Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹17.1 LAccepted-Finance | ₹17.1 L | L1 | Accepted-Finance LOWEST |
| 2 | L2₹19.1 L+₹2.0 L (11.7%)Accepted-Finance 37 1634 IMPERIAL HOUSE KALOOR KATHRIKADAVU KATHRIKADAVU ERNAKULAM KERALA 682017 | ERNAKULAM | KERALA | 682017 | ₹19.1 L+₹2.0 L (11.7%) | L2 | Accepted-Finance SECOND LOWEST |
| 3 | L3₹20.1 L+₹2.9 L (17.2%)Accepted-Finance | ₹20.1 L+₹2.9 L (17.2%) | L3 | Accepted-Finance THIRD LOWEST |
Tender Value
₹17.8 L
EMD Value
₹26,700
Closing Date
24 May 2023, 5:00 pmClosed
Executive Engineer
Transmission Division Ernakulam, Old Jankar Jetty Road, Near High Court Jn., Kochi- 31.
Renovation of 110kV Switchyard,Kaloor-Midterm flood mitigation works,procurement of RMU at 220kV GIS Substation,Kaloor
2023_KSEB_572421_1
E-tender-01/2023-24/EE/TD/EKM dated. 24.04.2023
Open Tender
Equipments
Percentage
90 days
220kV GIS Substation, Kaloor
Please refer Tender documents.
4 documents required · 4 mandatory
₹5,900
₹26,700
Yes
8 Jun 2023
24 Apr 2023
30 May 2023
29 Apr 2023
24 May 2023
2 May 2023
29 Apr 2023 - 23 May 2023
Supply of Floor mounted 11kV-630A, Metal enclosed SF6 insulated, Non extensible, Manual operated, Outdoor Ring Main Unit. The RMU should be two module configuration with 2 nos LBS ( three position snap action disconnector switch including integral earthing switch) and should have Capacitive voltage detectors, “Ready to service” gas pressure indicator and Mechanical position indicators integrated in the mimic diagram on front cover. The RMU should also have Manual spring charging mechanism, Logical mechanical interlocks on all operating shafts to prevent mal-operation, Suitable size HV cable termination bushing and cable compartment with arc proof inter lockable cable cover including Push on type cable terminal cover boots with cap and along with common items & accessories..
Supply of Floor mounted 11kV-630A, Metal enclosed SF6 insulated, Non extensible, Manual operated,Outdoor Ring Main Unit. The RMU should be Four module configuration; 2nos VCB with disconnector switch and 2nos LBS ( three position snap action disconnector switch including integral earthing switch) and should have Capacitive voltage detectors, “Ready to service” gas pressure indicator and Mechanical position indicators integrated in the mimic diagram on front cover. The RMU should also have Manual spring charging mechanism, Logical mechanical interlocks on all operating shafts to prevent maloperation, Suitable size HV cable termination bushing and cable compartment with arc proof inter lockable cable cover including Push on type cable terminal cover boots with cap and along with common items & accessories.
Imperial Engineering Company
PEACOCK RESOURCES LLP
stage.html
html • 0.03 MB
tech_eval.pdf
PDF • 0.09 MB
fin_eval.pdf
PDF • 0.10 MB
boq_comp_chart.xlsx
xlsx • 0.01 MB
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .