Loading…
Loading…
| # | Company | Quoted % | Amount | Rank | Status |
|---|---|---|---|---|---|
| 1 | L1₹38.1 LAdmitted-Finance | -28.30% | ₹38.1 L | L1 | Admitted-Finance |
| 2 | L2₹38.5 LAdmitted-Finance 12 A GAHMARKUNJ CHINHAT MATIYARI LUCKNOW UTTAR PRADESH 226017 UDYAM UP 50 0042074 | LUCKNOW | UTTAR PRADESH | 226017 | -27.62% | ₹38.5 L | L2 | Admitted-Finance |
| 3 | L3₹46.1 LAdmitted-Finance | -13.20% | ₹46.1 L | L3 | Admitted-Finance |
Tender Value
₹53.2 L
EMD Value
₹1.1 L
Closing Date
9 Feb 2026, 2:00 pmClosed
Shri. S K Dubey, Sc F, CCE
CCE (RnD) Estates South Chandrayangutta Hyderabad - 05
Provision of 2 x Utility Rooms with Epoxy Antistatic Flooring Near Building No. 16E in Technical Area at Site-G SF Complex, Jagdalpur
2026_DRDO_894656_1
CCEESTS/ENQ/CIV/2 X UTILITY /JPR/ 222/2025-26
Open Tender
Miscellaneous Works
365 days
SF Complex, Jagdalpur
Please refer Tender documents.
5 documents required · 5 mandatory
₹0
₹1.1 L
16 Feb 2026
19 Jan 2026
10 Feb 2026
19 Jan 2026
9 Feb 2026
19 Jan 2026
SUBHEAD - I EARTH WORK AND EXCAVATION
Clearing jungle including uprooting of rank vegetation, grass, brush wood, trees and saplings of girth up to 30 cm measured at a height of 1 m above ground level and removal of rubbish up to a distance of 50 m outside the periphery of the area cleared.
Earth work in excavation by mechanical means (Hydraulic excavator) / manual means in foundation trenches or drains (not exceeding 1.5 m in width or 10 sqm on plan), including dressing of sides and ramming of bottoms, lift upto 1.5 m, including getting out the excavated soil and disposal of surplus excavated soil as directed, within a lead of 50 m. All kinds of soil
Filling available excavated earth (excluding rock) in trenches, plinth, sides of foundations etc. in layers not exceeding 20cm in depth, consolidating each deposited layer by ramming and watering, lead up to 50 m and lift upto 1.5 m.
Supplying and filling in plinth with sand under floors, including watering, ramming, consolidating and dressing complete.
Supplying chemical emulsion in sealed containers including delivery as specified. Chlorpyriphos/Lindane emulsifiable concentrate of 20%
Diluting and injecting chemical emulsion for Pre & Post -CONSTRUCTIONAL anti-termite treatment (excluding the cost of chemical emulsion) : Along external wall where the apron is not provided using chemical emulsion @ 7.5 litres / sqm of the vertical surface of the substructure to a depth of 300mm including excavation channel along the wall & rodding etc. complete: With Chlorpyriphos/Lindane E.C. 20% with 1% concentration
Treatment of soil under floors using chemical emulsion @ one litre per hole, 300 mm apart including drilling 12 mm diameter holes and plugging with cement mortar 1 :2 (1 cement : 2 Coarse sand) to match the existing floor. With Chlorpyriphos/Lindane E.C. 20% with 1% concentration.
SUBHEAD- II PLAIN AND REINFORCED CEMENT CONCRETE WORK.
Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level :1:4:8 (1 Cement : 4 coarse sand (zone-III) derived from natural sources : 8 graded stone aggregate 40 mm nominal size derived from natural sources)
Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level 1:2:4 (1 cement : 2 coarse sand (zone-III) derived from natural sources : 4 graded stone aggregate 20 mm nominal size derived from natural sources)
Providing and laying cement concrete in retaining walls, return walls, walls (any thickness) including attached pilasters, columns, piers, abutments, pillars, posts, struts, buttresses, string or lacing courses, parapets, coping, bed blocks, anchor blocks, plain window sills, fillets, sunken floor etc., up to floor five level, excluding the cost of centering, shuttering and finishing:1:2:4 (1 Cement : 2 coarse sand (zone-III) derived from natural sources : 4 graded stone aggregate 20 mm nominal size derived from natural sources)
Providing and laying in position ready mixed or site batched design mix cement concrete for reinforced cement concrete work; using coarse aggregate and fine aggregate derived from natural sources, Portland Pozzolana / Ordinary Portland /Portland Slag cement, admixtures in recommended proportions as per IS: 9103 to accelerate / retard setting of concrete, to improve durability and workability without impairing strength; including pumping of concrete to site of laying, curing, carriage for all leads; but excluding the cost of centering, shuttering, finishing and reinforcement as per direction of the engineer-in-charge; for the following grades of concrete. Note: Extra cement up to 10% of the minimum specified cement content in design mix shall be payable separately. In case the cement content in design mix is more than 110% of the specified minimum cement content, the contractor shall have discretion to either re-design the mix or bear the cost of extra cement:
All works upto plinth level
Concrete of M25 grade with minimum cement content of 330 kg /cum
All works above plinth level upto floor V level
Concrete of M25 grade with minimum cement content of 330 kg /cum
Steel reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding all complete (Below & above plinth & at all heights.Thermo-Mechanically Treated bars of grade Fe-500D or more.
Centering and shuttering including strutting, propping etc. and removal of form for
Foundations, footings, bases of columns, etc. for mass concrete
Columns, Pillars, Piers, Abutments, Posts and Struts
Lintels, beams, plinth beams, girders, bressumers and cantilevers with water proof ply 12 mm thick
Weather shade, Chajjas, corbels etc., including edges
Suspended floors, roofs, landings, balconies and access platform
Extra for additional height in centering, shuttering where ever required with adequate bracing, propping etc., including cost of de-shuttering and decentering at all levels, over a height of 3.5 m, for every additional height of 1 metre or part thereof (Plan area to be measured). Suspended floors, roofs, landing, beams and balconies (Plan area to be measured)
Making plinth protection 50mm thick of cement concrete 1:3:6 (1 cement : 3 coarse sand (zone-III) derived from natural sources : 6 graded stone aggregate 20 mm nominal size derived from natural sources) over 75mm thick bed of dry brick ballast 40 mm nominal size, well rammed and consolidated and grouted with fine sand/ M-Sand, including necessary excavation, levelling & dressing & finishing the top smooth.
SUBHEAD - III BRICK MASONRY WORK .
Random rubble masonry with hard stone in foundation and plinth including levelling up with cement concrete 1:6:12 (1 cement : 6 coarse sand : 12 graded stone aggregate 20 mm nominal size) upto plinth level with :Cement mortar 1:6 (1 cement : 6 coarse sand)
Pointing on stone work with cement mortar 1:3 (1 cement : 3 fine sand) :
Raised and cut pointing
Brick work with fly ash bricks. (non modular) bricks of class designation 7.5 in foundation and plinth in: Cement mortar 1:6 (1 cement : 6 coarse sand)
Providing brick work with non modular fly ash bricks conforming to IS:12894,class designation 10 average compressive strength in super structure above plinth level upto floor V level in: Cement Mortar 1:6 ( 1 cement : 6 coarse sand )
SUBHEAD - IV : PLASTERING AND SURFACE TREATMENT
Providing of 6mm cement plaster of mix in all surface with cement mortar 1:3 (1 cement : 3 fine sand / M-Sand ) at all levels
Providing of 12 mm cement plaster of mix in all surface with cement mortar 1:6 (1 cement : 6 fine sand / M-Sand ) at all levels.
15 mm cement plaster on the rough side of single or half brick wall.1:6(1 cement:6 coarse sand)
18 mm cement plaster in two coats under layer 12 mm thick cement plaster 1:5 (1 cement : 5 coarse sand) and a top layer 6 mm thick cement plaster 1:3 (1 cement : 3 coarse sand) finished rough with sponge.
White washing with lime to give an even shade : New Work (three or more coats)
Distempering with oil bound washable distemper of approved brand and manufacture to give an even shade :New work (two or more coats) over and including water thinnable priming coat with cement primer
Finishing walls with Acrylic Smooth exterior paint of required shade : New work (Two or more coat applied @ 1.67 ltr/10 sqm over and including priming coat of exterior primer applied @ 2.20 kg/10 sqm)
Providing and applying white cement based putty of average thickness 1 mm, of approved brand and manufacturer, over the plastered wall surface to prepare the surface even and smooth complete.
Applying priming coat:
With ready mixed red oxide zinc chromate primer of approved brand and manufacture on steel galvanised iron/ steel works
Painting with synthetic enamel paint of approved brand and manufacture to give an even shade :
Two or more coats on new work
SUBHEAD - V: FLOORING
Providing and laying C.C. pavement of mix M-25 with ready mixed concrete from batching plant. The ready mixed concrete shall be laid and finished with screed board vibrator , vacuum dewatering process and finally finished by floating neat cement, thread lining 600 x 600mm. complete as per specifications and directions of Engineer-incharge
Finishing with Epoxy paint (two or more coats) at all locations prepared and applied as per manufacturer's specifications including appropriate priming coat, preparation of surface, etc. complete.
Cement plaster skirting up to 30 cm height, with cement mortar 1:3 (1 cement : 3 coarse sand), finished with a floating coat of neat cement. 18 mm thick
SUBHEAD -VI : DOOR WINDOW & WOOD WORK
Providing and fixing pressed steel door frames conforming to IS: 4351, manufactured from commercial mild steel sheet of 1.60 mm thickness, including hinges, jamb, lock jamb, bead and if required angle threshold of mild steel angle of section 50x25 mm, or base ties of 1.60 mm, pressed mild steel welded or rigidly fixed together by mechanical means, including M.S. pressed butt hinges 2.5 mm thick with mortar guards, lock strike-plate and shock absorbers as specified and applying a coat of approved steel primer after pre-treatment of the surface as directed by Engineer-in-charge: Profile C Fixing with adjustable lugs with split end tail to each jamb
Steel work welded in built up sections/ framed work, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer using structural steel etc. as required.
In gratings, frames, guard bar, ladder, railings, brackets, gates and similar works
Drilling suitable holes in reinforced or plain cement concrete with power driven drill machine to a minimum depth of 100mm upto 200mm in RCC beams, lintels, columns and slabs to introduce steel bars for sunshades/balconies including fixing the steel bars in position using epoxy resin anchor grout of approved make but excluding the cost of reinforcement, all complete as per direction of Engineer-In-Charge.
Upto and including 12mm dia.
From 12 to 20 mm mm dia
Wired glass
Providing and fixing M.S. grills of required pattern in frames of windows etc. with M.S. flats, square or round bars etc. including priming coat with approved steel primer all complete.
Fixed to openings /wooden frames with rawl plugs screws etc.
SUBHEAD - VII : ROOFING & WATER PROOFING
Providing and fixing on wall face unplasticised Rigid PVC rain water pipes conforming to IS : 13592 Type A, including jointing with seal ring conforming to IS : 5382, leaving 10 mm gap for thermal expansion, (i) Single socketed pipes.
a) 110 mm diameter
Providing and laying integral cement based water proofing treatment including preparation of surface as required for treatment of roofs, balconies, terraces etc consisting of following operations:
a)Applying and grouting a slurry coat of neat cement using 2.75 kg/sqm. of cement admixed with water proofing compound conforming to IS:2645 and approved by Engineer - in- charge over the RCC slab including adjoining walls up to 300 mm height including cleaning the surface before treatment.
b)Laying cement concrete using broken bricks/brick bats 25 mm to 115 mm size(Brick to be used second class) with 50% of cement mortar 1:5 (1 cement : 5 coarse sand) admixed with water proofing compound conforming to IS: 2645 and approved by Engineer - in- charge over 20mm thick layer of cement mortar of mix 1:5 (1 cement: 5 coarse sand) admixed with water proofing compound conforming to IS2645 and approved by Engineer - in- charge to required slope and treating similarly the adjoining walls up to 300 mm height including rounding of junctions of walls and slabs.
c)After two days of proper curing applying a second coat of cement slurry admixed with proprietary water proofing compound conforming to IS:2645 and approved by Engineer - in- charge .
d)Finishing the surface with 20 mm thick joint less cement mortar of mix 1:4 (1 cement : 4 coarse sand) admixed with water proofing compound conforming to IS:2645 and approved by Engineer - in- charge including laying glass fibre cloth of approved quality in top layer of plaster and finally finishing the surface with trowel with neat cement slurry and making of 300x300 mm square 3mm deep.
e)The whole terrace so finished shall be flooded with water for a minimum period of two weeks for curing and for final test. All above operations to be done in order and as directed and specified by the Engineer-in-Charge.
With average thickness of 120 mm and minimum thickness at khurra as 65 mm.
SUBHEAD - VIII:ROAD/HARD STANDINGS
Earth work in excavation by mechanical means (Hydraulic excavator)/ manual means over areas (exceeding 30 cm in depth, 1.5 m in width as well as 10 sqm on plan) including getting out and disposal of excavated earth lead upto 50 m and lift upto 1.5 m, as directed by Engineer-incharge. All kinds of soil.
Excavating, supplying and filling of local earth (including royalty) by mechanical transport upto a lead of 5km also including ramming and watering of the earth in layers not exceeding 20 cm in trenches, plinth, sides of foundation etc. complete.
Preparation and consolidation of sub grade with power road roller of 8 to 12 tonne capacity after excavating earth to an average of 22.5 cm depth, dressing to camber and consolidating with road roller including making good the undulations etc. and re-rolling the sub grade and disposal of surplus earthwith lead upto 50 metres.
Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level :1:4:8 (1 Cement : 4 coarse sand (zone-III) derived from natural sources : 8 graded stone aggregate 40 mm nominal size derived from natural sources)
Providing and laying C.C. pavement of mix M-25 with ready mixed concrete from batching plant. The ready mixed concrete shall be laid and finished with screed board vibrator , vacuum dewatering process and finally finished by floating, brooming with wire brush etc. complete as per specifications and directions of Engineer-in charge. (The panel shuttering work shall be paid for separately). (Note:- Cement content considered in this item is @ 330 kg/cum. Excess/less cement used as per design mix is payable/ recoverable separately).
SUBHEAD - IX: AREA DEVELOPMENT & DRAINAGE
Earth work in excavation by mechanical means (Hydraulic excavator) / manual means in foundation trenches or drains (not exceeding 1.5 m in width or 10 SQM on plan), including dressing of sides and ramming of bottoms, lift upto 1.5 m, including getting out the excavated soil and disposal of surplus excavated soil as directed, within a lead of 50 m.
All Kinds of soil
Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering -All work upto plinth level :
1:4:8 (1 Cement : 4 Coarse sand (Zone III) derived from natural sources) : 8 Graded stone aggregate 40 mm nominal size derived from natural sources)
Brick work with common burnt clay F.P.S. (non modular) bricks of class designation 7.5 in foundation and plinth in Cement mortar 1:6 (1 cement : 6 coarse sand)
Providing and laying cement concrete 1:2:4 (1 Cement : 2 coarse sand (zone-III) derived from natural sources : 4 graded stone aggregate 20 mm nominal size derived from natural sources) in retaining walls, return walls, walls (any thickness) including attached pilasters, columns, piers, abutments, pillars, posts, struts, buttresses, string or lacing courses, parapets, coping, bed blocks, anchor blocks, plain window sills, fillets, sunken floor etc., upto floor five level, excluding the cost of centering, shuttering and finishing
Providing of 12mm cement plaster of mix in all surface with (a) cement mortar 1:6 ( 1 cement : 6 fine sand ) at all levels
SUB HEAD - X INTERNAL ELECTRIFICATION (FLAME PROOF FIXTURES)
Supply and Fix Flame proof fluorescent tube light fitting 2X40 watt 4 feet day light 240 volts 50 Hz, 100 lumens per watt single phase as per IS/IEC 60079-1 : 2014, weather proof IP-66 as per IS/IEC 60529 : 2001 (Reaffired 2014) as per specification of CIMFR, BIS and PESO, Tempered true class- T6, die cast aluminium alloy shades as per IS : 5 and 01 No. Internal and 02 No external earthing, Gasket ‘o” ring SS name plate cum wiring plate, including tube rod PL/LED and necessary connection, all as per Make SUDHIR cat No- FF/1272 and Cat Part No- FF/OA/1272/2PL36 or equivalent make as per manufacturer specifications, complete all as directed.
Supply and Fix Flame proof Bulk head light fitting 45 watt day light 240 volts 50 Hz, 100 lumens per watt single phase as per IS/IEC 60079-1 : 2014, weather proof IP-66 as per IS/IEC 60529 : 2001 (Reaffired 2014) as per specification of CIMFR, BIS and PESO, Tempered true class- T6, die cast aluminium alloy shades as per IS : 5 and 01 No. Internal and 02 No external earthing, Gasket ‘o” ring SS name plate cum wiring plate, including tube rod PL/LED and necessary connection, all as per Make SUDHIR cat No- BH/124 and Cat Part No- FF/OA/124/2PL36 or equivalent make as per manufacturer specifications, complete all as directed.
Supply and fix Flame proof and weather proof FLP-WP Rotary switch with cable terminal chamber in LM6, 16 Amps single pole ON-OFF Rotary switch, suitable for light fittings IP-66 (Reaffired 2014) as per specification of CIMFR, BIS and PESO, Tempered true class- T6, die cast aluminium alloy shades single phase 240 volts, Make SUDHIR Cat No- RI/105 and Cat Part No- RI/OA/1010-2A or equivalent make complete all as per manufacturer specifications, controlled for four light points with necessae=ry connection, complete all as specified and as directed.
Supply and fix Flame proof and weather proof Rotery switch Socket 16 Amps, 2 Pin +Earth and including Horizontal Pins, single phase 240 volts with termination chember, LM6, IP-66 IS/IEC 60529 :2001 (Reaffired 2014) as per specification of CIMFR, BIS and PESO, Tempered true class- T6, die cast aluminium alloy shades as per IS : 5 and 01 No. Internal and 02 No external earthing, Gasket ‘o” ring SS name plate cum wiring plate, including tube rod PL/LED and necessary connection, all as per Make SUDHIR cat No- SS/2C/2021 and Cat Part No- SS/OA/1010-3 or equivalent make as per manufacturer specifications, complete all as directed.
Supply and Fixing for Flame Proof flexible metalic Hose Conduit 3/4” ET HEX made out of Brass Make-SUDHIR Cat Part No- ACC/2C/2019 or equivalent complete all as manufacturer Specification and as directed.
Supply and Fixing for Flame Proof Plug 3/4” ET HEX made out of Brass Make-SUDHIR Cat Part No- ACC/2C/2019 or equivalent complete all as manufacturer Specification and as directed.
Earthing with GI earth plate 600mmx600mmx6mm thick including accessories and providing masonry pit enclosure with CI cover plate having locking arrangement with watering pipe of 2.7 metre long, funnel etc. With charcoal/coke and salt as required, complete all as specified and as directed.
Supplying and laying 6 SWG GI wire at 0.50 metre below ground level for conductor earth electrode, including connection/ termination with GI thimble etc. As required, complete all as specified and as directed.
Supplying and laying 6 SWG GI wire on surface or in recess for loop earthing as required, complete all as specified and as directed.
Supply ,Installation,Testing and commissioning of 8 way Flame proof DB with one number 63A, 4pole MCB as incomer and 24Nos of 10A & 16A SPMCB as outgoing with fixing supports.
Supply, testing and commissioning of 1.1 KV grade PVC insulated armoured Copper Conductor cable as per specification.
3 Core X 4 Sqmm Cu
3 Core X 2.5 Sqmm Cu
Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of of size upto 35 sqmm on cable tray as required.
CABLE END TERMINATIONS :
Supplying and providing flameproof end terminations for the following 1.1 kv grade armoured copper conductor cables with Copper lugs, double compressed brass cable glands, taping, crimping, glanding and armour earthing, etc.complete as required.
i) 3C X 4 Sq.mm
ii) 3C X 2.5 Sq.mm
Supplying and providing flameproof end terminations of size 16sqmm 4core 1.1 KV grade XLPE insulated armoured alluminium conductor cables with alluminium lugs, double compressed brass cable glands, taping, crimping, glanding and armour earthing, etc.complete as required.
Supply and fixing of factory made flame proof 16A, 1Ph , 3 Pin Plug and socket including fixing accessories.
Wiring for circuit/submain earth wire along with earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/recesses steel conduit as required.
(a) 2 X 6 sqm + 1 x 6 sqmm
Supplying and installing of size 300 mm wide (for cable of lighting fixtures) of perforated Hot Dipped Galvanised Iron cable tray (Galvanisation thickness not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc. as required.
SUB HEAD - XI TELEPHONE AND LAN CONDUIT
Supplying and fixing of following sizes of steel conduit along with accessories in surface/recess including painting in case of surface conduit, or cutting the wall and making good the same in case of recessed conduit as required for Telephone and LAN conduit.
SUB HEAD - XII FIRE ALARM SYSTEM
Supplying, installation, testing & commissioning of heat detector operating at 54ºC/57ºC with rate of rise cum fixed temperature (dual thermistor) type with mounting base complete with all connection etc. as required.
Supplying, installation, testing & commissioning of smoke detector with builtin LED and mounting base complete with all connections etc. as required.
Providing and fixing GI pipes Heavy duty complete with GI fittings including trenching and refilling etc.
(a) 25mm dia bore
Supplying and fixing of following sizes of steel conduit along with accessories in surface/recess including painting in case of surface conduit, or cutting the wall and making good the same in case of recessed conduit as required.
(a) 20 mm dia
Supply,laying,testing of twisted pair 1.5sq mm shielded FR insulated copper conductor flexible cable drawn in existing PVC/steel conduit, complete all as specified and as directed by Engineer-in-Charge.
Supply, fixing and installation of fire exit signage's self illuminating light fixtures displaying exit with an arrow towards the exit door.
Supply & Installation of Carbon-di- oxide type fire extinguisher of 4.5 kgs. Capacity, CO2 gas filled in brand new seamless cylinder with powder coated finish, made out of Manganese steel, with wheel type valve, discharge nozzle, bend & horn, wal mounting bracket etc. complete, confirming to IS: 2878.
Supply & Installation of Water CO2 Type fire extinguisher of 9 Ltrs. Capacity, filled in brand new seamless cylinder with powder coated finish, made out of Manganese steel, with wheel type valve, discharge nozzle, bend & horn, wal mounting bracket etc. complete confirming to IS: 940.
SUB HEAD - XIII SPECIAL EARTHING
10. Supply, installation and testing of maintenance free chemical Earthing using copper bonded steel rod 17.2mm dia, 2.4 metres long and using groung enhancing artificial soil treatment chemical compound, TFRFC & Earthcon, having essential chemical ingradients, such as ionic cxhemicals, disperson chemicals, expansion chemicals, diffusion chemicals and hygroscopic chemicals, to provide stable low resistance in the earth terminal to make it maintenance free, (the Earth terminal ahall consist of 3 Nos separate earth pits for each down conductor) as per IEEE 80-2000 14.5D clause, complete all as specified and as directed by Engineer-in-Charge.
Supplying and laying 25 mm X 5 mm copper strip at 0.50 metre below ground as strip earth electrode, including connection/ terminating with nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of brass nut bolt & spring washer spaced at 50mm)
Providing and fixing 25 mm X 5 mm copper strip on surface or in recess for connections etc. as required.
SUB HEAD - XIV EXTERNAL WATER SUPPLY
Making connection of GI distribution branch with main of following sizes by provoding and fixing tee, including cutting and threading the pipe etc, complete all as specified and as directed by Engineer-in-Charge.
50 to 80 mm nominal bore
Providing and fixing GI pipes complete with GI fittings including trenching and refilling etc.
(a) 32mm dia bore
(b) 50mm dia bore
Providing and fixing gun metal gate valve with C.I. wheel of approved quality (screwed end),complete all as specified and as directed.
32 mm dia
50 mm dia
Provision and placing on terrace (at floor level) of Polythyline Water Storage Tank IS-12701 Marked, with cover and suitable lockingh arrange and making nessary holes for inlet, outlet and overflow pipe. But without fittings and base support for tank, complrte all as spesified and as dorected by Engineer-in-Charge.
SUB HEAD - XV EXTERNAL ELECTRIFICATION (External Lighting)
Providing and fixing following rating and breaking capacity and pole MCCB with thermomagnetic release and terminal spreaders in existing cubicle panel board including drilling holes in cubicle panel, making connections, Ics=100% Icu and Operational Voltage 690V etc. as required. (Existing FPB tapping poing).
(a) 125 A,30KA,FP MCCB
Supply, installation, Testing and Commissioning of LT Feeder Pillar Box (FPB) out door type, Double Door, weather proof, 3 phase and Neutral 415V 4 wire Free Standing Floor mounted MV panel made out of 2mm thick CRCA/Galvanised steel enclosure for main frame and 1.6mm thick partitions and shall have IK Certification as per IEC 62262 for mechanical strength/ruggedness, after seven tank process and painting with Epoxy powder coating. The panel shall consist of 400 Ampse rated TPN Aluminium busbar (R,Y,B,N) (at the rating of 0.8A/Sq.mm) supported with DMC/ SMC barriers and color coded with Heat shrinkable sleeves. Contd ...
Contd … The Metering shall be provided as specified. The panel shall have Short circuit withstanding capacity of minimum 50KA and consist of the switchgear as mentioned below.The panel shall be got fabricated from manufacturers as per IEC 61439(Part-1&2). out door FPB shall have IP-65 protection and Enclosure shall be powder coated with RAL-7035 coat with matt finish. Design ambient temperature shall be 50 degree centrigrade. No use of hygroscopic material like FRP/Hylam/Bakellite sheet inside the panel for partitions or any other purpose. Contd ...
Contd... The PCC shall have at least two spare cubicles. The size of all Panel Mounting Meters shall be 96X96mm. The Panels shall be mounted on 75MM U channels including supply and fixing of the same. Every MCCB shall be provided with ON/OFF /Trip Indication lamps of LED type. MCCBs shall be provided with Digital type Ammeter of suitable range along with CTs. All MCCBs shall be provided with ON/OFF/TRIP indication lamps and shunt trip coils. All MCCB of rating 125A and above shall be with Micro processor releases and MCCBs below 125A shall be with adjustable thermal magnetic based releases. All MCCBs shall be over load & short circuit releases with Icu=100% Ics. All CTs/CBCT Contd ...
Contd ... shall be resin cast type. All Controlling wiring shall be FRLS cables, all the bus bar sleeves shall be Heat shrinkable kits. Panels shall have form 4b/form 3b construction as per the requirement. MCCBs shall conform to IEC 60947 (part 1&2), shall be suitable for rated system voltage 690V, Insulation voltage 1000V and Impulse withstand of 12KV. In case of 4 pole MCCB, neutral rating shall be 100% of phase. MCCBs shall have same height & depth for entire range irrespective of frame size. MCCBs shall have Icu=Ics=Icw (Icw rating shall be for 1 sec). MCCB release shall be provided with built-in LCD display for following: Current measurement and display with bar graph, date & time stamping for events, last trip data & last 20 trip data. Release shall have over temp. protection. Panel Front side Glass to be provided for clear visibility for each section.
Contd … • MCCB shall be provided with double insulation (insulation between front cover and internal power circuits to avoid any accidental contact with live current carrying path with the front cover open) • The tripping devices shall be ambient temperature compensated type. The insulating case shall be made of high strength heat resistant and flame retardant thermosetting insulating material. (FOR MAIN PANEL TO FPB) Near tapping point. Contd...
INCOMING :-
(a) MCCB, with Microprocesssor release with 100Amps, 35KA, Four Pole - 01 No
(b) Incomer shall have one set of the following items:
(c) 0 - 500V Digital Volt meter - 1No.
(d) 0 - 400A Digital Ammeter- 1 No.
(e) Multi function digital meter of suitable range to read Volt,Amp, KVA, KVAH, KWAH, KW, KVAR, PF, Hz etc and LED display with required Nos CTs, 15 VA, class 1 class and control circuit wiring with MCBs - 1 No.
(f) One Set of Indication Lamps, LED type, R,Y,B and breaker 'ON' , 'OFF', 'TRIP' & spring charged lamps.
BUS BAR
FP Alluminium busbar of 400A with 50 KA fault level capacity, mounted on non-hygroscopic, glass fibre reinforced insulators-1Set
OUTGOINGS :-
(a) MCCB 40A, 25KA 4 Pole (Thermal Magnetic Release) - 4 No
(b) MCB 32A, 10KA , SPN - 02 Nos
(c)1 Lot of control wiring & outgoing feeder indication lamps 01 Set of designation plates.
(d)Two numbers 50mm X 6mm GI earthing terminals - one on each side of the panel with earth strip run inside the panel.
Supply, connection, Testing and commissioning XLPE screened PVC insulated steel strip armoured under ground aluminium stranded cable 1100 Volts grade, confirming to IS:7098(Part-I) and including making and copper lugs as required for the following size of cross sectional area :-
(a) 95 Sqmm 3.5 Core.
(b) 16 Sqmm 4 Core.
(c) 6 Sqmm 4 Core.
Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground including excavation, sand cushouoning, protectivebcovering and refilling the trench etc. as required.
(a) upto 35 Sq.mm
(b) Above 35 sq. mm and upto 95 sq. mm
Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1100 volts grade of following size direct in existing masonry duct as required.
(a) upto 35 Sq.mm
(b) Above 35 sq. mm and upto 95 sq. mm
Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.
(a) 6 Sqmm 4 core (25 mm)
(b) 16 Sqmm 4 core (28 mm)
(c) 95 Sqmm 3.5 core (45 mm)
Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 Meter long etc. with charcoal/ coke and salt as required.
Providing and fixing 25 mm X 5 mm G.I. strip in 40 mm dia G.I. pipe from earth electrode including connection with G.I. nut, bolt, spring, washer excavation and re-filling etc. as required.
Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for connections etc. as required.
Providing and laying earth connection from earth electrode with 6 SWG dia G.I. Wire in 15 mm dia G.I. pipe from earth electrode including connection with G.I. thimble excavation and re-filling as required.
Supply anfd fix 3 metre round lightingPole of size (Bottom 114x1000x3mm, Top 89x2000x3mm and Bottom plate 200x200x10mm) and including one coat of zink red oxide primer with two coats of silver aluminium paint, 01 metre of designed single arm bracket, M16x500 mm foundation bolts with nuts and washer set, In built electrical box with MCB SP 6Amps,4Pole connector,3core x 1.5 Sqmm copper cable required length, complete all as manufacturer specification. (Note - street light cable shall be connected with existing feeder).
Supply and fix for Street Light LED fitting 45 Watt light (IP65) complete all as specified or as directed complete all as specified and as directed.
SUB HEAD - XVI LIGHTNING PROTECTION SYSTEM
Earthing with GI earth plate 600 mm X 600 mm X 3 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required.
Providing and laying G.I. tape 32mm X 6mm from the earth electrode directly in ground as required.
Providing and fixing G.I tape 20mm X 3mm thick on parapet or surface of wall for lightning conductor complete as required.(For horizontal run). NOTE- all GI tape shall be fixing with DMC Insulated Supports.
Providing and fixing G.I tape 20mm X 3mm thick on parapet or surface of wall for lightning conductor complete as required.(For vertical run). NOTE - all GI tape shall be fixing with DMC Insulated Supports.
Providing and fixing testing , joint, made of 20mm X 3mm thick GI strip, 125mm long, with 4 nos. Of GI bolts, nuts, check nuts,and spring washers etc. Complete as required.
Providing and fixing of lightning conductor finial, made of 25mm dia 300mm long, GI tube having single prong at top, 85mm dia 6mm thick GI base plate including holes etc. Complete as required.
Providing and fixing testing jointing, made of 20mm x 3mm thick GI tape on parapet or surface of wall for lightning conductor complete as required for vertical run, complete all as specified and as directed.
Supply and fix single pointed air termination aluminium rod 12mm dia, 300mm long .
SUB HEAD - XVII FIRE FIGHTING SYSTEM & SPRINKLER SYSTEM
Cutting existing 150 mm dia heavy duty fire fighting MS pipe line and necessary connection with connecting material including necessary excavation, returning filling etc, complete all as specified and as directed by Engineer-in-Charge.
Providing laying, testing & commissioning of 'C' class heavy duty MS Pipe conforming to IS 1239/Class -II of IS: 3589 i/c fittings like elbows, tees, flanges, tapers, nuts bolts, gaskets etc. in ground including welding, excavation & providing cement concrete blocks as supports, anticorrosive treatment with coaltar/asphalt tape as per IS 10221, refilling the trench etc. of following sizes com
(a) 80 mm dia
(b) 65 mm dia
(c) 32 mm dia
Supplying, fixing, testing & commissioning of double flanged sluice valve of rating PN 1.6 with non rising spindle, bronze/gun metal seat, ISI marked complete with nuts, bolts, washers, gaskets and conforming to IS 780 of following sizes as required , complete all as specified and as directed by Engineer-in-Charge.
(a) 65 mm dia
(b) 80 mm dia
Supplying and fixing Single headed external yard hydrant valve with 1 No. 63 mm dia instantaneous FM Gunmetal/Stainless Steel coupling and cast iron wheel, ISI marked, conforming to IS 5290 (type A) with blank Gunmetal/Stainless Steel cap and chain as required :
(a) Single headed Gunmetal
Supplying, fixing, testing and commissioning of butterfly valve of PN 1.6 rating with bronze/gunmetal seat duly ISI marked complete with nuts, bolts, washers, gaskets conforming to IS 13095 of following sizes as required :
(a) 65 mm dia
(b) 80 mm dia
Supplying and fixing first-aid Hose Reel with MS construction spray painted in post office red, conforming to IS 884 complete with the following as required. (a) 20 mm nominal internal dia water hose thermoplastic (Textile reinforced) type -2 as per IS:12585 (b) 20 mm nominal internal dia gun metal globe valve & nozzle. (c) Drum and brackets for fixing the equipmets on wall. (d) Connections from riser with 25 mm dia stop gunmetal valve & M.S. Pipe and socket.
(a) 30 m Hose reel.
Providing, fixing, testing and commisioning of 15 mm dia quartzoid bulb type sprinklers of rating 68 degree centrigrade with required accessories.
(a) Horizontal side wall sprinkler
Providing and fixing GI Gun metak Gate valve with CI wheel of approved quality (Screwed head) of 25 mm dia nominal bore, complete all as specified and as directed.
Please Enable Macros to View BoQ information
stage.html
html • 0.03 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.05 MB
Tendernotice_1.pdf
PDF • 0.98 MB
Annexure_II.pdf
Tender Documents • 0.30 MB
GCC.pdf
Tender Documents • 0.19 MB
Annexure_I_NIT.pdf
Tender Documents • 0.43 MB
Approved_Makes_EnM.pdf
Tender Documents • 0.55 MB
Annexure_III_A.pdf
Tender Documents • 0.60 MB
Annexure_IV.pdf
Tender Documents • 0.19 MB
BGB_Proforma.pdf
Tender Documents • 0.24 MB
Annexure_V.pdf
Tender Documents • 0.24 MB
Floor_Plan_Utility_Room_1.pdf
Tender Documents • 0.21 MB
Floor_Plan_Utility_Room_2.pdf
Tender Documents • 0.21 MB
Annexure_V_VI.pdf
Tender Documents • 0.44 MB
Tender_Enquiry.pdf
Tender Documents • 0.33 MB
Annexure_VI.pdf
Tender Documents • 0.39 MB
BOQ_940367.xls
BOQ • 2.02 MB
GCC_2023_F.pdf
Tender Documents • 23.68 MB
Special_Conditions.pdf
Tender Documents • 0.47 MB
Annexure_VII.pdf
Tender Documents • 0.29 MB
Approved_Makes.pdf
Tender Documents • 0.69 MB
Annexure_III.pdf
Tender Documents • 0.42 MB
Download all tender documents and submit your bid