| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹38.5 LAccepted-AOC | L1 | Accepted-AOC First Lowest | |
| 2 | L2₹39.3 L+₹80,237.92 (2.09%)Rejected-AOC REX BUILDING II FLOOR R S ROAD ALUVA 683 101 | ALUVA | ERNAKULAM | KERALA | 683101 | L2 | Rejected-AOC Second Lowest |
Tender Value
₹41.7 L
EMD Value
₹50,000
Closing Date
23 Jan 2021, 4:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
Regional Engineer
REGIONAL ENGINEER KERALA STATE NIRMITHI KENDRA COCHIN DEVASWOM BOARD BUILDING ROUND NORTH THRISSUR 1 PH NO 04872322654
Electrification and lighting work
2021_KSNK_404641_1
KSNK/TECH/ THRS/VNEL-73/2021
Open Tender
Electrical Works
Item Rate
30 days
Poothole
Refer NIT
6 documents required · 6 mandatory
₹2,500
₹50,000
26 Feb 2021
7 Jan 2021
25 Jan 2021
7 Jan 2021
23 Jan 2021
7 Jan 2021
7 Jan 2021 - 23 Jan 2021
90 days
Amount
8. Electrification and Lighting: - 90.2.1.1 : Supply and wiring points according to IS 732-1989 using rigid PVC conduit of minimum size 20 mm with specials conforming to IS 9537 part III 1983 and with suitable size specials conforming to IS 3419-1988, fixing the conduit using metal saddles spacing not exceeding 50 cm or concealed suitably and with 1.00 sq mm FRLS PVC insulated stranded single core copper conductor cable 650V grade, including providing switch board main and continuous earthing with No.14 SWG bare copper,required quantity of copper earth socket, brass bolt and nut crimping/ soldering etc complete with suitable size modular type metal switch boxes, modular type front plates (white) etc. up to and including 6A modular type SP switches and making good the surface of wall, colour washing etc. complete. All the terminations in the switch boards and DB's shall be tinned and the wires shall be drawn and fixed along the periphery of the box using suitable ties, tie mounts etc as required. (RoHS compliant modular accessories).
90.2.1.3 : Supply and wiring points according to IS 732-1989 using rigid PVC conduit of minimum size 20 mm with specials conforming to IS 9537 part III 1983 and with suitable size specials conforming to IS 3419-1988, fixing the conduit using metal saddles spacing not exceeding 50 cm or concealed suitably and with 1.00 sq mm FRLS PVC insulated stranded single core copper conductor cable 650V grade, including providing switch board main and continuous earthing with No.14 SWG bare copper,required quantity of copper earth socket, brass bolt and nut crimping/ soldering etc complete with suitable size modular type metal switch boxes, modular type front plates (white) etc. up to and including 6A modular type SP switches and making good the surface of wall, colour washing etc. complete. All the terminations in the switch boards and DB's shall be tinned and the wires shall be drawn and fixed along the periphery of the box using suitable ties, tie mounts etc as required. (RoHS compliant modular accessories).
90.2.1.4 : Supply and wiring points according to IS 732-1989 using rigid PVC conduit of minimum size 20 mm with specials conforming to IS 9537 part III 1983 and with suitable size specials conforming to IS 3419-1988, fixing the conduit using metal saddles spacing not exceeding 50 cm or concealed suitably and with 1.00 sq mm FRLS PVC insulated stranded single core copper conductor cable 650V grade, including providing switch board main and continuous earthing with No.14 SWG bare copper,required quantity of copper earth socket, brass bolt and nut crimping/ soldering etc complete with suitable size modular type metal switch boxes, modular type front plates (white) etc. up to and including 6A modular type SP switches and making good the surface of wall, colour washing etc. complete. All the terminations in the switch boards and DB's shall be tinned and the wires shall be drawn and fixed along the periphery of the box using suitable ties, tie mounts etc as required. (RoHS compliant modular accessories).
90.2.1.6 : Supply and wiring points according to IS 732-1989 using rigid PVC conduit of minimum size 20 mm with specials conforming to IS 9537 part III 1983 and with suitable size specials conforming to IS 3419-1988, fixing the conduit using metal saddles spacing not exceeding 50 cm or concealed suitably and with 1.00 sq mm FRLS PVC insulated stranded single core copper conductor cable 650V grade, including providing switch board main and continuous earthing with No.14 SWG bare copper,required quantity of copper earth socket, brass bolt and nut crimping/ soldering etc complete with suitable size modular type metal switch boxes, modular type front plates (white) etc. up to and including 6A modular type SP switches and making good the surface of wall, colour washing etc. complete. All the terminations in the switch boards and DB's shall be tinned and the wires shall be drawn and fixed along the periphery of the box using suitable ties, tie mounts etc as required. (RoHS compliant modular accessories).Combined plug point with 6 A, 5 pin plug socket controlled by 6 A, switch in the same switch board as that of light points
90.2.1.8 : Supply and wiring points according to IS 732-1989 using rigid PVC conduit of minimum size 20 mm with specials conforming to IS 9537 part III 1983 and with suitable size specials conforming to IS 3419-1988, fixing the conduit using metal saddles spacing not exceeding 50 cm or concealed suitably and with 1.00 sq mm FRLS PVC insulated stranded single core copper conductor cable 650V grade, including providing switch board main and continuous earthing with No.14 SWG bare copper,required quantity of copper earth socket, brass bolt and nut crimping/ soldering etc complete with suitable size modular type metal switch boxes, modular type front plates (white) etc. up to and including 6A modular type SP switches and making good the surface of wall, colour washing etc. complete. All the terminations in the switch boards and DB's shall be tinned and the wires shall be drawn and fixed along the periphery of the box using suitable ties, tie mounts etc as required. (RoHS compliant modular accessories).
90.2.1.10 : Supply and wiring points according to IS 732-1989 using rigid PVC conduit of minimum size 20 mm with specials conforming to IS 9537 part III 1983 and with suitable size specials conforming to IS 3419-1988, fixing the conduit using metal saddles spacing not exceeding 50 cm or concealed suitably and with 1.00 sq mm FRLS PVC insulated stranded single core copper conductor cable 650V grade, including providing switch board main and continuous earthing with No.14 SWG bare copper,required quantity of copper earth socket, brass bolt and nut crimping/ soldering etc complete with suitable size modular type metal switch boxes, modular type front plates (white) etc. up to and including 6A modular type SP switches and making good the surface of wall, colour washing etc. complete. All the terminations in the switch boards and DB's shall be tinned and the wires shall be drawn and fixed along the periphery of the box using suitable ties, tie mounts etc as required. (RoHS compliant modular accessories).
90.2.1.11 : Supply and wiring points according to IS 732-1989 using rigid PVC conduit of minimum size 20 mm with specials conforming to IS 9537 part III 1983 and with suitable size specials conforming to IS 3419-1988, fixing the conduit using metal saddles spacing not exceeding 50 cm or concealed suitably and with 1.00 sq mm FRLS PVC insulated stranded single core copper conductor cable 650V grade, including providing switch board main and continuous earthing with No.14 SWG bare copper,required quantity of copper earth socket, brass bolt and nut crimping/ soldering etc complete with suitable size modular type metal switch boxes, modular type front plates (white) etc. up to and including 6A modular type SP switches and making good the surface of wall, colour washing etc. complete. All the terminations in the switch boards and DB's shall be tinned and the wires shall be drawn and fixed along the periphery of the box using suitable ties, tie mounts etc as required. (RoHS compliant modular accessories).
90.2.1.12 : Supply and wiring points according to IS 732-1989 using rigid PVC conduit of minimum size 20 mm with specials conforming to IS 9537 part III 1983 and with suitable size specials conforming to IS 3419-1988, fixing the conduit using metal saddles spacing not exceeding 50 cm or concealed suitably and with 1.00 sq mm FRLS PVC insulated stranded single core copper conductor cable 650V grade, including providing switch board main and continuous earthing with No.14 SWG bare copper,required quantity of copper earth socket, brass bolt and nut crimping/ soldering etc complete with suitable size modular type metal switch boxes, modular type front plates (white) etc. up to and including 6A modular type SP switches and making good the surface of wall, colour washing etc. complete. All the terminations in the switch boards and DB's shall be tinned and the wires shall be drawn and fixed along the periphery of the box using suitable ties, tie mounts etc as required. (RoHS compliant modular accessories).
90.2.1.13 : Supply and wiring points according to IS 732-1989 using rigid PVC conduit of minimum size 20 mm with specials conforming to IS 9537 part III 1983 and with suitable size specials conforming to IS 3419-1988, fixing the conduit using metal saddles spacing not exceeding 50 cm or concealed suitably and with 1.00 sq mm FRLS PVC insulated stranded single core copper conductor cable 650V grade, including providing switch board main and continuous earthing with No.14 SWG bare copper,required quantity of copper earth socket, brass bolt and nut crimping/ soldering etc complete with suitable size modular type metal switch boxes, modular type front plates (white) etc. up to and including 6A modular type SP switches and making good the surface of wall, colour washing etc. complete. All the terminations in the switch boards and DB's shall be tinned and the wires shall be drawn and fixed along the periphery of the box using suitable ties, tie mounts etc as required. (RoHS compliant modular accessories).Combined plug point with 6 A, 5 pin plug socket controlled by 6 A switch in the same switch board as that of light points.
90.3.20.3 : Supply & installation of light fittings on TW round block <br> Supply, conveyance installation testing and commissioning the light fittings of following types made of CRCA with 0.5mm thickness complete with all accessories and lamps etc. directly on wall or ceiling with PVC round block neatly painted to suit the fitting and giving connection with required length of 16/0.20mm 3 core copper conductor flex wire conforming to relevant ISS and giving connections as required.
90.3.21.3 : Supply & installation of light fittings on 'C/U' shaped flat iron bracket <br> Supply, conveyance, installation, testing and commissioning the light fittings of following types made from 0.5mm CRCA sheet complete with all accessories and lamps etc. directly on wall using 2 nos. 'C/U' brackets made from 20 x 3 mm MS flat, painting the flat iron bracket and giving connections with required length of 16/0.20mm 3 core copper conductor flex wire conforming to relevant ISS or extending the original wiring and giving connection etc. as required.
90.4.1 : Supply and installation of suitable size MS rod type fan clamp in the RCC slab as per IS 732 as required.
90.4.5.2 : Supply, conveyance, installation, testing and commissioning of ceiling fans of the following sizes using standard accessories excluding resistance type regulator, wiring the down rod with 16/0.20mm PVC insulated and PVC sheathed 650/1100V grade 3 core round copper conductor flex wire or with extended original wiring etc. as required.
1.48 : Supplying and fixing extra conduit down rod of 20 cm length G.I. pipe 15 mm dia, heavy gauge including painting etc. as required. (Note : More than 5 cm length shall be rounded to the nearest 10 cm and 5 cm or less shall be ignored)
90.5.1.3 : Supply and fixing the following types of superior quality 250V A.C call bell on existing M.S. box and giving connections with required length of 3 core, 16 / 0.20mm 650/1100V grade PVC insulated and PVC sheathed round copper conductor flex wire conforming to relevant ISS or with the extended original wiring, earthing the MS box and making good the surface as required.
90.5.1.9 : Supply and fixing the following types of superior quality 250V A.C call bell on existing M.S. box and giving connections with required length of 3 core, 16 / 0.20mm 650/1100V grade PVC insulated and PVC sheathed round copper conductor flex wire conforming to relevant ISS or with the extended original wiring, earthing the MS box and making good the surface as required.
90.4.6 : Conveyance, installation, testing and commissioning of wall mounting fans of all types using mounting brackets supplied along with the fan.
od224319/2020_2021 : Supplying and fixing 400 mm metal wall Fans (almonard/ equivalent make
1.22.3 : Supplying and fixing metal box of following sizes (nominal size) on surface or in recess with suitable size of phenolic laminated sheet cover in front including painting etc as required.150 mm X 75 mm X 60 mm deep
1.27.2 : Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required.3 Module (100mmX75mm)
1.27.5 : Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required.8 Module (125mmX125mm)
1.24.1 : Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.5/6 amps switch
1.24.3 : Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.15/16 amp switch
1.24.4 : Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.3 pin 5/6 amp socket outlet
1.24.5 : Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.6 pin 15/16 amp socket outlet
90.6.10.1 : Supply and fixing of following sizes of light gauge PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required
90.6.10.2 : Supply and fixing of following sizes of light gauge PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required
90.6.10.3 : Supply and fixing of following sizes of light gauge PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required
90.9.1.1 : Supply and fixing 50 x 50 mm PVC Cable Management System with base and lid along with the following accessories conforming to IEC 61084/ BS 476 & 4678 on surface / recess including cutting the wall and making good the damages in case of recessed installation as required.
90.9.1.7 : Supply and fixing 50 x 50 mm PVC Cable Management System with base and lid along with the following accessories conforming to IEC 61084/ BS 476 & 4678 on surface / recess including cutting the wall and making good the damages in case of recessed installation as required.
90.9.2.1 : Supply and fixing 100 x 50 mm PVC Cable Management System with base and lid along with the following accessories conforming to IEC 61084/ BS 476 & 4678 on surface / recess including cutting the wall and making good the damages in case of recessed installation as required.
90.9.2.8 : Supply and fixing 100 x 50 mm PVC Cable Management System with base and lid along with the following accessories conforming to IEC 61084/ BS 476 & 4678 on surface / recess including cutting the wall and making good the damages in case of recessed installation as required.
4.1.2 : Supplying and installing following size of perforated pre-painted M.S. cable trays with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc as required.150 mm width X 50 mm depth X 1.6 mm thickness
4.2.2 : Supplying and installing following size of perforated pre-painted M.S. cable trays bends with perforation not more than 17.5%,, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc as required.150 mm width X 50 mm depth X 1.6 mm thickness
4.4.2 : Supplying and installing following size of perforated pre-painted M.S. cable trays Tee's with perforation not more than 17.5%, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc as required.150 mm width X 50 mm depth X 1.6 mm thickness
1.17.2 : Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.2 x 1.5 sq. mm
1.17.4 : Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.4 x 1.5 sq. mm
1.17.11 : Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.2 x 2.5 sq. mm
1.17.13 : Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.4 x 2.5 sq. mm
1.17.20 : Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.2 x 4 sq. mm
90.6.4.63 : Supply and drawing 650/1100 V grade FRLS PVC insulated stranded single core copper conductor cables conforming to IS 694 part I 1990 in the existing surface / recess conduit as required including giving necessary connections of the following sizes.
90.6.5.9 : Supply and drawing the following sizes of multi-core PVC insulated & FRLS PVC sheathed 650/1100 V grade copper conductor round flexible cables conforming to IS 694 part I 1960 in the existing surface / recess conduit as required including giving necessary connections of the following sizes.
2.3.2 : Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCBIRCCB/Isolator8 way, Double door
2.3.3 : Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCBIRCCB/Isolator12 way, Double door
90.11.1.15 : Supply and installation of sheet steel, phosphatised and painted, dust and vermin proof enclosure of MCB DB including copper /brass bus bar, neutral link, earth bus and DIN rail suitable for fixing MCB/ isolator etc. fixed on wall using suitable anchor bolts or fixed in recess including cutting hole on the wall , making good the damages, colour washing etc. as required
2.10.1 : Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.Single pole
2.10.4 : Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.Triple pole
2.11 : Supplying and fixing single pole blanking plate in the existing MCB DB complete etc. as required.
2.12.1 : Supplying and fixing following rating, double pole, 240 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.40 amps
2.13.2 : Supplying and fixing following rating, four pole, 415 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.63 amps
2.14.1 : Supplying and fixing following rating, double pole, (single phase and neutral), 240 volts, residual current circuit breaker (RCCB), having a sensitivity current upto 300 milliamperes in the existing MCB DB complete with connections, testing and commissioning etc. as required.25 amps
2.15.2 : Supplying and fixing following rating, four pole, (three phase and neutral), 415 volts, residual current circuit breaker (RCCB), having a sensitivity current upto 300 milliamperes in the existing MCB DB complete with connections, testing and commissioning etc. as required.40 amps
90.12.39.1 : Supply & laying of one number PVC insulated and PVC sheathed armoured copper power cable of 1.1KV grade of the following sizes in the existing RCC/ HUME / STONE WARE/ GI/ DWC pipe as required.
90.12.39.2 : Supply & laying of one number PVC insulated and PVC sheathed armoured copper power cable of 1.1KV grade of the following sizes in the existing RCC/ HUME / STONE WARE/ GI/ DWC pipe as required.
90.12.39.33 : Supply & laying of one number PVC insulated and PVC sheathed armoured copper power cable of 1.1KV grade of the following sizes in the existing RCC/ HUME / STONE WARE/ GI/ DWC pipe as required.
90.12.41.1 : Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured copper power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.
90.12.41.2 : Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured copper power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.
90.12.41.33 : Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured copper power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.
9.1.1 : Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.2 X 6 sq. mm (19mm)
9.1.32 : Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.4 X 10 sq. mm (25mm)
od236664/2020_2021 : Supplying and providing 4 sqmm to 16 sqmm. 60 mm long x 12 mm wide x 1 mm thick Copper earthing clips for single compression glands using brass bolt and nut etc as required.
90.12.9.2 : Supplying, laying and jointing of the following sizes of double wall corrugated (DWC) pipes made out of HDPE conforming to IS 14930 Part II for mechanical protection to underground power cables with all required accessories in ground in the existing trench
90.12.9.3 : Supplying, laying and jointing of the following sizes of double wall corrugated (DWC) pipes made out of HDPE conforming to IS 14930 Part II for mechanical protection to underground power cables with all required accessories in ground in the existing trench
7.10 : Supplying and fixing cable route marker with 10 cm X 10 cm X 5 mm thick G.I. plate withinscription there on, bolted /welded to 35 mm X 35 mm X 6 mm angle iron, 60 cm long and fixingthe same in ground as required.
90.16.2.3 : Supply and laying of the following sizes of B class GI pipe laid 0.6 m below ground level including excavating trench of suitable size and refilling etc, as required.32 mm dia G.I pipe ( medium class)
90.16.2.4 : Supply and laying of the following sizes of B class GI pipe laid 0.6 m below ground level including excavating trench of suitable size and refilling etc, as required.40 mm dia G.I. pipe ( medium class)
90.16.2.5 : Supply and laying of the following sizes of B class GI pipe laid 0.6 m below ground level including excavating trench of suitable size and refilling etc, as required.50 mm dia. G.I. pipe (medium class)
90.14.1.2 : Fabrication, supply, conveyance, installation testing and commissioning of floor or wall mounting, dust and vermin proof, cubicle type MV panel board comprising of the following components/ devices & complying to IS 8623.<br> Fabrication of fully partitioned, dust and vermin proof enclosure for panel assembly as per form 4 of IS 8623 (with latest amendments) using CRCA sheet as per approved design and requirement, with front and rear access facility, bus bar chambers, hinged doors for all switch gear compartments, earthing the doors using 4 sq mm braided copper conductor, providing necessary cut-outs for mounting meters, relays, indication lamps, bus bar interconnection etc, detachable covers for bus bar chamber and cable alley, powder coating the assembly after subjecting to 7 tank process etc as required. CRCA sheet alone be used for the fabrication. Angles/ flats/ slotted angles etc shall not be used for the fabrication of panel assembly. The measurments will be taken the area of the complete sheets used for panel board including partitions, folding, shrouding etc.
90.14.2.2 : Supply and providing 3mm SMC sheet as shrouding for bus interconnection / terminations etc. including required nut & bolt etc.
90.14.3.1 : Supply and providing heavy duty 'A' section neoprene gasket in the panel board
90.14.4 : Supply and fabrication conveyance and installation of base frame of panel board using 75 x 40 mm rolled steel channel (ISMC)
90.14.5 : Supply and fabrication conveyance and installation of angle iron frame work for wall mounting panel board
90.14.6 : Supply and providing copper bus bars including finger type SMC bus bar supports in the bus chamber, suitable size nut & bolt, providng heat shrink sleeves etc. as required.
90.14.7 : Supply and providing copper earth bus in the panel board
90.14.10.5 : Supply, conveyance and fixing the following types & current rated control gears & switchgears conforming to IS 13947 suitable for 440 V, 50 Hz, AC supply in the existing panel assembly as required.
90.14.11.1 : MCCB Accessories
90.14.11.13 : MCCB Accessories
od228954/2020_2021 : Supplying and fixing one set spreader/terminal adapter kit extended terminal for4poleMCCBof rating up to 100A
2.1.2 : Providing and fixing following capacity TP&N disconnector fuse switch unit inside the existing panel board with ISI marked HRC fuses including drilling holes in cubicle panel, making connections, etc. as required.63 Amp TP & N
od227502/2020_2021 : Providing and fixing following switch dis connector fuse switch unit inside the existing panel board with ISI marked HRC fuses including drilling holes in cubicle panel, making connections, etc. as required.<br>32 Amp SPN
od227499/2020_2021 : Supply and providing three phase multi function meter inside the existing panel including drilling holes in cubicle panel, making connections, etc. as required.<br>
od229175/2020_2021 : Supplying and fixing CT100/5 VA accuracy 1 Resin cast metering CT
od229176/2020_2021 : Supplying and fixing LED indicator green, yellow, orange ,white color
od229177/2020_2021 : Supplying and fixing LED indicator blue clour
od229183/2020_2021 : Supplying and fixing HRC fuse base with 2 A fuse
2.21 : Providing and fixing M.V. danger notice plate of 200 mm X 150 mm, made of mild steel, at least 2mm thick, and vitreous enameled white on both sides, and with inscription in single red colour on front side as required.
od236329/2020_2021 : Numbering/lettering in the main board / ceiling fan / exhaust fan/ fluorescent fittings/other light fittings etc as required.
od236335/2020_2021 : Supplying and providing 2 mm thick 3.3KV synthetic elastromeric fire retardant insulating sheet in front of the main board eta as required
od249981/2020_2021 : Supply and providing 2.5 KG ,fire extinguisher on wall providing suitable hook etc as required (CO2)
5.3 : Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, andproviding masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. (but without charcoal/ coke and salt ) as required.
od231821/2020_2021 : Supply and provding test joint for earthing system using 2 nos of the following strips including cutting and bending to shape ,drilling necessary holes and fixing to the watering pipe etc as required .<br>2x25x6mm GI strip
od231820/2020_2021 : Supply and providing earth lead from test joint to earth electrode using the following strips including cutting and bending to shape ,drilling necessary holes and fixing to the earth plate to test joint etc as required 25x6mm GI strip
5.9 : Supplying and laying 25 mm X 5 mm G.I strip at 0.50 metre below ground as strip earthelectrode, including connection/ terminating with G.I. nut, bolt, spring, washer etc. as required.(Jointing shall be done by overlapping and with 2 sets of G.I. nut bolt & spring washer spaced at 50mm)
5.14 : Providing and fixing 25 mm X 5 mm copper strip on surface or in recess for connections etc. as required.
90.16.1.1 : Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required
90.16.1.2 : Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required
90.16.1.3 : Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required
90.16.2.1 : Supply and laying of the following sizes of B class GI pipe laid 0.6 m below ground level including excavating trench of suitable size and refilling etc, as required.15.mm dia. G.I pipe ( medium class)
90.16.5.1 : Supply of superior quality copper earth socket for the following size of earth conductor including crimping etc. as required.
90.16.5.2 : Supply of superior quality copper earth socket for the following size of earth conductor including crimping etc. as required.
90.16.5.3 : Supply of superior quality copper earth socket for the following size of earth conductor including crimping etc. as required.
90.12.24.2 : Supply of superior quality copper tubular cable socket and making core termination of cables of the following sizes including crimping etc. as required.
90.12.24.5 : Supply of superior quality copper tubular cable socket and making core termination of cables of the following sizes including crimping etc. as required.
od233485/2020_2021 : Supplying and providing 12x3 mm brass bolt and nut with washer etc as required .
od233486/2020_2021 : Supplying and providing 25x6 mm brass bolt and nut with washer etc as required .
od236643/2020_2021 : Supplying and fixing 100 2 way N/Lin existing meter board and giving connection etc as required
od236644/2020_2021 : Supplying and fixing 100 HRC fuse base with HRC fuse in the existing meter board and giving connectin etc as required
od236645/2020_2021 : Supplying, installing, testing and commissioning of Hensel/equivlent make thermoplastic polycarbonate Energy meter enclosures with hinged lid - environment friendly, recyclable, UV resistant, halogen & silicon free, anti acid & anti corrosive, degree of Ingress Protection IP 65 in accordance with IEC 60529, gasket material of enclosure is Polyurethane; while the gasket is internally embedded.<br>600x300x170mm<br>
od236659/2020_2021 : Supplying, installing, testing and commissioning of Hensel/equivlent make thermoplastic polycarbonate enclosures with hinged lid - environment friendly, recyclable, UV resistant, halogen & silicon free, anti acid & anti corrosive, degree of Ingress Protection IP 65 in accordance with IEC 60529, gasket material of enclosure is Polyurethane; while the gasket is internally embedded.<br>300x300x170mm<br>
od236656/2020_2021 : Supply and providing Hensel/equivlent make thermoplastic polycarbonate cable junction box with integral membrence/metric knock outs for cable entry etc (4-6 sq mm UG cable ) - environment friendly, recyclable, UV resistant, halogen & silicon free, anti acid & anti corrosive, degree of Ingress Protection IP 66 in accordance with IEC 60529, gasket material of enclosure is Polyurethane; while the gasket is internally embedded.<br>130x130x77mm(DK0606 of hensil/equivlent )<br>
od236657/2020_2021 : Supply and providing Hensel/equivlent make thermoplastic polycarbonate enclosures with lid - environment friendly, recyclable, UV resistant, halogen & silicon free, anti acid & anti corrosive, degree of Ingress Protection IP 66 in accordance with IEC 60529, gasket material of enclosure is Polyurethane; while the gasket is internally embedded.<br>300x300x70mm(K0200 of hensil/equivlent )<br>
od236658/2020_2021 : Supply and providing Hensel/equivlent make thermoplastic polycarbonate enclosures with lid - environment friendly, recyclable, UV resistant, halogen & silicon free, anti acid & anti corrosive, degree of Ingress Protection IP 66 in accordance with IEC 60529, gasket material of enclosure is Polyurethane; while the gasket is internally embedded.<br>300x150x70mm(K0100 of hensil/equivlent )<br>
od236646/2020_2021 : Supplying, installing, testing and commissioning of following capacity 4 pole on load change over switch in sheet steel enclosure duly painted with powder coating on existing wall /frame work .<br>100 A 4 pole COS.
od236647/2020_2021 : Supplying, installing, testing and commissioning of following capacity TPN with enclosure box made of 1.6mm thick sheet steel enclosure duly painted with powder coating on existing wall /frame work .<br>100 A TPN SDF with 50/60A HRC fuse
14.1 : Excavation for foundation in soft soil including dressing of sides and ramming of bottoms, lift upto 1.5 m including getting out the excavated soil and disposal of surplus excavated soil as directed, within a lead of 50 metres.
14.2 : Excavation for cable trenches of depth upto 1.2 m in soft soil including getting out the excavated soil and disposal of surplus excavated soil as directed within a lead of 50 metres.
14.10 : Providing and laying in position reinforced cement concrete 1 :2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) in foundation of pump, DG set etc. including form work etc. as required (excluding reinforcement).
14.11 : Providing brick work (in width 225 mm or more) with F.P.S. bricks of class designation 7.5 in cement mortar 1:4 (1 cement : 4 coarse sand) at all levels.
14.12.1 : Providing 15mm thick cement plaster of mix 1:4 (1 cement : 4 fine sand) at all levels.
od249975/2020_2021 : Steel reinforcement for R.C.C work including straightening, cutting, bending, placing in position and binding all complete upto plinth level
od241780/2020_2021 : Supply Conveyance, installation, testing and commissioning of 11.5/12W focus light light fitting (K-lite ID-4268/similar make ) on the existing cc plinth and giving connection etc as required.
od241781/2020_2021 : Supply Conveyance, installation, testing and commissioning of 15/16W bollard light fitting (K-lite ID-5566/Abby -Helix) on the existing cc plinth and giving connection etc as required.
od241782/2020_2021 : Supply Conveyance, installation, testing and commissioning of 15/16W bollard light fitting (K-lite ID-5565/Abby -Helix NW 30 K) on the existing cc plinth and giving connection etc as required.
od249495/2020_2021 : Supply Conveyance, installation, testing and commissioning of LED indirect wall bracket 24W fitting (K-lite ID-3658/similar make ) in place and giving connection with pvc insulated and sheathed 3 core round copper flex wire confirming to relevant ISS etc as required.
od249496/2020_2021 : Supply,conveyance , installation testing and commissioning of the following 12V 30W LED drive in the existing enclosure and giving connection as required (K-lite ID 8191/equivlent )
od249497/2020_2021 : Supply and providing flexible 12/15W/M LED strip inside the existing alu; diffucer and giving connection as rquired (Klite -ID 7281/equivlent )
od249498/2020_2021 : Supply and providing aluminium profile with P.C opal matt diffucer ,end cap,connector ,glue etc on surface using steel screws washer ,phil plug etc as required (Klite -ID 3087/equivlent )
od249499/2020_2021 : Supply,conveyance , installation of2/3 wire track with connector /end cap etc on the existing surface using steel screws /phil plug etc as required (K-liteID 7803/equivlent )
od249500/2020_2021 : Supply Conveyance, installation, testing and commissioning of 1x20W track light in position as required ( K-lite-ID-3678/similar make )
od249501/2020_2021 : Supply,conveyance , installation testing and commissioning of the following 12V150W LED drive of IP 65/67in the existing enclosure and giving connection as required (K-lite ID 8193/equivlent )
od249502/2020_2021 : Supply,conveyance , installation testing and commissioning of the following 12V100W LED drive of IP 65/67in the existing enclosure and giving connection as required (K-lite ID 8205/equivlent )
od249503/2020_2021 : Supply,conveyance , installation testing and commissioning of the following 12V 60W LED drive of IP 65/67in the existing enclosure and giving connection as required (K-liteID8192/equivlent )
od249504/2020_2021 : Supply and providing flexible 12/15W/M out door type IP 65/67 LED strip on surface using aluminium profile with diffucer ,end cap,connector ,glueetc ;and giving connection as rquired (Klite -ID 7289/equivlent )
od249505/2020_2021 : Supply Conveyance, installation, testing and commissioning of LED ceiling fixture 15/18W fitting (K-lite ID-3055/similar make ) in place and giving connection with pvc insulated and sheathed 3 core round copper flex wire confirming to relevant ISS etc as required.
od249506/2020_2021 : Supply Conveyance, installation, testing and commissioning of LED hanging light 15/18W fitting (K-lite ID-2875/similar make ) in place using anchor bolt and giving connection with pvc insulated and sheathed 3 core round copper flex wire confirming to relevant ISS etc as required.
od249507/2020_2021 : Supply Conveyance, installation, testing and commissioning of LED light fitting with IP 65 (K-lite ID-3780/similar make ) in place and giving connection with pvc insulated and sheathed 3 core round copper flex wire confirming to relevant ISS etc as required.
od249508/2020_2021 : Supply Conveyance, installation, testing and commissioning of wall bracket 10.5/12W light fitting (K-lite ID-3653/similar make ) in place and giving connection with pvc insulated and sheathed 3 core round copper flex wire confirming to relevant ISS etc as required.
od249509/2020_2021 : Supply Conveyance, installation, testing and commissioning of 3 W spot/focus light fitting (K-lite ID-6988/similar make ) in place and giving connection with pvc insulated and sheathed 3 core round copper flex wire confirming to relevant ISS etc as required.
od249510/2020_2021 : Supply Conveyance, installation, testing and commissioning of 15/16W yard/projector light fitting ite ID-4223/similar make ) in place and giving connection with PVC insulated and sheathed flexible 3 core(K-l copper wire confirming to relevent ISS etc as required.
od249511/2020_2021 : Supply,conveyance , installation testing and commissioning of the following make garden/path way poles with light fitting on the existing CC foundation with base plate ,foundation bolt/nut with washer etc and giving connection with PVC insulated and sheathed 3 cor copper flexible copper conductor conforming with relevant ISS etc as required .(K-lite ID KP4783 with 2x60W wing polar LED Lamps)
od249512/2020_2021 : Supply Conveyance, installation, testing and commissioning of 9 W up light /ground light with IP 68 connector (K-lite ID-4140 ) and giving connection etc as required.
od249514/2020_2021 : Supply Conveyance, installation, testing and commissioning of 40W Column light fitting (K-lite ID-7020/KeslecLUPUS-40) on the existing cc plinth using foundation bolt and nut with washer and giving connection etc as required.
Delstar a Grade Electrical contractors
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart shows the information on this page on a best-effort basis and does not guarantee that it is accurate, complete or current. Check it against the buyer's official notice and documents before you act on it; the official record prevails. TenderKart is not liable for any loss or claim arising from the use of this information. If you notice any error or omission, please let us know at .