type heat detector with base with rate of rise cum fixed temperature as per IS: 2175 complete all as specified and directed.
Supply and replace of remote response indicators complete all as specified and directed.
Supply and replace of addressable manual call point resettable type complete all as specified and directed.
Supply and replace of hooter/sounder cum strobe complete all as specified and directed.
Supply and replace of addressable monitor module complete all as specified and directed.
Supply and replace of analog addressable multisensor detector with blue LED(OT blue detector) source of optical ray to identify open or fast fire signature -specially catering to TF1 & pes of fires as prescribed by EN54.It shall also comprise of additional heat detector sensor with decentralise intelligence, soft addressability with inbuilt fault isolator complete all as specified and directed.
Supply and replace of Intelligent analog addressable mutisensory with two inbuilt optical smoke ensures with backward & forward scattering light angles eliminating false fire signatures as well as additional heat detector sensor with decentralise intelligence (OTG detector), soft addressable photo thermal type with inbuilt fault isolator complete all as specified and directed. Temp range of this detector shall be confined between - 20 Deg C to + 65 Deg C
Supply, Installation, testing and commissioning of intelligent addressable type active loop repeater fire terminal, backlite LCD display, having controls for reset, mute, accept, slience alarms and selftest, with progarammable free keys and duly approved by EN-54 complete all as specified and directed
Supply and fixing of 2x1.5 Sqmm (FRLS) armoured copper cable ISI marked with proper clamping, supports and terminations complete all as specified and directed.
Supply and fixing of 2X2.5 Sqmm FRLS armoured copper cable ISI marked with proper clamping, supports and terminations complete all as specified and directed.
Supply and replace of butterfly valve reflux ,with by pass Arrangement ,100 mm dia complete all as specified and directed.
Supply and replace of butterfly valve reflux ,with by pass Arrangement,80 mm dia complete all as specified and directed.
Supply and replace of hydrant Landing Valve Type A (single head outlet )of 63 mm dia complete all as specified and directed.
Supply and replace of hose reel of 20 mm dia and 30 Meter Length complete all as specified and directed.
Supply and replace of sprinkler quick/early response type , pendent type, set to operate at 68 degree C complete all as specified and directed.
Supply and replace of flow switch 80 mm dia complete all as specified and directed.
Supply and replace of pressure gauge Ar / N2 complete all as specified and directed.
Supply and replace of microprocessor gas release panel for each protected area triggered in 2 stage action having additional features like easy on-site configuration, upload & download datas, identification of origin of events, display countdown timer before extinguishing release etc. and extinguishing automatic activation with various alarm combinations, 72 hour battery backup time, automatic calibration facility for actuator's control lines (solenoid or pyrotechnical actuators), manual release button for manual activation of extinguishing, Emergency hold button to temporarily stop the extinguishing or abort button to cancel the initiated extinguishing release as long as the pre-warning time is running, Remote transmission facility for transmitting alarms and faults etc in compliance with EN standards complete all as specified and directed.
Supply, Installation, testing and commissioning in replacement of of micro controlled base intelligent power distribution panel,Incomer supply spot,output 230 volt alternating current and 24 volt direct current distribution in the panel providing single switch operation in signboard lights and lobby lights.Stablity powersupply in fire alarm control panel . Defend voltage fluctuations in the panel and this panel acts as a ensure the smooth functioning of the control panel by providing a ressistance shield against any voltage variation coming to the control panel complete all as specified and directed
Pipe galvanized 'heavy class' including fittings laid in trenches or fixed to walls and ceilings or laid in floors of the following dia complete all as specified and directed.
150 mm dia
100 mm dia
80 mm dia
65 mm dia
50 mm dia
40 mm dia
32 mm dia
25 mm dia
Supply and fix in replacement of swing type wafer check valve of size 150 mm DI type body SS disc with rating of PN-1.0 complete all as specified and directed
Supply and fix in replacement of swing type wafer check valve of size 80 mm DI type body SS disc with rating of PN-1.0 complete all as specified and directed
Supply and replace of loop card for fire alarm panel complete all as specified and directed
Supply and replace of network card for the fire alarm panel complete all as specified and directed
Supply and replace of mechanical seal for 70 mtr head and 2850/2640 LPM wet riser system complete all as specified and directed
Supply and replace of Impeller bronze for 70 mtr head and 2850/2640 LPM capacity pump complete all as specified and directed
Supply and replace of spider coupling for 85/75 HP pump set complete all as specified and directed
Supply and replace of battery 12V 150AH suitable for 85 HP DD engine pump complete all as specified and directed
Supply and replace of engine oil grade 20 W-40 complete all as specified and directed
Supply and replace of coolant complete all as specified and directed
Supply and replace of oil filter suitable for 85 HP DD engine pump complete all as specified and directed
Supply and replace of fuel filter set suitable for 85 HP DD engine pump complete all as specified and directed
Supply and replace of air filter set suitable for 85 HP DD engine pump complete all as specified and directed
Supply and replace of LED Indicator with Red, Yellow, Blue and Green colour complete all as specified and directed
Supply and replacement of gas cylinder valve suitable 140 ltr capacity IG 541 complete all as specified and directed
Caliberation test of pressure guages of IG 541 gas cylinders 140 L capacity and submitt the report from authorised agency complete all as specified and directed
Supply and repalce of power supply unit for fire alrm panel complete all as specified and directed
Material and labour for attending any type of leakage/shortage/overflow in water supply distribution lines laid at various locations inside Kataribagh and INS Garuda area for detection of nature of defect including carry out minor repairs to make the distribution line functional complete all as specified and directed. Notes :- (a) The unit rate quoted shall be deemed to be included the elements of labour only for arresting the leakage and making the supply line functional for minor repair such as releasing air locks, clearing float valve blockages and checking any closed valves alongwith the supply, putting an end cap, etc. If replacements of pipe/items is required to make the supply line functional, the cost of labour and material for the same shall be measured and paid as "Supply & fix/Material & labour in repairs" under relevant items of this schedule here in after. (b) If leakage/shortage shall not be attended & rectified in the same day as received by the contractor except major break down, the recovery will be made @ Rs 500/- per breakdown per day and after 15 days of non functional of any distribution line, as specified for any reason, the recovery will be made @ 2000/- per day till the distribution line functional
Excavation in trenches not exe. 1.5 M in depth and not exe 1.5 M in width including getting out for laying pipes etc including forming bottom surface to required level in soft/loose soil complete all as specified and directed.
Returning, refilling including spreading levelling watering and well ramming in layers not exce. 25 cm thick complete all as specified and directed.
Removing the surplus soil to a distance not exe. 50 M and depositing where directed at a level not exe. 1.5 M from the starting point complete all as specified and directed.
Supply and laying 100 mm inner dia of CPVC pipes with CPVC Sch 40 pipes & plain Sch 80 fittings and jointed with CPVC primer & solvent cement laid trenches including taking down old unserviceable PVC/PP-R/ GI Tubing, laid in trenches , complete all as specified and directed.
All as per item No 58 here-in-before but of size 75 mm dia complete all as specified and directed.
Supply and fix in repairs in trenches high pressure CPVC pipes SDR-13.5 & plain CPVC SDR 11 fittings including all necessary fittings, solvents of size 50 mm dia complete all as specified and directed.
All as per item No 60 here-in-before but of size 40mm dia complete all as specified and directed.
All as per item No 60 here-in-before but of size 25mm dia complete all as specified and directed.
Supply and laying 100 mm inner dia of CPVC pipes with CPVC Sch 40 pipes & plain sch 80 fittings and jointed with CPVC primer & solvent cement including taking down old unserviceable PVC/PP-R/ GI Tubing, laid on wall/concealed on wall/floor, complete all as specified and directed.
All as per item No 63 here-in-before but of size 75 mm dia complete all as specified and directed.
Supply and fix in repairs on wall/concealed on wall high pressure CPVC pipes SDR-13.5 & plain CPVC SDR 11 fittings including all necessary fittings, solvents of size 50 mm dia including taking down old unserviceable PVC/PP-R/ GI tubing complete all as specified and directed.
All as per item No 65 here-in-before but of size 40 mm dia complete all as specified and directed.
All as per item No 65 here-in-before but of size 25mm dia complete all as specified and directed.
All as per item No 65 here-in-before but of size 20mm dia
Supply and fix in repairs CPVC Ball Valve of size 50 mm dia suitable for CPVC pipe incl necessary fittings and taking down old one complete all specified and directed.
All as per item No. 69 here-in-before but of size 40 mm dia complete all as specified and directed.
All as per item No. 69 here-in-before but of size 25 mm dia complete all as specified and directed.
All as per item No.69 here-in-before but of size 20 mm dia complete all as specified and directed.
Demolition of cement concrete in ground floors and paving n exc 15cm thickness, above ground level in the foundation complete all as specified and directed.
Material and labour for cement concrete in foundations, filling and mass concrete 1:3:6 type C2 (40mm graded stone aggregate) complete all as specified and directed.
Supply and fix in repairs Gun metal Gate/Globe valve with iron wheel head, screwed both ends suitable for fixing with CPVC pipe of outer dia 50mm, complete all as specified and as directed by the Engineer-in-charge.
Supply and fixing CI butterfly valve 100 mm suitable for CPVC pipe/DI pipe with necessary fittings complete all as specified and directed.
All as per item No 76 here-in-before, but 80 mm dia complete all as specified and directed.
Material and labour for construction of brick masonry valve pit of size 1.2 x 1.2 x 0.9 Mtrs(internal dimensions) including excavation and earth work in any type of soil, PCC 1:2:4 type B-2 in foundation brick work in CM 1:4, 15mm thick plastering in CM 1:4 internally and flush pointing externally in same mortar as the work process angle iron frame work 40X40X6mm, with 6mm thick MS sheet cover with 12 mm dia handle and locking arrangement (including lock and two Keys) and two coats of synthetic enamel paint over a coat of red oxide primer complete all as specified and directed by Engr-in-Charge including demolition of old valve pits
Supply and fix in repairs in replacement of 2000 litre capacity rotational moulded polyethylene water storage tanks( ISI marked) (cylindrical vertical with closed top) hoisted & fixed in position including taking down old one complete all as specified and directed
All as per item No 79 here-in-before but 1000 litre capacity complete all as specified and directed.
All as per item No 79 here-in-before but 500 litre capacity complete all as specified and directed.
Supply and fix in repairs 40 mm bore float valve synthetic (PVC) high pressure with polythene ball of suitable size and flynut including taking out old one complete all as specified and directed.
All as per item No 82 here-in-before but 25 mm bore complete all as specified and directed.
All as per item No 82 here-in-before but 20 mm bore complete all as specified and directed.
Supply and fix in replacement of CPVC flanges of Size 62.5 mm complete all as specified and as directed
All as per item No 85 here-in-before but 75 mm bore complete all as specified and directed.
All as per item No 85 here-in-before but 100 mm bore complete all as specified and directed.
Supply and fix in repairs, 15 mm size chromium plated fancy type bib taps, half turn with flange and aerator, short body, cast copper alloy with crutch or butterfly handle, screwed for GI/PVC pipe, complete including taking down old one complete all as specified and directed by the Engineer in charge
Supply and fix in repairs, 15 mm size chromium plated cast copper alloy bib cock short body with flange and nozzle for garden/washing machine complete including taking down old one all as specified and directed by the Engineer in charge
Material and labour for MS plates (plain or chequered) channels, square cut or notched (ordinary and counter sunk) forming holes, without any attachment any size for making cover for valve pits including nuts,bolts, washers, welding, bending cold or hot drilling holes for bolts, in any shape of size as indicated or directed and inclusive of one primer coat one under coat and one finishing coat of synthetic enamel paint (black colour) including taking out old petted corroded plates complete all as specified and directed.
ELAN ENGINEERS (BID ID -3379809)
SKYLIGHT INNOVATIONS (BID ID -3371257)
AAG INDIA PVT LTD (BID ID -3371395)
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid