Loading…
Loading…
Tender Value
₹30 L
EMD Value
₹40,000
Closing Date
2 Sept 2026, 6:00 pm
Executive Engineer, RANDER DIVISION
RND-525 : For Work of ARC for Erection & Maintenance of HT/LT Line and TC work and other Maintenance work of O/H Line & UG XLPE Cable laying & commissioning of UG Cable with as per REC Norms for Ramnagar Sub Division under Rander Division under All Scheme and if required for work to be carried out in any other sub division under Rander Division. (The work to be carried out in all Scheme).
337853
RND-525 : DGVCLDRND/0244/08/2026 Approved Date: 21-08-2026
Open
Electrical - All
Works
Surat
3 documents required · 3 mandatory
₹1,180
SURAT
₹40,000
21 Aug 2026
21 Aug 2026
21 Aug 2026
2 Sept 2026
21 Aug 2026
Schedule-B for Work of ARC for Erection & Maintenance of HT/LT Line and TC work and other Maintenance work of O/H Line &
UG XLPE Cable laying & commissioning of UG Cable with as per REC Norms for Ramnagar Sub Division under Rander Division
under All Scheme and if required for work to be carried out in any other sub division under Rander Division. (The work to be
carried out in all Scheme)
PART-A : 1 : HT, LT & TC WORK & O/H UG XLPE CABLE
PART-A : 1 : CAPITAL WORK LABOUR RATES FOR FY 2024-25 (WITHOUT GST)
Item Code Item Unit FY 2024-25
HT TAPPING FROM THE EXISTING POLE INCLUDING FIXING OF CROSS ARMS,
CLAMPS ANTI-CLIMBING DEVICES, DANGER BOARD, INSULATORS ETC.
1 9926000001 COMPLETE AND PAINTING OF FABRICATED MATERIALS AND NUMBERING No.
COMPLETE WITH COST OF PAINTS AS PER STANDARD SPECIFICATION BUT
EXCLUDING ERECTION OF GUY SET AND EARTHING.
ERECTION OF PSC POLES OF 8 *200 KG INCLUDING EXCAVATION OF PIT AND
REFILLING OF EARTH, FIXING OFCROSS ARMS, TOP FITTING CLAMPS ANTI-
CLIMBING DEVICES, INSULATORS ETC. COMPLETE AND PAINTING OF
FABRICATED MATERIALS USED ON THE POLES AND NUMBERING WITH COST
OF PAINT AS PER STANDARD SPECIFICATION BUT EXCLUDING ERECTION OF
GUY SET AND EARTHING.
ERECTION OF STEEL POLES OF 9 TO 11 METERS INCLUDING EXCAVATION OF
PIT AND REFILLING OF EARTH, FIXING OFCROSS ARMS, TOP FITTING CLAMPS
ANTI-CLIMBING DEVICES, DANGER BOARD, INSULATORS ETC. COMPLETE AND
PAINTING OF STEEL POLE, FABRICATED MATERIALS USED ON THE POLEAND
NUMBERING WITH COST OF PAINT AS PER STANDARD SPECIFICATION BUT
EXCLUDING ERECTION OF GUY SET AND EARTHING.
ERECTION OF STEEL POLE OF 13 METERS FOR RAILWAY CROSSING ON
BG/MG/NG LINE FOR 0.400/11/22KV OVERHEAD LINES I.E INCLUDING
EXCAVATION OF PIT & REFILLING OF EARTH, FIXING CROSS ARMS, TOP
4 9926000004 FITTING CLAMPS,ANTI-CLIMBING DEVICES DANGER BOARD, INSULATORS ETC. No.
COMPLETE AND PAINTING OF STEEL POLES, FABRICATED MATERIALS USED
ON THE POLES AND NUMBERING WITH COSTOF PAINT AS PER STANDARD
SPECIFICATION BUT EXCLUDING ERECTION OF GUY SETS AND EARTHING.
ERECTION OF DOUBLE POLE STRUCTURE OF 8 METERS 200 KG PSC POLES
INCLUDING EXCAVATION OF PITS & REFILLING OF EARTHING, FIXING OF
CHANNELS, SUPPORTING ANGLES,CLAMPS, ANTI-CLIMBING DEVICES DANGER
5 9926000005 BOARDS,INSULATORS ETC.COMPLETE AND PAINTING OF FABRICATED No.
MATERIALS USED ON THE POLES AND NUMBERING WITH COST OF PAINT AS
PER STANDARD SPECIFICATION BUT EXCLUDING ERECTION OF GUY SETS AND
EARTHING.(WITHOUT AB SWITCH)
ERECTION OF DOUBLE POLE STRUCTURE OF 9 TO 11 METERS.STEEL POLE
INCLUDING EXCAVATION OF PITS & REFILLING OFEARTH, FIXING OF
CHANNELS, SUPPORTING ANGLES, CLAMPS,ANTI-CLIMBING DEVICES DANGER
6 9926000006 BOARDS, INSULATORS ETC.COMPLETE & PAINTING OF POLES,FABRICATED No.
MATERIALSUSED ON THE POLES AND NUMBERING WITH COST OF PAINTSAS
PER STANDARD SPECIFICATION BUT EXCLUDING ERECTION OF GUY SET AND
EARTHING.(WITHOUT AB SWITCH)
ERECTION OF DOUBLE POLE STRUCTURE WITH MOUNTING OF AB SWITCH, HG
FUSES OF 8 MTRS 200 KG PSC POLES INCLUDING EXCAVATION OF PITS AND
REFILLING OF EARTH,FIXING OF CHANNELS SUPPORTING ANGLES, CLAMPS,
7 9926000007 ANTI-CLIMBING DEVICES, DANGER BOARDS, INSULATORS,DOFUSES ETC. No.
COMPLETE AND PAINTING OF FABRICATED MATERIALS USED ON THE POLES
AND NUMBERING WITH COSTOF PAINT AS PER STANDARD SPECIFICATION BUT
EXCLUDINGOF ERECTION OF GUY SET AND EARTHING.(WITH AB SWITCH)
ERECTION OF DOUBLE POLE STRUCTURE WITH MOUNTING OF AB SWITCH,HG
FUSES, 9 TO 11 METERS STEEL POLES INCLUDING EXCAVATION OF PITS AND
REFILLING OF EARTH, FIXING OFCHANNEL, SUPPORTING ANGLES, CLAMPS,
8 9926000008 ANTI-CLIMBING DEVICES , DANGER BOARDS, INSULATORS, ETC. COMPLETE No.
AND PAINTING OF POLES FABRICATED MATERIALS USED ON THE POLES AND
NUMBERING WITH COST OF PAINT AS PER STANDARD SPECIFICATION BUT
EXCLUDING ERECTION OF GUY SET AND EARTHING.(WITH AB SWITCH)
ERECTION OF DOUBLE POLE STRUCTURES WITH MOUNTING OFAB SWITCH,
HG FUSES, TRANSFORMERS, LIGHTENING ARRESTORS, DISTRIBUTION BOX.
OF 8 METER,200KG PSC POLE METERS POLES INCLUDING EXCAVATION OF
PITS AND REFILLING OF EARTH, CARTING OF TRANSFORMERS FROMSTORES
9 9926000009 TO SITE, FIXING OF CHANNELS, SUPPORTING ANGLES,BRACINGS CROSS ARMS No.
CLAMPS, ANTICLIMBING DEVICES DANGER BOARDS, CONDUCTOR AND CABLE
WIRING ETC.COMPLETE AND PAINTING OF FABRICATED MATERIALS USEDON
THE POLES AND NUMBERING WITH COST OF PAINT AS PER STANDARD
SPECIFICATION BUT EXCLUDING ERECTION OF GUY SETS AND EARTHING.
ERECTION OF DOUBLE POLE STRUCTURE WITH MOUNTING OF AB SWITCH,HG
FUSES TRANSFORMERS, LIGHTENING ARRESTORS, DISTRIBUTION BOX 9 TO
METERS STEEL POLES INCLUDING EXCAVATION OF PITS & REFILLING OF
EARTH CARTING OF TRANSFORMERS FROM STORE TO SITE, FIXINGOF
10 9926000010 CHANNELS SUPPORTING ANGLES, BRACING, CROSS ARMS,CLAMPS, No.
ANTICLIMBING DEVICES, DANGER BOARDS,CONDUCTOR AND CABLE WIRING
ETC. COMPLETE AND PAINTING OF POLES FABRICATED MATERIALS USED ON
THE POLES AND NUMBERING AS PER STANDARD SPECIFICATION BUT
EXCLUDING ERECTIONS OF GUY SETS AND EARTHING.
ERECTION OF GUY SET INCLUDING EXCAVATION OF PITS & REFILLING OF
EARTH AS PER STANDARD SPECIFICATION WITH STAY CLAMPS, STAY WIRE,
ANCHOR ROD, TURN BUCKLE, EYEBOLT, GUY INSULATOR, CEMENT CONCRETE
BLOCK ETC. BUT EXCLUDING CONCRETING.
CONCRETING OF POLES, GUYS, ETC. INCLUDING COST OF CEMENT SAND
12 9926000012 METAL (1:2:4) AND WATER ETC. AS PER STANDARD SPECIFICATION.(cement CMT
Should be 53 grade) used for Concreting.
ERECTION OF COIL TYPE EARTHING INCLUDING COST OF COAL,SALT ETC. BUT
13 9926000013 WITHOUT COST OF GI WIRE AS PER STANDARD SPECIFICATION(20kg solt+20kg No.
ERECTION OF GI PIPE/CI PLATE TYPE EARTHING INCLUDINGCOST OF COAL
14 9926000014 SALT ETC. BUT WITHOUT COST OF PIPE/GIPLATE GI WIRE AS PER STANDARD No.
SPECIFICATION.(20kg solt+20kg coal)
ERECTION OF STREET LIGHT FIXTURE COMPLETE WITH CLAMPS, BRASS
15 9926000015 NIPPLE, BRASS HOLDER TECK WOOD BUSH,REFLECTORS FUSE, WIRING ETC. No.
AS PER STANDARD SPECIFICATION BUT EXCLUDING COST OF MATERIALS.
STRINGING OF(30mm2)ACSR/34MM@,55MM2 AAA CONDUCTOR for ALL TYPE OF ONE
16 9926000016 CONDUCTOR (EXCEPT DOG CONDUCTOR) FOR 11/22KV & LT LINES INCLUDING COND
FIXING OF INSULATORS, BINDING JUMPERING ETC. PER KM
17 9926000017 STRINGING OF GI WIRE 8 SWG INCLUDING BINDING JUMPERING ETC. DO
PROVIDING SINGLE PHASE SERVICE CONNECTION WITH PVC 2.5/4MM2 TWIN
CORE CABLE FROM TERMINAL POLE TO METERING POINT INCLUDING FIXING
OF METER WITH METER EARTHING COMPLETE WORK AS PER STANDARD
SPECIFICATION BUT EXCLUDING COST OF MATERIALS.
PROVIDING THREE PHASE 4 WIRE SERVICE CONNECTION WITH PVC
4MM2/10MM2 FOUR CORE CABLE FROM TERMINAL POLE TO METERING POINT
INCLUDING FIXING OF METER WITH METER EARTHING COMPLETE WORK AS
PER STANDARD SPECIFICATION BUT EXCLUDING COST OF MATERIALS.
ADDITIONAL COST FOR EXCAVATION OF PIT IN HARD ROCK AREA FOR
ERECTION OF POLE/ GUY ETC. AS PER STANDARD SPECIFICATION OVER &
20 9926000020 ABOVE NORMAL COST COVERED AGAINST EXCAVATION OF PIT UNDER No.
NORMAL SOIL FOR ERECTION OF POLE,GUY, DOUBLE POLE STRUCTURE
EARTHING WITH THE APPROVAL OF SUPDT.ENGINEER.
21 9926000021 PROVIDING GUARDING TO HT LINE ON ROAD/ RAIL CROSSING. MTR
22 9926000022 PROVIDING GUARDING OF LT LINES ON ROAD/RAIL CROSSING. MTR
23 9926000023 LT LINE TAPPING- SINGLE PHASE No.
24 9926000024 LT LINE TAPPING- THREE PHASE No.
Stringing/LAYING OF OVER HEAD LT CABLE FOR ROAD CROSSING,HT LINE
CROSSING AND TELEPHONE LINE CROSSING ETC.(PER SPAN)
ERECTION OF SINGLE POLE STRUCTURES WITH , HG FUSES,TRANSFORMERS,
LIGHTENING ARRESTOR, DISTRIBUTION BOX. ON 8 METERS 200 KGAND PSC
POLE INCLUDING EXCAVATION OF PITS AND REFILLING OF EARTH, CARTING
OF TRANSFORMERS FROM STORES TO SITE, FIXING OF CHANNELS,
26 9926000026 SUPPORTING ANGLES,BRACINGS CROSS ARMS CLAMPS, ANTICLIMBING No.
DEVICES DANGER BOARDS, CONDUCTOR AND CABLE WIRING ETC.COMPLETE
AND PAINTING OF FABRICATED MATERIALS USED ON THE POLE AND
NUMBERING WITH COST OF PAINT AS PER STANDARD SPECIFICATION BUT
EXCLUDING ERECTION OFGUY SETS AND EARTHING.
ERECTION OF SINGLE POLE STRUCTURES WITH MOUNTING OFAB SWITCH
HG FUSES,TRANSFORMERS, LIGHTENINGARRESTOR, DISTRIBUTION BOX. ON
9 to 11 METERS RSJ POLE INCLUDING EXCAVATION OF PITS AND REFILLING OF
EARTH, CARTING OF TRANSFORMERS FROM STORES TO SITE, FIXING OF
27 9926000027 CHANNELS, SUPPORTING ANGLES,BRACINGS CROSS ARMS CLAMPS, No.
ANTICLIMBING DEVICES DANGER BOARDS, CONDUCTOR AND CABLE WIRING
ETC.COMPLETE AND PAINTING OF FABRICATED MATERIALS USED ON THE
POLE AND NUMBERING WITH COST OF PAINT AS PER STANDARD
SPECIFICATION BUT EXCLUDING ERECTION OFGUY SETS AND EARTHING.
ERECTION OF PSC POLES OF 10 *270 KG INCLUDING EXCAVATION OF PIT AND
REFILLING OF EARTH, FIXING OF CROSS ARMS, TOP FITTING CLAMPS ANTI-
CLIMBING DEVICES, INSULATORS ETC. COMPLETE AND PAINTING OF
FABRICATED MATERIALS USED ON THE POLES AND NUMBERING WITH COST
OF PAINT AS PER STANDARD SPECIFICATION BUT EXCLUDING ERECTION OF
GUY SET AND EARTHING.
ERECTION OF DOUBLE POLE STRUCTURE OF 10 METERS 270 KG PSC POLES
INCLUDING EXCAVATION OF PITS & REFILLING OF EARTHING, FIXING OF
CHANNELS, SUPPORTING ANGLES,CLAMPS, ANTI-CLIMBING DEVICES DANGER
29 9926000029 BOARDS,INSULATORS ETC.COMPLETE AND PAINTING OF FABRICATED No.
MATERIALS USED ON THE POLES AND NUMBERING WITH COST OF PAINT AS
PER STANDARD SPECIFICATION BUT EXCLUDING ERECTION OF GUY SETS AND
EARTHING.(WITHOUT AB SWITCH)
STRINGING OF 100MM2 ACSR/100MM2 AAAC CONDUCTOR FOR 11/22KV & LT
LINES INCLUDING FIXING OFINSULATORS, BINDING JUMPERING ETC.
STRINGING OF DOG CONDUCTOR FOR 11/22KV & HT LINES INCLUDING FIXING
OF INSULATORS, BINDING JUMPERING ETC.
ERECTION OF DOUBLE POLE STRUCTURES WITH MOUNTING OF AB SWITCH,
HG FUSES, TRANSFORMERS, LIGHTENING ARRESTORS, DISTRIBUTION BOX.
OF 10 METERS 270 KGAND PSC POLES INCLUDING EXCAVATION OF PITS AND
REFILLING OF EARTH, CARTING OF TRANSFORMERS FROMSTORES TO SITE,
32 9926000032 FIXING OF CHANNELS, SUPPORTING ANGLES,BRACINGS CROSS ARMS No.
CLAMPS, ANTI-CLIMBING DEVICES,DANGER BOARDS, CONDUCTOR AND CABLE
WIRING ETC.COMPLETE AND PAINTING OF FABRICATED MATERIALS USED ON
THE POLES AND NUMBERING WITH COST OF PAINT AS PER STANDARD
SPECIFICATION BUT EXCLUDING ERECTION OF GUY SETS AND EARTHING.
DISMENTALLING OF 8 MTR PSC POLE WITH CREDITING OF FABRICATION AT
33 9926000033 STORE & STACKING OF POLE SAFELY ON ROAD SIDE OR CREDITING TO No.
DEPARTMENTAL STORE
DISMENTALLING OF 10 MTR PSC POLE WITH CREDITING OF FABRICATION AT
34 9926000034 STORE & STACKING OF POLE SAFELY ON ROAD SIDE OR CREDITING TO No.
DEPARTMENTAL STORE
DISMENTALLING OF TRANSFORMER CENTRE (8 MTR PSC POLE) (WITH
TRANSFORMER) WITH CREDITING OF FABRICATION & TRANSFORMER AT
STORE & STACKING OF POLE SAFELY ON ROAD SIDE OR CREDITING TO
DEPARTMENTAL STORE
DISMENTALLING OF TRANSFORMER CENTRE (8 MTR PSC POLE) (WITHOUT
36 9926000036 TRANSFORMER) WITH CREDITING OF FABRICATION AT STORE & STACKING OF No.
POLE SAFELY ON ROAD SIDE OR CREDITING TO DEPARTMENTAL STORE
STRINGING OF LT ABC OF 1*35 SQ MM + 1*25 SQ MM INCLUDING FITTING OF ALL
ACESSARIES I.E. SPECIAL DESIGN SUSPENSION / TENSION CLAMP, FIXING OF
CROSS ARM, LT SHACKLE INSULATOR ETC. FOR FIXING OF MESSENGER WIRE
AND TO PROVIDE SERVICE CONNECTION ON AERIAL BUNCH CABLE BY
INSULATED PIERCEING CONNECTORS THROUGH SERVICE CONNECTION BOX
COMPLETE AS REQUIRED & DIRECTED BY ENGINEER IN CHARGE.
STRINGING OF LT ABC OF 3*50 SQ MM +1*25 SQ MM+1*35 SQ MM INCLUDING
FITTING OF ALL ACESSARIES I.E. SPECIAL DESIGN SUSPENSION / TENSION
CLAMP, FIXING OF CROSS ARM, LT SHACKLE INSULATOR ETC. FOR FIXING OF
38 9926000038 MESSENGER WIRE AND TO PROVIDE SERVICE CONNECTION ON AERIAL KM
BUNCH CABLE BY INSULATED PIERCEING CONNECTORS THROUGH SERVICE
CONNECTION BOX COMPLETE AS REQUIRED & DIRECTED BY ENGINEER IN
STRINGING OF 11KV ABC OF 3*95 SQ MM +80 SQ MM INCLUDING FITTING OF
ALL ACESSARIES I.E. SPECIAL DESIGN SUSPENSION / TENSION CLAMP, FIXING
OF CROSS ARM, BINDING TO PIN INSULATOR,PREPARING SHACKLE
POINT,JUMPERS ETC. AS REQUIRED & DIRECTED BY ENGINEER IN CHARGE
STRINGING OF 22 KV ABC OF 3*70 SQ MM +95 SQ MM INCLUDING FITTING OF
ALL ACESSARIES I.E. SPECIAL DESIGN SUSPENSION / TENSION CLAMP, FIXING
OF CROSS ARM, BINDING TO PIN INSULATOR,PREPARING SHACKLE
POINT,JUMPERS ETC. AS REQUIRED AND DIRECTED BY ENGINEER IN CHARGE
STRINGING OF LT ABC OF 2*50 SQ MM +1*25 SQ MM+ 35 SQ MM INCLUDING
FITTING OF ALL ACESSARIES I.E. SPECIAL DESIGN SUSPENSION / TENSION
CLAMP, FIXING OF CROSS ARM, LT SHACKLE INSULATOR ETC. FOR FIXING OF
41 9926000041 MESSENGER WIRE AND TO PROVIDE SERVICE CONNECTION ON AERIAL KM
BUNCH CABLE BY INSULATED PIERCEING CONNECTORS THROUGH SERVICE
CONNECTION BOX COMPLETE AS REQUIRED & DIRECTED BY ENGINEER IN
DISMENTALING OF RSJ (9/11 METER) POLE AND CREDITING THE OLD
MATERIAL TO STORE
DISMENTALING OF TRANSFORMER CENTER ON 10MTR,270KG PSC
POLE(WITHOUT TRANSFORMER) WITH CREDITING OF FABRICATION AT STORE
AND STACKING OF POLE SAFELY ON ROAD SIDE OR CREDITING TO
DEPARTMENTAL STORE
DISMENTALING OF TRANSFORMER CENTER ON 10MTR,270KG PSC POLE(WITH
44 9926000044 TRANSFORMER) WITH CREDITING OF FABRICATION AT STORE AND STACKING No.
OF POLE SAFELY ON ROAD SIDE OR CREDITING TO DEPARTMENTAL STORE
DISMENTLING OF 11KV ABC OF 3*95 SQ MM +80 SQ MM AND CREDITING
FITTING OF ALL ACESSARIES AND FABRICATION TO DEPARTMENTAL STORE
DISMENTLING OF 22 KV ABC OF 3*70 SQ MM +95 SQ MM AND CREDITING
FITTING OF ALL ACESSARIES AND FABRICATION TO DEPARTMENTAL STORE
DISMENTALING OF LT ABC OF 1*35 SQ MM + 1*25 SQ MM AND CREDITING
FITTING OF ALL ACESSARIES TO DEPARTMENTAL STORE.
DISMENTALING OF LT ABC OF 3*50 SQ MM +1*25 SQ MM+1*35 SQ MM AND
CREDITING FITTING OF ALL ACESSARIES TO DEPARTMENTAL STORE.
DISMENTALING OF LT ABC OF 2*50 SQ MM +1*25 SQ MM+ 35 SQ MM AND
CREDITING FITTING OF ALL ACESSARIES TO DEPARTMENTAL STORE.
RESTRINGING OF ALL TYPE OF CONDUCTOR (EXCEPT DOG CONDUCTOR) FOR ONE
50 9926000050 11/22KV & LT LINES INCLUDING FIXING OF INSULATORS, BINDING JUMPERING COND
RESTRINGING OF DOG CONDUCTOR FOR 11/22KV HT LINES INCLUDING
BINDING JUMPERING ETC.
LABOUR CHARGE FOR THE INSTALLATION OF NEW DTR METER. (METER WILL
BE PROVIDED BY DGVCL)
LABOUR CHARGE FOR THE REPLACEMENT OF DTR METER AND OLD METER
SHOULD BE CREDITED TO SDN STORE. (METER WILL BE PROVIDED BY DGVCL)
LABOUR CHARGE FOR PROVIDING CT COIL FOR DTR METER CONNECTION.
(CT COIL WILL BE PROVIDED BY DGVCL)
LABOUR CHARGE FOR REPLACEMENT OF CT COIL FOR DTR METER
55 9926000055 CONNECTION AND OLD CT SHOULD BE CREDITED TO SDN STORE. (CT COIL PER CT
WILL BE PROVIDED BY DGVCL)
LABOUR CHARGE FOR FIXING OF MMB FOR DTR METER (MMB WILL BE
PROVIDED BY DGVCL)
LABOUR CHARGE FOR REPLACEMENT OF DTR METER BOX. (METER WILL BE
PROVIDED BY DGVCL)
PROVIDING / REPLACEMENT OF 1.5 SQ MM 10 CORE COPPER CABLE 3.5 METER
(CABLE TO BE PROVIDED BY AGENCY)
LABOUR CHARGE FOR PROVIDING/RECONNECTION OF TERMINAL PER
59 9926000059 CONNECTION WITH PROPER SIZE OF LUGS. (LUGS COST IS BORNE BY TERMIN
LABOUR CHARGE FOR THE SPOT READING OF DTR METER WITH DETAIL
SURVEY OF DEFECT IF ANY. A DULY SIGN COPY BY SURVEYOR PERSON OF
60 9926000060 AGENCY IN PRO-FORMA REPORT SHOULD BE SUBMITTED TO SDN OFFICE.(* PER DTR
ONLY IF ALL PARAMETER OF VOLTAGE, CURRENT & LOAD AS SHOWN IN PER-
FORMA IS FILLED) AS PER THE INSTRUCTION OF ENGINEER IN-CHARGE.
LABOUR CHARGE FOR THE SPOT READING OF DTR METER WITH DETAIL
SURVEY OF DEFECT IF ANY. A DULY SIGN COPY BY SURVEYOR PERSON OF
61 9926000061 AGENCY IN PRO-FORMA REPORT SHOULD BE SUBMITTED TO SDN OFFICE. PER DTR
(DULY FILL PER-FORMA IN FAULT CONDITION IN WHICH READING PARAMETER
IS NOT SHOWN IN METER)
INSTALLATION OF DTR METER INCLUDING METER BOX, PROVIDING & FIXING OF
1.5SQ MM SINGLE STRAND 10 CORE ARMOURED COPPER CABLE (3.5METER),
TERMINATION IN METER & COIL ETC.(METER, METER BOX, C.T./P.T. COIL WILL
BE PROVIDED BY DGVCL)
INSTALLATION OF DTR METER INCLUDING METER BOX, TERMINATION IN
63 9926000063 METER & COIL ETC. (WITHOUT 10CORE COPPER CABLE) (METER, METER BOX, No.
C.T./P.T. COIL WILL BE PROVIDED BY DGVCL)
Binding of messanger Conductorat with a distance not more than 0.75 mtr with 6 turns
minimum on XLPE Cable with single strand binding wire (including cost of binding wire)
Supply and Installation of 11/22 kV Distribution Transformers HT Terminal protector (UV
65 9926000086 Resistance) with using 95/120/150 sq.mm long barrel aluminum lug. (1Set = 3 Nos i.e. PER SET
Supply & Installation of HT EPR Tap on 11/22 kV Distribution Transformer with
replacement of bare conductor by HT ABC conductor (DO bottom side to transformer)
after removal of semi conductor by HT ABC (6 inch both side). HT ABC to be supplied
by DGVCL. (1Set = 3 Nos i.e. on R, Y, B)
Supply, Installation, Testing and Commissioning of Maintenance Free, Ready Capsule,
Pipe-In-Cage (Pic) Type, Earth Electrodes for HT Feeder Pole Having 2000 mm
Electrode Length as per the Tender Specifications and Drawing. (All Materials Will Be
Supplied By Agency)
Supply, Installation, Testing and Commissioning of Maintenance Free, Ready Capsule,
Pipe-In-Cage (Pic) Type, Earth Electrodes for HT Feeder Pole Having 3000 mm
Electrode Length as per the Tender Specifications And Drawing. (All Materials Will Be
Supplied By Agency)
Supply and Installation of 25 X 3 mm GI Strip having hot dip- galvanized-zinc coating of
80-100 microns without any joints or welding. Both the end of the GI strip should be
connected with GI nut bolts and required fabrication work for giving separate earthing
69 9926000090 (1) Neutral of the transformer Meter
(2) MS structures of the transformer center (Approximately 25 meter GI strip per
transformer centre
- as per requirement and instruction of Engineer in- charge) (All Materials will be
supplied by Agency)
Supply and Installation of uPVC standard make Pipe of 1.25" diameter for covering GI
strip with UV protected Cable Ties of 550 X 7.6 mm size to bind with pole
face(Approximately 25 meter uPVC pipe for GI strip covering per transformer centre -as
per requirement and instruction of Engineer in-charge.
Supply & fixing of upto 33 kV Conducotr sleev for Busbar to Drop out Fuse and Drop out
71 9926000093 fuse to Transformer H.T. including Busbar (12 mm sleev) as per technical specification. Meter
(All Materials will be supplied by Agency)
Supply & fixing of upto 33 kV Conducotr sleev for Busbar to Drop out Fuse and Drop out
72 9926000094 fuse to Transformer H.T. including Busbar(15 mm sleev) as per technical specification. Meter
(All Materials will be supplied by Agency)
Supply & fixing of Disc type Red Color FRP(Non-flammable) material with Weather
resistant, Non-conductive bird guard OD=300 MM, ID=33 MM, Width =1.25 MM, one
side cut from ID to OD. (All Materials will be supplied by Agency)
Providing and fixing of LT Terminal protectors i.e. Re-useable boot (LT Side 1.1 kV)
74 9926000096 including LT (1.1 kV) insulating taps. All live part at LT side shall be covered with fixing No
of LT insulating taps.
75 Nylon Net around Transformer Center
75.1 9926000097 Nylon Net (12 * 15 ft) Per Net
75.2 9926000098 Nylon Dori Per TC
Labour charge for fitting Nylon Net (All fabricated material for fitting nylon net shall be
provided by DGVCL)
PART-A : 2 : LABOUR RATES FOR MAINTENANCE WORKS FOR THE FY 2024-25 (WITHOUT GST)
Sr.No. Item Code Details of works Unit FY 2024-25
(A) LINE MAINTENANCE
1 9924000001 Cutting of Tree branches surounding HT/LT line Per Tree
Replacement of old jumpers & providing new double jumpers with 8" binding [D Type] &
capsuling with PVC pipe etc
3 9924000005 Support pole for Stay PSC/STP/RSJ No.
4 9924000006 Pin binding of conductor 11/22kv Pin insulator No.
5 9924000007 Pin binding of conductor 11/22kv Pin insulator per pole in costle area with cleaning . No.
6 9924000008 Pin binding of conductor LT shakel insulator No.
7 9924000009 Replacement of one/both disc.insulator at strain pole No.
8 9924000010 Replacement of LT shackle insulator at cut point No.
9 9924000011 Refixing of V cross Arm No.
10 9924000012 Replacement of V cross Arm (With Transportation & Painting) No.
11 9924000013 Refixing of Top fitting in proper position No.
12 9924000014 Replacement of Top fitting No.
13 9924000015 Replacement of LT cross Arm No.
14 9924000016 Providing DO fuse on DP with carting & jumpuring(ONE DO FUSE) No.
Numburing of pole with paint by preparing back ground of one colour and have lettering(height
3" * width 0.5") using stensil
16 9924000018 Fixing of MMB(1PH.) at consumer end No.
17 9924000019 Fixing of MMB(3PH.) at consumer end No.
18 9924000020 Replacement of (1ph.) meter for Urban area No.
19 9924000021 Replacement of (1ph.) meter for Rural area No.
20 9924000022 painting consumer no. on MMB (Urban) (with letter size height 40mm* width 8mm) No.
21 9924000023 painting consumer no. on MMB (Rural) (with letter size height 40mm* width 8mm) No.
22 9924000024 Replacement of deteriorated Single phase Service line No.
23 9924000025 Fixing of new dist. Box with complete wiring including clamps,nut bolts etc. No.
24 9924000026 Reparing of guarding involving reshaping of bearer wire cross lacing binding etc. R Mtr.
25 9924000027 Painting of steel fabricated material of RSJ DO DP structure with paint No.
Painting of steel fabricated material of RSJ pole mounted transformer double pole structure
27 9924000029 Painting of steel fabricated material of RSJ single pole with paint No.
28 9924000030 painting of steel fabricated material of PSC Single pole (HT line) with paint No.
29 9924000031 painting of steel fabricated material of PSC DO DP double pole with paint No.
30 9924000032 painting of steel fabricated material of PSC double pole at pole mounted transformer with paint No.
31 9924000033 Providing line seperater single phase No.
32 9924000034 Providing line seperater three phase No.
33 9924000035 Replacement / Providing of stay insulator along with adjustment of tension in stay wire No.
Replacement of deteriorated /providing LT dist. Box with new up to 100KVA capacity &
crediting it to store.
Replacement of deteriorated /providing LT dist. Box with new above 100KVA capacity &
crediting it to store.
36 9924000038 Adjustment of tension in stay wire No.
37 9924000039 Refitting of LA No.
38 9924000040 Converting pin point to Shackle point including dismentaling & restringing etc. location
39 9924000041 replacement of 11KV Pin insulator with providing new double pin binding No.
replacement of 22KV Pin insulator by new 11kv pin insulator with spares & providing new
double pin binding
41 9924000043 Providing 11kv double disc insulators with binding & restringing No.
42 9924000045 Replacement of existing 11kv conductor (all size) with new double pin binding Cond/KM
43 9924000046 Plumbing of PSC Pole with straightening at pin point No.
44 9924000047 Plumbing of PSC Pole with straightening at tension point No.
45 9924000048 Plumbing of tilted DP structure (PSC/RSJ/STP) with refilling of stone Murrum etc. No.
Providing new 11kv AB /GO switch with fabrication and insulated colour code jumper, binding,
47 9924000051 Replacement of old 11kv AB /GO switch with providing new insulated jumper, binding, lugs etc Set
48 9924000052 Providing cage type loop guard in verticle LT line with using PVC reel insulators etc per pole
Labour charges for replacement /providing of MMB & service with all accessories for three
phase connection
Labour charges for replacement /providing of MMB & service with all accessories for single
phase connection
Dismentalling of existing Dist.X'mer center(RSJ /STP POLE) 25/63/100/200 KVA with all
fabrication & creditig the old material to store
Disconnection from LT pole 1 phase
Reconnection from LT pole 1 phase
( payment after receipt of R/C charges)
Disconnection from LT pole 3 phase
Reconnection from LT pole 3 phase
( payment after receipt of R/C charges)
56 9924000060 Dismentaling & removing of service line from pole & crediting to S/dn (1 ph.) No.
57 9924000061 Dismentaling & removing of service line from pole & crediting to S/dn (3 ph.) No.
58 9924000062 Reconnection of service line complete with PVC cable (1 Ph) No.
59 9924000063 Reconnection of service line complete with PVC cable (3 Ph) No.
Providing spiral type earthing by G.I. NO 8(weight 2kg -5mtr in length) with salt and coal 10kg
60 9924000064 each, including pvc rigid pipe 20mm dia( 1.5mtr length) to pass exposed part of G.I. wire at No.
consumer end with all materials, earth resistance should be less than 2 ohms
Providing and fixing of signle core 1.5 sq mm single strand copper insulated cable with cable nail
clip for spiral type earthing at consumer end. The end of G.I. no 8 is to be connected by
61 9924000070 connector with copper cable of which other end shall be connected to the earth terminal of per meter
meter box. This item shall be used in location where there is more distance between earth
terminal and earthing terminal of meter. (All materials supplied by contractor)
TOTAL AMOUNT OF PART-A (5,00,000=00 FIVE LAKHS RUPEES ONLY)
TOTAL AMOUNT OF PART-A (5,00,000=00 FIVE LAKHS RUPEES ONLY)
PART-B FOR UG CABLE
LABOUR RATE FOR UNDERGROUND CABLE WORK FOR FY 2024-25 (WITHOUT GST)
Item Code Description Unit FY 2024-25
Labour charge for excavation of cable trench of 400mm width x 1200mm depth, in any
1 9925000001 type of soil for laying of cable of size up to 240 mm2 (For additional cable 200 mm Meter
additional width shall be considered i.e. half trench length is to be considered)
Labour charge for excavation of cable trench of 600mm width x 1200mm depth, in any
2 9925000002 type of soil for laying of cable of size up to 240 mm2 (For additional cable 200 mm Meter
additional width shall be considered i.e. half trench length is to be considered)
Labour charge for excavation of cable trench of 400mm width x 1500mm depth, in any
3 9925000003 type of soil for laying of cable of size up to 240 mm2 (For additional cable 200 mm Meter
additional width shall be considered i.e. half trench length is to be considered)
Labour charge for laying of 11kV / 22 kV XLPE Cable of size up to 240 mm2 &
preparation of sand layer 100mm thick, in the cable trench & covering the cable with
mm dia (Inner), thickness 25 mm, 1.0 meter long RCC half round muffs and providing
and fixing of 4inch width yellow colour polyethylene tape with printing "CAUTION
ELECTRIC CABLE BELOW" at 0.75 m depth from ground surface after laying cable in
trench. This will provide indication that electric cable is passing underground so as to
protect cable from mechnical injuries, refilling the same, as per Instruction of Engineer in
Labour charge for horizontal drilling using Auger machine without damage to surface
road at max 2.0 mtrs depth & putting of 6.11 kg/cm2 , class-4,Green color, 110mm O.D.
, 8.5mm thickness H.D.P.E. pipe confirms to IS 4984-1987(3rd revision) and BIS
certification and laying of 11KV/22KV XLPE cable of size up to 240 mm2 in HDPE pipe,
5 9925000005 as per Site Condition (excluding cost of pipe). The detail map obtained from HDD Meter
machine and excell sheet(hard and soft copy) indicating the respective depth and
distance from adjacent landmark for each segment for HDD is must required to be
submitted. HDD to be carried out at depth 1.5 mtrs to 2.0 mtrs as per site conditions and
as per instruction of EIC.
Labour charge for horizontal drilling manually without damage to surface road at max
2.0 mtrs depth & putting of 6.11 kg/cm2 , class-4,Green color, 110mm O.D. , 8.5mm
thickness H.D.P.E. pipe confirms to IS 4984-1987(3rd revision) and BIS certification and
laying of 11KV/22KV XLPE cable of size up to 240 mm2 size, as per Site Condition
(excluding cost of pipe). The detail map and excell sheet(hard and soft copy) indicating
the respective depth and distance from adjacent landmark for each segment of cable to
be submitted. Drilling to be carried out at depth Minimum 1.2 mtrs to 2.0 mtrs as per
site conditions as per instruction of EIC.
Supply of 6.11kg/cm2 , class-4,Green color, 110mm O.D. , 8.5 mm thickness H.D.P.E.
7 9925000007 pipe confirms to IS 4984 and BIS certification for laying of underground 11KV / 22KV Meter
XLPE cable up to 240 mm2 size.
Labour work for RCC concreting on disputed location and repairing of damage portion of
8 9925000008 road crossing for the work carried out for roads crossing as well as concreting & CMT
muffing of ploes including all materials (1:2:4)
Providing & fixing concrete stone route marker of 300 mm width x 150 mm thick x
mm height embedded in earth at least 300 mm below & 350 mm above ground level
respectively at distance approx 50 meters along the length of cable. The RCC
concreting (1:2:4)(all necessary maeterials will be in bidder's scope) of route marker is
to be carried out 300 mm width x 150 mm thick x 300 mm below ground level as per
instruction of EIC. The route marker should be with name of company with approved
yellow colour-DGVCL. The distance from marker to cable and cable depth with feeder
name etc., marked with arrow sign is to be painted on it.The route marker is to be fixed
at location near to any fixed permanent location (not necessary to fix exact on top of
cable) as per instruction of EIC.
Erection of D.P. (double pole) structure using 9 / 11 Mtr. RSJ pole with cable
connection arrangement along with fitting of necessary fabrication for 11KV cable
including excavation of pit & refilling of earth as per instruction of EIC. (Exclusive of
concreting & muffing of poles)
Erection of Single pole structure using 9 / 11 Mtr RSJ pole with cable connection
arrangement along with fitting ofnecessary fabrication for 11KV/22 KV cable including
excavation of pit & refilling of earth as per instruction of EIC. (Exclusive of concreting &
muffing of poles)
Erection of D.P. (double pole) structure using 8.0 Mtr. PSC pole with cable
connection arrangement along with fitting of necessary fabrication for 11KV cable
including excavation of pit & refilling of earth as per instruction of EIC. (Exclusive of
concreting & muffing of poles)
Erection of Single pole structure using 8.0 Mtr PSC pole with cable connection
arrangement along with fitting ofnecessary fabrication for 11KV/22 KV cable including
excavation of pit & refilling of earth as per instruction of EIC. (Exclusive of concreting &
muffing of poles)
Labour charge for erecting of 11kV / 22 kV XLPE cable of size up to 240 mm2 on DP
14 9925000014 Structure with fixing of 02 Nos polymer cleats on top and middle part.Polymer Per Job
cleats, nut bolts etc. fixing material to be provided by contractor.
Providing & fixing of 6.11kg/cm2 , class-4,Green color, 110mm O.D. , 8.5mm
thickness H.D.P.E. pipe confirms to IS 4984 and BIS certification on the erected
DP structure for the mechanical protection of cable by inserting the cable inside HDPE
15 9925000015 pipe. The HDPE pipe shall be erected in such a way that 300mm shall be below the Per Job
ground level and the rest 2700 mm shall be supported on the DP Structure with
No Polymer cleat.All materials including polymer cleat and Nut bolt to be provided by
Providing and fixing of pipe type earthing from 80 mm dia class-B GI pipe with pit to be
filled with salt & coke and construction of chamber as per DGVCL Drg. No. dg /100 for
DP and cable. The earthing pit should be joined with cable by G.I. strip of size 1” width
& 2 mm thick. All material GI pipe, Coke, Salt etc will be supplied by bidder.
Supply & fixing of heat shrink type end terminations (outdoor) for upto 11kV 3C x
185 mm2 size XLPE cable as per DGVCL technical specification
Supply & fixing of heat & shrinkable end terminations (outdoor) for upto 22 kV 3C x
185 mm2 size XLPE cable as per DGVCL technical specification)
Supply & fixing of heat shrink type end terminations (indoor) for upto 11kV 3C x
mm2 size XLPE cable as per DGVCL technical specification)
Supply & fixing of heat & shrinkable end terminations (indoor) for upto 22 kV 3C x
185 mm2 size XLPE cable as per DGVCL technical specification
Supply & fixing of heat shrinkable straight through joint for upto 11kV 3C x 185 mm2
size XLPE cableas per DGVCL technical specification.
Supply & fixing of heat shrinkable straight through joint type for upto 22kV 3C x
mm2 size XLPE cable as per DGVCL technical specification
Labour charge for excavation of 2100mm long x 1200mm wide x 1200 mm deep joint
pits for installation of 11kV / 22kV Straight through joints as per instruction of
engineer-in-charge & covering the cable with 150 mm dia (Outer), thickness 25 mm,
1.0 meter long RCC half round muffs & refilling same as per instruction of EIC .
Providing and fixing of insulating bus bar, made from 11KV/22KV XLPE cable after
removal of semi conducting layer and applying of PVC heat shrinkable anti-tracking
core insulating tubing (1.1KV), on both end terminal using Aluminium long barrel heavy
24 9925000024 duty up to 240 sq mm lugs, Aluminium bus connector. Taping with PG- clamp for bus No.
conductor as per drawing and as per instruction of EIC. The Alluminium lugs and PG
clamp shall be covered with 11KV/22KV HT insulating tapes.(11KV/22KV XLPE cable
will be in scope of DGVCL while all other materials will be in bidder's scope)
Testing of cable at various points and commissioning the feeder as per instruction of
engineer-in-charge.Test result shall be submitted by contractor with bill.
Preparation and submission of 6 (six) copies, of complete layout drawings with GIS
26 9925000026 mapping as per actual cable routing showing road crossing, HDPE pipe sleeving, Set
jointing locations, markers etc.
Providing and fixing of Sign Board at junction point Made out of 2 mm aluminium sheet
size 750x300 mm (2.5 x 1ft) rectangle, as per design, pre treated with phosphate
process and acid etching coated with one coat of epoxy primer and two coats of best
quality paints, refloctrorised with Hi-Intensity retro – reflective sheeting as per the latest
27 9925000027 and frame fabricated from suitable size iron angle. The Sign Board is to be fixed on the No.
base prepared from channel and bracing angles which is grouted by means of cement
concreting of 1:2:4 for size of 300 mm dia x 800 mm height (500 mm to be grouted in
ground). The details to be displayed on sign board will be given by In-charge Engineer.
(a) Hi intensity Micro prismatic Grade
Providing and fixing of Sign Board (Danger Board) on Distribution Transformer Centers
Made out of 2mm aluminium sheet size 300x300mm (1x1ft) as per design, pre treated
with phosphate process and acid etching coated with one coat of epoxy primer and two
28 9925000028 coats of best quality paints, refloctrorised with Hi-Intensity retro-reflective sheeting as No.
per the latest and frame fabricated from suitable size iron angle. The Sign Board
(Danger Board is to be fixed at the location as per instruction of In-charge Engineer.
(a) Hi intensity Micro prismatic Grade
Providing & fixing of aluminium tag of size 250 mm (L) x 75 mm (W) from 3 mm
aluminium sheet along with 1.0 mm dia aluminium binding wire for fixing of aluminium
29 9925000029 tag near end termination joint at DP structure for identifyng the cable. The details of No.
feeder i.e. 11 / 22 KV with feeder name shound be punched on the tag by letter punch of
size 16 mm as per instruction of In-charge Engineer.
Supply & fixing of heat shrink type end terminations (outdoor) for 11kV 3C x
mm2 size XLPE cable as per DGVCL technical specification
Supply & fixing of heat & shrinkable end terminations (outdoor) for 22 kV 3C x
mm2 size XLPE cable as per DGVCL technical specification)
Supply & fixing of heat shrink type end terminations (indoor) for 11kV 3C x 240 mm2
size XLPE cable as per DGVCL technical specification)
Supply & fixing of heat & shrinkable end terminations (indoor) for 22 kV 3C x
mm2 size XLPE cable as per DGVCL technical specification
Supply & fixing of heat shrinkable straight through joint for 11kV 3C x 240 mm2 size
XLPE cableas per DGVCL technical specification.
Supply & fixing of heat shrinkable straight through joint type for 22kV 3C x 240 mm2
size XLPE cable as per DGVCL technical specification
Installation, Testing and commissioning of 11 KV,630 A SCADA Compatible, RRL type-
36 9925000038 3 Way RMU including Two numbers of earthings as per Drawing (material is in bidder's No.
scope) and as per DGVCL Technical specification.
Installation, Testing and commissioning of 11 KV,630 A SCADA Compatible, RRLL
37 9925000039 type- 4 Way RMU including Two numbers of earthings as per Drawing (material is in No.
bidder's scope) and as per DGVCL Technical specification.
Installation, Testing and commissioning of 22KV,630 A SCADA Compatible, RRL type-
38 9925000040 3 Way, RMU including Two numbers of earthings as per Drawing (material is in bidder's No.
scope) and as per DGVCL Technical specification.
Installation, Testing and commissioning of 22KV,630 A SCADA Compatible, RRLL
39 9925000041 type-4 Way, RMU including Two numbers of earthings as per Drawing (material is in No.
bidder's scope) and as per DGVCL Technical specification.
Construction of plinth for 11KV, RRL type- 3 Way (i.e Two numbers of Isolator & One
40 9925000042 number of Breaker) Ring Main Unit as per DGVCL's technical specification mentioned No.
in drawing no: Drg. 11kv-01. All required material will be supplied by contractor.
Construction of plinth for 11KV, RRLL type- 4 Way (i.e Two numbers of Isolator &
Two number of Breaker)Ring Main Unit as per DGVCL's technical specification
mentioned in drawing no:Drg. 11kv-02.All required material will be supplied by
Construction of plinth for 22KV, RRL type- 3 Way (i.e Two numbers of Isolator & One
42 9925000044 number of Breaker) Ring Main Unit as per DGVCL's technical specification mentioned No.
in drawing no: Drg. 22kv-01. All required material will be supplied by contractor.
Construction of plinth for 22KV, RRLL type- 4 Way (i.e Two numbers of Isolator &
Two number of Breaker)Ring Main Unit as per DGVCL's technical specification
mentioned in drawing no:Drg. 22kv-02.All required material will be supplied by
Modifications e.g.Providing and fixing of Terminal protectors i.e. Re-use able boot (HT
Side 11/22KV, LT Side 1.1KV) including 11/22 KV insulating taps and L.T.(1.1 KV)
insulating taps ,Busbar, Tapping from Bus Bar (11/22 KV XLPE cable) through P.G.
Clamp for H.T. Jumper to D.O. Fuse to bushings of Transformer Center, providing &
Fixing of jumper and providing & fixing of Heat Shrinkable Anti Tracking Core Insulating
Tubing (Insulation Level 11/22 KV) in H.T. jumper , Clamping arrangement of cable
44 9925000046 support frame on both side of existing Over Head type Distribution Transformer to No.
utilize in Under Ground cable network as per drawing & as per instruction of Engineer
incharge. All live parts i.e. PG-Clamp, connections of D.O.fuses, HT bushings etc .
shall be covered with fixinng of 11/22 KV HT insulating tapes. ( 11/22 KV XLPE cable
will be in scope of DGVCL while all other materials will be in bidder's scope ) .
Laying of any size of 11/ 22 KV XLPE /PILC Cable in redaymade trench or in open
46 9925000060 Labour charges for Lying of O/H XLPE cable pole to pole KM
47 9925000064 Supply of 150 mm dia (Inner), thickness 25 mm, 1.0 meter long RCC half round pipe No.
TOTAL AMOUNT OF PART-B (25,00,000=00 TWENTY FIVE LAKHS RUPEES ONLY)
TOTAL AMOUNT OF PART-B (25,00,000=00 TWENTY FIVE LAKHS RUPEES ONLY)
TOTAL OF AMOUNT (PART:A + PART:B) 30,00,000=00
THIRTY LAKHS ONLY
% Above/Below of Estimate Amount
Stamp & Sign of Contractor
Executive Engineer (O&M)
DGVCL, Rander Division
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
RAW_HTML
1. RND-525 UG Cable HT LT TC Work Ramnagar Sdn.pdf
1.1 RND-525 Ramnagar SDN Schedule A.pdf
2. Ramnagar SDN Bid Document.pdf
3. Ramnagar SDN Detail Tech Specification.pdf
4. Erection and Maintenance for Technical Specification.pdf
5. Ramnagar Schedule-b for ug .pdf
6.Reference Bid Drawing.pdf
7 .UG CABLE TENDER IMP POINTS LETTER RANDER.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at [email protected].