Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹15.0 LAccepted-AOC THEKKILAKKATTIL HOUSE KALKANDI PO KALLAMALA PALAKKAD DISTRICT | PALAKKAD | KERALA | ₹15.0 L | L1 | Accepted-AOC Lowest bidder |
| 2 | L2₹16.5 LRejected-AOC | ₹16.5 L | L2 | Rejected-AOC second lowest bidder |
| Sl No | Description | Qty | Unit | P. PRADEEPAN L2 | VARGHESE THEKKILAKKATTIL REJI L1 |
|---|---|---|---|---|---|
| 1.00Electrification | |||||
| 1.00 | 1.10.3:Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC
insulated copper conductor single core cable in surface / recessed medium class PVC conduit,
with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FRLS
PVC insulated copper conductor single core cable etc as required.Group C | 142 | point | 1,689 ₹2.4 L | 1,536.99 ₹2.2 L |
| 1.00 | 1.11:Wiring for twin control light point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, 2 way modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable etc as required. | 6 | point | 1,799 ₹10,794 | 1,637.09 ₹9,822.54 |
| 1.00 | OD147488/2025-2026:Supply and fixing 9/12 W LED lamp with angle ,brass lined skirt type, bakelite batten holder and giving connection etc as required | 9 | each | 224 ₹2,016 | 203.84 ₹1,834.56 |
| 1.00 | OD224048/2024-2025:Supply, conveyance, installation, testing and commissioning of pre-wired light fitting complete with all accessories and lamps etc. directly on wall and giving connections with required length of 16/0.20mm 3 core copper conductor flex wire conforming to relevant ISS or extending the original wiring and giving connection etc. as required.1 feet 5 W mirror lamp. | 2 | each | 462 ₹924 | 420.42 ₹840.84 |
| 1.00 | 90.5.1.3:Supply and fixing the following types of superior quality 250V A.C call bell on existing M.S. box and giving connections with required length of 3 core, 16 / 0.20mm 650/1100V grade PVC insulated and PVC sheathed round copper conductor flex wire conforming to relevant ISS or with the extended original wiring, earthing the MS box and making good the surface as required.Ding dong bell | 2 | each | 200 ₹400 | 180.18 ₹360.36 |
| 1.01 | OD253342/2025-2026:Supply, conveyance installation testing and commissioning of LED bulk head fittings made with poly carbonate housing , consumption 10W LED with system efficiency > 115lumen/watt with premium quality diffuser for even distribution of light directly on wall including cutting necessary holes, giving connections with the extended original wiring , making good the damages, color washing etc as required | 4 | each | 580 ₹2,320 | 525.07 ₹2,100.28 |
| 1.01 | OD269107/2025-2026:
Supply, conveyance installation testing and commissioning the light fittings made of CRCA sheet with 0.5mm thickness complete with all accessories and lamps etc. directly on wall or ceiling with PVC round block neatly painted to suit the fitting giving connections with required length of 16/0.20mm 3 core copper conductor flex wire conforming to relevant ISS or extending the original wiring and giving connection etc. as required. including providing 1200 mm 20 W T8 LED tube , having total efficiency of 100 Lumen /watt with 4 feet Aluminium extrusion in the tube for better heat dissipation,, THD < 20% PF> 0.95 ( LM 79 & LM 80 Certificate from NABL should be submitted ) | 2 | each | 1,275 ₹2,550 | 1,158.43 ₹2,316.86 |
| 1.01 | OD253343/2025-2026:Supply, installation, testing and commission of 1200 lumen round surface mount fitting made of diecast aluminium, having efficacy not less than 100l/w, pf greater than 0.95, THD less than or equal to 10%, Chip make Cree/Osram/lumilled/Nichea and giving connections with 16/0.20mm 3 core PVC insulated and sheathed round copper conductor flex wire or extending the original wiring and giving connections as required | 9 | each | 1,420 ₹12,780 | 1,289.47 ₹11,605.23 |
| 1.01 | OD147591/2025-2026:SITC of 1800 lumen square/round surface mount LED fitting made of min 0.5mm CRCA Sheet, having efficacy not less than 110 lm/w, pf greater than 0.95, THD less than or equal to 10%, Chip make Cree/Osram /lumileds /Nichia /Bridgelux /Seoul and giving connections with 16/0.20mm 3 core PVC insulated and sheathed round copper conductor flex wire or extending the original wiring and giving connections as required | 29 | each | 2,040 ₹59,160 | 1,855.49 ₹53,809.21 |
Tender Value
Refer Docs
EMD Value
₹41,309
Closing Date
24 Jan 2026, 5:00 pmClosed
Executive Engineer
PWD Electrical Division Thrissur
GENERAL Construction of 2nd phase finishing work of Office Building for 28K NCC Battalion at Ottappalam PalakkadElectrificationGeneral Electrical Work
2026_PWD_828416_1
PWD/BLDG/15130/2025-2026
Open Tender
Electrical Works
180 days
Ottappalam
Please refer Tender documents.
9 documents required · 9 mandatory
₹2,760
₹41,309
12 May 2026
17 Jan 2026
27 Jan 2026
17 Jan 2026
24 Jan 2026
17 Jan 2026
Electrification
1.10.3:Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable etc as required.Group C
1.11:Wiring for twin control light point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, 2 way modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable etc as required.
OD147488/2025-2026:Supply and fixing 9/12 W LED lamp with angle ,brass lined skirt type, bakelite batten holder and giving connection etc as required
OD224048/2024-2025:Supply, conveyance, installation, testing and commissioning of pre-wired light fitting complete with all accessories and lamps etc. directly on wall and giving connections with required length of 16/0.20mm 3 core copper conductor flex wire conforming to relevant ISS or extending the original wiring and giving connection etc. as required.1 feet 5 W mirror lamp.
90.5.1.3:Supply and fixing the following types of superior quality 250V A.C call bell on existing M.S. box and giving connections with required length of 3 core, 16 / 0.20mm 650/1100V grade PVC insulated and PVC sheathed round copper conductor flex wire conforming to relevant ISS or with the extended original wiring, earthing the MS box and making good the surface as required.Ding dong bell
OD253342/2025-2026:Supply, conveyance installation testing and commissioning of LED bulk head fittings made with poly carbonate housing , consumption 10W LED with system efficiency > 115lumen/watt with premium quality diffuser for even distribution of light directly on wall including cutting necessary holes, giving connections with the extended original wiring , making good the damages, color washing etc as required
OD269107/2025-2026: Supply, conveyance installation testing and commissioning the light fittings made of CRCA sheet with 0.5mm thickness complete with all accessories and lamps etc. directly on wall or ceiling with PVC round block neatly painted to suit the fitting giving connections with required length of 16/0.20mm 3 core copper conductor flex wire conforming to relevant ISS or extending the original wiring and giving connection etc. as required. including providing 1200 mm 20 W T8 LED tube , having total efficiency of 100 Lumen /watt with 4 feet Aluminium extrusion in the tube for better heat dissipation,, THD < 20% PF> 0.95 ( LM 79 & LM 80 Certificate from NABL should be submitted )
OD253343/2025-2026:Supply, installation, testing and commission of 1200 lumen round surface mount fitting made of diecast aluminium, having efficacy not less than 100l/w, pf greater than 0.95, THD less than or equal to 10%, Chip make Cree/Osram/lumilled/Nichea and giving connections with 16/0.20mm 3 core PVC insulated and sheathed round copper conductor flex wire or extending the original wiring and giving connections as required
OD147591/2025-2026:SITC of 1800 lumen square/round surface mount LED fitting made of min 0.5mm CRCA Sheet, having efficacy not less than 110 lm/w, pf greater than 0.95, THD less than or equal to 10%, Chip make Cree/Osram /lumileds /Nichia /Bridgelux /Seoul and giving connections with 16/0.20mm 3 core PVC insulated and sheathed round copper conductor flex wire or extending the original wiring and giving connections as required
OD269117/2025-2026: Supply, conveyance, installation, testing and commissioning the light fittings made from 0.5mm CRCA sheet complete with all accessories and lamps etc. directly on wall using 2 nos. 'C/U' brackets made from 20 x 3 mm MS flat, painting the flat iron bracket and giving connections with required length of 16/0.20mm 3 core copper conductor flex wire conforming to relevant ISS or extending the original wiring and giving connection etc. as required. including providing 1200 mm 20 W T8 LED tube , having total efficiency of 100 Lumen /watt with 4 feet Aluminium extrusion in the tube for better heat dissipation,, THD < 20% PF> 0.95 ( LM 79 & LM 80 Certificate from NABL should be submitted )
OD271718/2025-2026: Supply, conveyance installation testing and commissioning the light fittings made of CRCA sheet with 0.5mm thickness complete with all accessories and lamps etc. directly on wall or ceiling, neatly painted to suit the fitting giving connections with required length of 16/0.20mm 3 core copper conductor flex wire conforming to relevant ISS or extending the original wiring and giving connection etc. as required. including providing 1200 mm 20 W T8 LED tube , having total efficiency of 100 Lumen /watt with 4 feet Aluminium extrusion in the tube for better heat dissipation,, THD 0.95 ( LM 79 & LM 80 Certificate from NABL should be submitted )
OD271724/2025-2026: Supply, conveyance, installation, testing and commissioning the light fittings of following types made of .5mm thick CRCA sheet accessories and lamps etc. including supplying and fixing ball and socket arrangements on PVC round block, suspension down rod of 19mm dia MS conduit up to 2x30cm length including painting and wiring the down rod with 16/0.20mm 3 core round copper conductor flex wire conforming to relevant ISS or extending the original wiring andgiving connections with required length of 16/0.20mm 3 core copper conductor flex wire conforming to relevant ISS or extending the original wiring and giving connection etc. as required. including providing 1200 mm 20 W T8 LED tube , having total efficiency of 100 Lumen /watt with 4 feet Aluminium extrusion in the tube for better heat dissipation,, THD < 20% PF> 0.95 ( LM 79 & LM 80 Certificates from NABL should be submitted )
90.15.4.5:Supply Conveyance, installation, testing and commissioning of 40W LED Flood light output greater than 105lumen/W 4000-6000 K with IP 66 protection LED Chip make Cree/Lumilled/Nichea with power factor greater than 0.95 at full load, internal surge protection up to 8 KV,and Aluminium pressure die-cast Powder coated housing, acrylic cover complete with THD less than10%, power factor greater than 0.98, RoHS compliant, duly wired up for use on 230 V AC supply. Driver compartment should be seperatly accessible for maintenance (LM 79&80 certificates from NABL accredited Third party lab to be produced mentioning chip manufacturer)
OD257103/2025-2026:Supply, conveyance,installation ,testing and commissioning of 400mm sweep wall mounting fan with metallic blades , blade covers, body, mounting brackets etc with existing wires orient/havells/crompton make
OD147715/2025-2026:Supply and installation, testing and commissioning of 225 mm sweep, Exhaust fan working on 230 V A/C supply including connections with the supply wire along with the exhaust fan
OD147716/2025-2026:Supply of 305mm sweep,1400rpm heavy duty exhaust fan working on 230V single phase ac , air delivery 6120m3/hr, metal frame in the existing opening
90.4.8:Charges for cutting holes suitable for accommodating exhaust fans up to 305mm sweep including plastering colour washing etc. as required.
90.4.5.4:Supply, Installation, testing and commissioning of ceiling fan of following sizes including wiring the down rods of standard length (up to 30 cm) with 1.5 sq. mm FRLS PVC insulated, copper conductor, single core cable etc. as required. 1200mm sweep - ceiling fan complete with service value minimum 4.0(cub meter/minute/Watt), Air delivery minimum 210(cubic meter/minute), Copper winding suitable for 230V/240V single phase AC supply
90.4.1:Supply and installation of suitable size MS rod type fan clamp in the RCC slab as per IS 732 as required.
1.25:Supplying and fixing two module stepped type electronic fan regulator on the existing modular plate switch box including connections but excluding modular plate etc. as required.
90.15.3.2:Supply installation testing commissioning of Octogaonal Pole made of hot dip galvanised GI sheet 70mm top diameter, 130mm bottom diameter thickness 3mm base plate dimensions of 200x200x12mm suitable for wind speed as per IS 875 Part III double arm bracket 0.5mt including connector foundation bolt 4 nos fixed in existing RCC foundation and junctions box etc.complete 5 Meters
90.15.4.2:Supply Conveyance, installation, testing and commissioning of 36/40W LED street light output greater than 105lumen/W 4000-6000 K with IP 66 protection LED Chip make Cree/Lumilled/Nichea with power factor greater than 0.95 at full load, internal surge protection up to 8 KV,and Aluminium pressure die-cast Powder coated housing,acrylic cover complete with THD less than 10%, power factor greater than 0.98, RoHS compliant, duly wired up for use on 230 V AC supply. Driver compartment should be seperatly accessible for maintenance (LM 79&80 certificates from NABL accredited Third party lab to be produced mentioning chip manufacturer)
90.6.5.11:Supply and drawing the following sizes of multi-core PVC insulated & FRLS PVC sheathed 650/1100 V grade copper conductor round flexible cables conforming to IS 694 part I 1960 in the existing surface / recess conduit as required including giving necessary connections of the following sizes.3 core 1.50 sq mm
OD257106/2025-2026:Supply and installation of SINTEX loop box GSJB-1510 with suitable bakelite connector and necessary connections as required
1.24.4:Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.3 pin 5/6 amp socket outlet
1.24.1:Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.5/6 amps switch
1.24.5:Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.6 pin 15/16 amp socket outlet
1.24.3:Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.15/16 amp switch
1.27.2:Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required.3 Module (100mmX75mm)
90.10.1.2:Supply & Fixing the following types/ sizes of boxes suitable for modular accessories in surface/ recess including making good the damages, colour washing etc as required (RoHS compliant )2 module moulded plastic box on surface
1.27.5:Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required.8 Module (125mmX125mm)
90.10.1.6:Supply & Fixing the following types/ sizes of boxes suitable for modular accessories in surface/ recess including making good the damages, colour washing etc as required (RoHS compliant )8 module moulded plastic box on surface
1.28.5:Supplying and fixing following Modular base & cover plate on existing modular metal boxes etc. as required.8 Module
1.27.4:Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required.6 Module (200mmX75mm)
90.10.3.33:Supply and Fixing the following modular switches & accessories in the existing front plates and giving necessary connections as required (RoHS compliant )25A 3pin Shuttered socket
90.10.3.15:Supply and Fixing the following modular switches & accessories in the existing front plates and giving necessary connections as required (RoHS compliant )32A DP switch with indicator
1.27.1:Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required.1 or 2 Module (75mmX75mm)
1.14.1:Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface / recessed medium class PVC conduit as required2x1.5 sq.mm + 1x1.5 sq.mm earth wire
1.17.3:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 X 1.5 sq.mm
1.17.6:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.6 x 1.5 sq. mm
1.17.12:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 x 2.5 sq. mm
1.17.15:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.6 x 2.5 sq. mm
1.17.21:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 x 4 sq. mm
1.17.22:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.4 x 4 sq. mm
1.17.24:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.6 x 4 sq. mm
1.17.9:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.9 x 1.5 sq. mm
4.1.3:Supplying and installing following size of perforated painted with powder coating M.S. cable trays with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc as required. 225 mm width X 50 mm depth X 1.6 mm thickness
4.3.3:Supplying and installing following size of perforated painted with powder coating M.S. cable trays Tee with perforation not more than 17.5%, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc as required. 225mm width X 50 mm depth X 1.6 mm thickness
90.9.2.1:Supply and fixing 100 x 50 mm PVC Cable Management System with base and lid along with the following accessories conforming to IEC 61084/ BS 476 & 4678 on surface / recess including cutting the wall and making good the damages in case of recessed installation as required.100 x 50 mm CMS with base and lid
90.9.2.3:Supply and fixing 100 x 50 mm PVC Cable Management System with base and lid along with the following accessories conforming to IEC 61084/ BS 476 & 4678 on surface / recess including cutting the wall and making good the damages in case of recessed installation as required.External angle 90 degree
90.9.2.5:Supply and fixing 100 x 50 mm PVC Cable Management System with base and lid along with the following accessories conforming to IEC 61084/ BS 476 & 4678 on surface / recess including cutting the wall and making good the damages in case of recessed installation as required.Internal angle 90 degree
90.9.2.8:Supply and fixing 100 x 50 mm PVC Cable Management System with base and lid along with the following accessories conforming to IEC 61084/ BS 476 & 4678 on surface / recess including cutting the wall and making good the damages in case of recessed installation as required.End cap
1.21.1:Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required.20 mm
1.21.2:Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required.25 mm
OD150051/2025-2026:Supplying and fixing FP enclosure MCB DB sheet steel Phosphatised, painted, dust and vermin proof enclosure on surface/ recess complete with connections, testing and commissioning etc. as required
2.16:Supplying and fixing DP sheet steel enclosure on surface/ recess along with 25/32amps 240 volts "C" curve DP MCB complete with connections, testing and commissioning etc. as required.
2.3.1:Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 volts, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) 6 way, Double door
2.3.4:Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 volts, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) 16 way, Double door
2.3.3:Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 volts, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) 12 way, Double door
2.12.1:Supplying and fixing following rating, double pole, 240 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.40 amps
2.14.2:Supplying and fixing following rating, double pole, (single phase and neutral),240 volts, residual current circuit breaker (RCCB), having a sensitivity current 30 milli amperes in the existing MCB DB complete with connections, testing and commissioning etc. as required. 40 amps
2.14.1:Supplying and fixing following rating, double pole, (single phase and neutral),240 volts, residual current circuit breaker (RCCB), having a sensitivity current 30 milli amperes in the existing MCB DB complete with connections, testing and commissioning etc. as required. 25 amps
2.10.1:Supplying and fixing 5A to 32 A rating, 240/415 volts, 10 kA, ""C"" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. Single pole
2.10.4:Supplying and fixing 5A to 32 A rating, 240/415 volts, 10 kA, ""C"" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. Triple pole
2.11:Supplying and fixing single pole blanking plate in the existing MCB DB complete etc. as required.
OD150248/2025-2026:Supplying and fixing 40 amps to 63 amps rating, 415 volts, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. Triple pole
90.11.1.10:Supply and installation of sheet steel, phosphatised and painted, dust and vermin proof enclosure of MCB DB including copper /brass bus bar, neutral link, earth bus and DIN rail suitable for fixing MCB/ isolator etc. fixed on wall using suitable anchor bolts or fixed in recess including cutting hole on the wall , making good the damages, colour washing etc. as required4 way (8+12) - three phase double cover (IP 42/43)
90.11.1.11:Supply and installation of sheet steel, phosphatised and painted, dust and vermin proof enclosure of MCB DB including copper /brass bus bar, neutral link, earth bus and DIN rail suitable for fixing MCB/ isolator etc. fixed on wall using suitable anchor bolts or fixed in recess including cutting hole on the wall , making good the damages, colour washing etc. as required6 way (8+18) - three phase double cover (IP 42/43)
2.13.1:Supplying and fixing following rating, four pole, 415 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.40 amps
2.15.2:Supplying and fixing following rating, four pole, (three phase and neutral), 415 volts, residual current circuit breaker (RCCB), having a sensitivity current 30 milli Amperes in the existing MCB DB complete with connections, testing and commissioning etc. as required. 40 amps
2.15.1:Supplying and fixing following rating, four pole, (three phase and neutral), 415 volts, residual current circuit breaker (RCCB), having a sensitivity current 30 milli Amperes in the existing MCB DB complete with connections, testing and commissioning etc. as required. 25 amps
90.11.1.14:Supply and installation of sheet steel, phosphatised and painted, dust and vermin proof enclosure of MCB DB including copper /brass bus bar, neutral link, earth bus and DIN rail suitable for fixing MCB/ isolator etc. fixed on wall using suitable anchor bolts or fixed in recess including cutting hole on the wall , making good the damages, colour washing etc. as required4 way (8+12) - double cover TPN vertical DB with provision for fixing 4P MCB / Isolator/ RCCB/ RCBO as incomer and SP/ TP MCB as outgoing (IP 42/43)
90.11.1.19:Supply and installation of sheet steel, phosphatised and painted, dust and vermin proof enclosure of MCB DB including copper /brass bus bar, neutral link, earth bus and DIN rail suitable for fixing MCB/ isolator etc. fixed on wall using suitable anchor bolts or fixed in recess including cutting hole on the wall , making good the damages, colour washing etc. as required6 way (8+12) - double cover TPN vertical DB with provision for fixing MCCB as incomer and SP/ TP MCB as outgoing (IP 42/43)
90.14.10.4:Supply, conveyance and fixing the following types & current rated control gears & switchgears conforming to IS 13947 suitable for 440 V, 50 Hz, AC supply in the existing panel assembly as required.16 A-100A, 25/35 kA (Ics=100%Icu), 4 pole, current limiting type MCCB having thermal setting range of 80 - 100% with thermal magnetic release having adjustable OL
90.12.5.38:Supply & laying of one number PVC insulated and PVC sheathed armoured aluminium power cable of 1.1KV grade of the following sizes in the existing RCC/ HUME / STONE WARE/ GI/ DWC pipe as required.4 core 4 sq mm
90.12.7.38:Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.4 core 4 sq mm with factory made clamp
90.12.7.39:Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.4 core 6 sq mm with factory made clamp
90.12.7.40:Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.4 core 10 sq mm with factory made clamp
90.12.7.41:Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.4 core 16 sq mm with factory made clamp
OD150897/2025-2026:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. 4 X 6 sq. mm
9.1.33:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.4 X 16 sq. mm (28mm)
9.1.32:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.4 X 10 sq. mm (25mm)
90.12.7.29:Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.3.5 core 50 sq mm with factory made clamp
9.1.22:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 1/2 X 50 sq. mm (35mm)
90.16.1.1:Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required2.00 mm copper conductor ( 14 SWG)
90.16.5.1:Supply of superior quality copper earth socket for the following size of earth conductor including crimping etc. as required.2.00 mm (14 SWG)
90.16.1.2:Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required2.65 mm copper conductor (12 SWG)
90.16.1.3:Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required3.15 mm copper conductor ( 10 SWG)
90.16.1.4:Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required4.00 mm copper conductor ( 8 SWG)
90.16.5.4:Supply of superior quality copper earth socket for the following size of earth conductor including crimping etc. as required.4.00 mm (8 SWG)
90.16.5.2:Supply of superior quality copper earth socket for the following size of earth conductor including crimping etc. as required.2.65 mm (12 SWG)
90.16.5.3:Supply of superior quality copper earth socket for the following size of earth conductor including crimping etc. as required.3.15 mm (10 SWG)
90.14.11.1:MCCB AccessoriesSupply and fixing one number earth fault Relay up to 100A with CBCT.
OD151153/2025-2026:S&F Spreader/terminal adapter kit extended terminal for 3/ 4 pole MCCB rating upto 250A (8 Pcs)
90.14.11.12:MCCB AccessoriesSupply and fixing shunt release for all voltage range up to 630A.
OD150257/2025-2026: SITC of multi function meter VAF 3 Phase class 1
OD150258/2025-2026:Supply & fixing 100/ 5 A, 5 VA, resin cast metering CT of accuracy class 0.5
OD150259/2025-2026:supply and fixing Red , Yellow & blue colour LED indicator, AC/DC, as required
OD150260/2025-2026:Supply and fixing 2A SP MCB L and T make/eqt
OD151622/2025-2026:Carrying out control wiring for panel with normal meters and indication lamps alone with 650/1100 V grade PVC insulated stranded single core copper conductor cables conforming to IS 694 part I 1990 for interconnecting the control devices/ equipments including providing suitable size insulated sockets at the termination points or soldered properly, providing numbering ferrules for the proper identification of the wiring, keeping the wiring firm by suitable tie/ tie mounts/ PVC duct etc as required. 1.50 sq mm single run with required sockets.
OD150262/2025-2026:Supply and installation of Change Over Switch in sheet steel enclosure complete with handle assembly, door interlock and pad locking arrangement of the following ratings on existing angle iron frame work or directly to wall using necessary bolts & nuts, fixing the unit to wall, making good the damages, colour washing etc. including giving necessary connections as required. 100 A 4 pole on-load COS AC 23A duty
OD150611/2025-2026:Supply and fixing 100 A HRC fuse base with HRC fuse link on the existing metering cubicle and giving connection as required
OD150612/2025-2026:Supplying and fixing 100 A Neutral link with connections, in existing meter board
2.1.3:Providing and fixing following capacity TP&N disconnector fuse switch unit inside the existing panel board with ISI marked HRC fuses including drilling holes in cubicle panel, making connections, etc. as required.100 Amp TP&N
90.14.5:Supply and fabrication conveyance and installation of angle iron frame work for wall mounting panel board
90.14.3.1:Supply and providing heavy duty 'A' section neoprene gasket in the panel boardA' section neoprene beeding suitable for 1.60/ 2.00 mm sheet
5.4:Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required.
90.12.10.2:Supply & laying of DWC pipe in ordinary soil 0.75m below ground level including excavation50/38 mm or nearest size
14.7:Providing and laying in position cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) in foundation of pump, DG set etc including form work etc as required.
14.10:Providing and laying in position reinforced cement concrete 1 :2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) in foundation of pump, DG set etc. including form work etc. as required (excluding reinforcement).
OD257148/2025-2026:Steel reinforcement for RCC Work including straightening, cutting, bending, placing in position and binding all complete
14.1:Excavation for foundation in soft soil including dressing of sides and ramming of bottoms, lift upto 1.5 m including getting out the excavated soil and disposal of surplus excavated soil as directed, within a lead of 50 metres.
OD255347/2025-2026:Supply, conveyance , installation , testing and commissioning of 3HP, three phase Bore well submersible motor pump set with Head Range 75M to 150M discharge range 500LPH to 3000LPH Outlet size 32MM. texmo/kirloscar/CRI eqt complete including trail run etc as required
OD255342/2025-2026:Supply installation testing ad commissioning DOL motor controller with ammeter, voltmeter, electronic single phasing preventer, Indication lamps etc suitable for for Three phase 3HP motor pump set and giving necessary connections etc as required reputed make/eqt
OD255343/2025-2026: Supply and providing 1.25" fittings such as GI bend coupling cover, bend, clamp hose collar
OD255346/2025-2026:Supply and providing 32 mm UPVC heavy duty High pressure column Pipe (SCH 40 ) for the existing bore well motor pump set reputed Make including all necessary connected accessories
OD255348/2025-2026:Supply and laying of 20mm or nearest size Nylon rope
90.6.6.3:Supply and drawing FRLS PVC insulated & sheathed 650/1100 V grade 3 core copper conductor flat cable for submersible pump motor conforming to IS 694 part I 1990 as required including giving necessary connections of the following sizes.4 sq mm
90.16.2.2:Supply and laying of the following sizes of B class GI pipe laid 0.6 m below ground level including excavating trench of suitable size and refilling etc, as required.20 mm dia. G.I pipe ( medium class)
90.16.2.3:Supply and laying of the following sizes of B class GI pipe laid 0.6 m below ground level including excavating trench of suitable size and refilling etc, as required.32 mm dia G.I pipe ( medium class)
OD257147/2025-2026:Supply , Installation , Testing and Commissioning of 2 kVA Online UPS - Single Phase input to Single Phase Output, Online UPS With isolation transformer , High frequency and double conversion online technology, Rated battery voltage 48V DC , Lightning and Surge protection , EMI/RFI noise filter, DSP technology, High efficiency up to 95.5% ,OUTPUT PF = 1, High load adaptability, Wide input Voltage range of 110-300 Vac, Maximum charging current upto 12 A.IGBT technology for fast switching and better efficiency and an advanced battery management system- 3000 W with 2 years warranty, Certified with 4Nos 12V 100 AH SMF Battery with 2 years warranty , including all connections and battery stand hykon/reputed eqt make
OD257146/2025-2026:Supply , Installation , Testing and Commissioning of Inline single phase input - single phase output HOME UPS of rating 2 KVA / 24VDC , automatic voltage regulation, pure sine wave output, advanced bat Trey chargiong technology, low power consumption, surge protection with 2nos 100AH/12V C20 Tubular batteries , with Interconnecting cable, Nut & Bolt etc with suitable stand Hykon MODEL SP plus 2500/24V hom UPS eqt make
OD275749/2025-2026:Supply, Conveyance Installation of Fire Extinguisher-CO2 4.5 Kg Type on the wall/floor with necessary brackets as required.
Please Enable Macros to View BoQ information
stage.html
html • 0.04 MB
tech_eval.pdf
fin_eval.pdf
aoc.pdf
finance_1390816.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Tendernotice_1.pdf
PDF • 0.12 MB
Tendernotice_2.pdf
PDF • 0.10 MB
Tendernotice_3.pdf
PDF • 0.02 MB
viewnit.pdf
Tender Documents • 0.05 MB
BOQ_1390816.xls
BOQ • 0.39 MB
sbd.pdf
Tender Documents • 1.65 MB
Download all tender documents and submit your bid