Loading…
Loading…
Tender Value
Refer Docs
EMD Value
₹1.5 L
Closing Date
31 Aug 2026, 3:00 pm7d left
Sudipta Bose (EE/EL)
nbdd uttarkanya
Special repairing of 2X750KVA indoor dry type Sub-Station and 11KV VCB panel, Bus-Duct, L.T Panel, PLC Panel, APFC Panel and Synchronising Panel including all DG Sets in sub-station building at Uttarkanya,Kamrangaguri in the district of Jalpaiguri fo
2026_NBDD_1038300_5
NBDD/BS/EE /NIQ-15- (EL) of 2026-2027 (SL No. 13 to 20)
Open Tender
Electrical Work/ Equipment
Item Rate
Jalpaiguri
Please refer Tender documents.
6 documents required · 6 mandatory
₹1.5 L
Yes
17 Aug 2026
17 Aug 2026
3 Sept 2026
17 Aug 2026
31 Aug 2026
17 Aug 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Charges for electrical maintenance of Two nos 750KVA indoor Dry type transformer and 1no 11KV VCB and 1600Amps Sandwich type Bus-Duct as per attached Terms & condition and as per direction of E-I-C with the help of manpower (i) Shift-1 (from 8 a.m. to 4 p.m.) - 1 no. Semi-skilled Electrician & 1 no. Helper. (ii) Shift-2 (from 2 p.m. to 10 p.m.) - 1 no. Semi-skilled Electrician & 1 no. Helper.
(iii) Shift-3 [General Shift during VVIP visit] (during entire period of VVIP presence.) - 1 no. Semi skilled Electrician & 1 no. Helper. Charges for electrical maintenance of APFC panel, PLC panel,L.T panel,Synchronysing panel and AMF panel including all parts of L.T panel boards,all cables of consumer sides, all type of glands & sockets ,MCBs,ACB,MCB isolators as per attached terms & condition and as per direction of E-I-C with the help of manpower (i) Shift-1 (from 8 a.m. to 4 p.m.) - 1 no. Semi-skilled Electrician & 1 no. Helper. (ii) Shift-2 (from 2 p.m. to 10 p.m.) - 1 no. Semi-skilled Electrician & 1 no. Helper.
(iii) Shift-3 [General Shift during VVIP visit] (during entire period of VVIP presence.) - 1 no. Semi skilled Electrician & 1 no. Helper. Charges for maintenance of the Diesel Generator sets-320KVA,160KVA-1 & 2 , 25KVA and 200 KVA with periodically servicing the all mention sets as required with the help of authorised technicians with the help of manpower (i) Shift- (periodic monthly servicing with record of service strictly maintained and duly signed by JE, AE & EE) - 1 no. .
(ii) Shift-3 [General Shift during VVIP visit] (during entire period of VVIP presence.) - 1 no. Semi skilled Electrician & 1 no. Helper. | - | Years | - | - |
| 2 | Charges for attending the 11 KV VCB Panel -R.M.U based and 750KVA Transformers and whole L.T panel at Sub-Station for health check-up of these heavy electrical equipments on hire basis by highly Skilled employee. | - | Days | - | - |
| 3 | Providing a highly skill employee for attending all technical fault of all electrical equipments including checking all electrical parameters and with the record of service strictly maintained and duly signed by JE, AE & EE in proper way at Sub-Station building monthly atleast one day. | - | Months | - | - |
| 4 | Supply & delivery of 230 V, 50 Hz, single phase, 80 watts, 12" (300 mm) Sweep, speed 1400 rpm (minimum), A.C. Exhaust Fan and class of insulation: B, 4 nos. metal (Aluminium alloy) blades, copper winding, steel/Al body. Power Factor not less than 0.9 and minimum air delivery 1710 cmh (minimum) including capacitor with safety pin, nut bolts, washers, temperature rise=75 degree C (max.), insulation resistance more than 2 mega ohm, suitable for compliant to IS 374:2019 and external connections with 1.5 sq.mm FR, PVC insulated copper conductor single core cable and earthing etc. as required. | - | Each | - | - |
| 5 | LED Down lighter (COB Type) (System lumen efficacy ≥120 lm/Watt ) Supplying, Installation, Testing & Commissioning of LED Recessed/surface Down lighter (Round / square/ Rectangular) COB Type of following body material and construction as per IS : 10322 with driver as per the requirement with Driver efficiency >85%, Operating voltage AC 140-270 Volt, frequency 50/60 hz, Operating temp range -5 0C
to 40 0C, internal surge protection of 2.5 KV with Short & Open circuit protection ,THD < 10% ,
P. F.≥0.95, IP20, CRI >80 , UGR (Unified Glare Rating) < 19, Flicker free (flicker should be below 5
%), life time (LED, Driver & electrical circuitry), life time of minimum 50000 Burning Hours with, 70%
of initial Lumen maintained till life ends , CCT 3000°K / 4000°K / 5700°K 22 Watt (System lumen efficacy ≥ 120 lm/Watt) | - | Each | - | - |
| 6 | 30 Watt (System lumen efficacy ≥ 120 lm/Watt) | - | Each | - | - |
| 7 | LED Panel light 2x2 ft. (System lumen efficacy ≥120 <135 lm/Watt)Supplying, Installation, Testing & Commissioning of Panel light 2x2 ft., of following body material and construction as per IS : 10322 with driver as per the requirement with Driver efficiency >85%, Operating voltage AC 140-270 Volt, frequency 50/60 hz, Operating temp range -5 0C to 40 0C, internal surge protection of 2.5 KV with Short & Open circuit protection ,THD < 10% , P. F.≥0.95, IP20, CRI >80, UGR (Unified Glare Rating) <19, Flicker free,
(flicker should be below 5 %), life time (LED, Driver & electrical circuitry), of minimum 50000 Burning
Hours with , 70% of initial Lumen maintained till life ends, CCT 3000°K / 4000°K / 5700°K
/6500°K (As per ANSI Bin), SDCM(Standard Deviation Color Matching) <3, Maximum power
consumption should not more than the specified rating and Fixture shall be of relevant BIS standard.
Manufactures Word Mark/ Name Engraved 36 Watt (System lumen efficacy
≥120 <135 lm/Watt) | - | Nos | - | - |
| 8 | LED Street light fixture, powder coated pressure die cast aluminium body (System lumen efficacy
>135 lm/Watt).Supplying, installation, Testing & Commissioning of Street light LED fixture powder coated pressure die cast aluminum body finish with corrosion resistance fasteners (SS hardware) & silicon gasket for proper sealing with driver as per the requirement with Driver efficiency >80%, Input voltage: 140-270 Volt AC, freq 50/60 hz, Operating temp range 0o to 50o C and working RH 10% - 90%, internal surge protection of 5 KV internal and external SPD min. 10 KV, L,N,E as per IEC 61000-4-5. The driver rated output wattage should be 10% to 15% higher than lamp rating and at least 2 driver for 200W & above and Driver efficiency >85%, THD < 10% as per IEC 61000-3-2 , P. F.≥0.9, IP- 66, IK-08 specified below, CRI >70, under voltage and over voltage protection, high efficiency lens with type
II/III distribution as required with UV stabilized optical lens, life time (LED,Driver & electrical circuitry) of minimum 50000 Burning Hours (Life projection shall be calculated as per TM-21 methodology) and
70% of initial Lumen maintained till life ends. CCT 3000°K / 4000°K / 5700°K /6000°K/6500°K, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant
BIS standard complete in all respect and LED Chips of SMD mid to high-power (2.5 to 4 watt for 200 watt and above, as per required (LM- 80 tested) and necessary inter-connections with 1.5 sq mm FR, PVC
insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM comprehensive on-site warranty against manufacturing defects including driver and LED module. All
test report except L80 should be from 3rd party NABL accredited Lab as per BIS shall be submitted. Shape size and CCT shall be as
approved by Engineer-in-Charge as per requirement. 72 Watt (System lumen efficacy
>135 lm/Watt) | - | Nos | - | - |
| 9 | Supplying and delivery of following size Armoured cables XLPE/PVC insulated are designed for 1.1 kV Stranded Aluminium conductor, high tensile galvanized steel wire/strip armour for mechanical protection, and PVC/FR PVC outer sheathing power cable of following size. (IS 7098 Part - 1/2011 with Up To Date Amendments.) 2CX10 Sqmm | - | Mtr | - | - |
| 10 | 4X25 Sqmm | - | Mtr | - | - |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 1.47 MB
Tendernotice_2.pdf
PDF • 0.51 MB
BOQ_2550642.xls
BOQ • 0.35 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at [email protected].