| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹11.2 LAccepted-AOC HOUSE NO 01 B JANANA DODI OPP AKSHAY HOTEL RAI KA BAGH JODHPUR RAJASTHAN 342010 | 342010 | L1 | Accepted-AOC L1 | |
| 2 | L2₹14.4 L+₹2.8 L (24.3%)Rejected-AOC 06 KHASRA NUMBER 56 KIRAN NAGAR BASNI JODHPUR JODHPUR RAJASTHAN 342001 UDYAM RJ 22 0002214 | JODHPUR | RAJASTHAN | 342001 | L2 | Rejected-AOC L2 | |
| 3 | L3₹14.9 L+₹3.3 L (28.4%)Rejected-AOC H 10 KARNI NAGAR NEW NAGAUR ROAD NEAR MANDORE POLICE STATION 8TH MILL MANDORE JODHPUR 342304 | JODHPUR | JODHPUR | RAJASTHAN | 342304 | L3 | Rejected-AOC L3 | |
| 4 | L4₹15.0 L+₹3.4 L (29.1%)Rejected-AOC | L4 | Rejected-AOC L4 | |
| 5 | L5₹16.7 L+₹5.1 L (43.9%)Rejected-AOC | L5 | Rejected-AOC L5 |
Tender Value
₹20 L
EMD Value
₹40,000
Closing Date
20 Jul 2023, 6:00 pmClosed
GE (AF) No 02 Jodhpur
GE (AF) No 2 Jodhpur
Repair and Maint of external electric service at EM installation including earthing LT cable MCBBs and allied work under AGE EM GE AF 2 Jodhpur
2023_MES_599411_2
8389/E8
Open Tender
Electrical and Maintenance Works
Item Rate
210 days
GE
As per tender documents
8 documents required · 8 mandatory
₹500
GE (AF) No 02 Jodhpur
₹40,000
Yes
3 Aug 2023
22 Jun 2023
22 Jul 2023
22 Jun 2023
20 Jul 2023
7 Jul 2023
22 Jun 2023 - 29 Jun 2023
Amount
Taking down carefully copper/aluminum point wiring (Light/ fan, socket or power) complete, including fixture and fittings such as switches, ceiling roses, pendants, regulators, sockets, light fitting etc, stacking at site for reuse or removing materials to store for keeping in for taking credit and making good the disturbed surfaces / walls/ floors etc.
M&L for point wiring with 1.5 Sq. mm, multi-stranded copper conductor, single core, PVC insulated and unsheathed cable for phase and neutral, including 1.5 Sq. mm PVC insulated unsheathed multi-stranded copper conductor single core cable as earth continuity conductor (in green colour) connected to common earth dolly, drawn in and including PVC Casing and Capping, GI terminal boxes 1.2mm thick fixed flush to wall surface, covered with & including 3 mm thick plastic laminated sheet top cover for mounting switch and sockets etc. complete all as specified and directed for following : -
One light point/exhaust fan point controlled by one switch or one ceiling fan point controlled by one switch & electronic type fan regulator.
One 3 pin 5 Amp switch & socket outlet on same board with other switches.
One 3 pin 5 Amp switch & socket outlet on Independent board.
All same as per item ser No. 2.00 here-in-above but wiring using 2.5 sqmm multi-stranded copper conductor, single core, PVC insulated and unsheathed cable, including 2.5 Sq. mm PVC insulated unsheathed multi-stranded copper conductor single core cable as earth continuity conductor (in green colour) connected to common earth dolly for 6 pin, 15/16 Amps socket outlet on independent board.
S&F in repairs Switch piano, flush type, single pole, one way, 6 Amp.
S&F in repairs Socket outlet 2/3 pin, 2-in-1, 5/6 Amp, flush type.
S&F in repairs Switch Socket combination outlet 6 pin, 6/16 Amp, flush type
S&F in repairs Ceiling rose surface bakelite 65x50mm three terminal.
S&F in repairs Stepped type electronic fan regulator, socket size, flush type 230V AC.
S&F in repairs fan capacitor 2.5 Mfd suitable for 1200mm sweep ceiling fan, Make-EPCOS/USHA/Havells
S&F in repairs switch modular single pole one way 6 Amps 230 volt 1 module.
S&F in repairs switch modular single pole one way 16 Amps 230 volt 1 module.
S&F in repairs Socket modular 6 Amp 2/3 pin combined two module.
S&F in repairs Socket modular 6&16 Amp 2/3 pin combined two module.
S&F in repairs electronic fan regulator modular stepped type 120 watt, two module.
S&F MCB single pole 6-32 Amps, 240 volts, 10 kA rupturing capacity providing in DB complete including connection & testing all as specified.
M&L for MCB SPN 32Amps 240 volts, 10 kA rupturing capacity providing in DB complete including connection & testing all as specified.
M&L for MCB SPN/DP 40 to 63 Amps 240 volts, 10 kA rupturing capacity providing in DB complete including connection & testing all as specified.
M&L for MCB TPN/FP, 40 to 100 Amps 415 volts, 10 kA rupturing capacity providing in DB complete including connection & testing all as specified.
S&F in repairs metal clad, 2 Pin + Earth Plug Top 16 Amps, 240 volt.
S&F in repair of MCCB 4 Pole, 415 V, Adjustable type, 160 Amps with breaking capacity 36 KA, complete all as specified & directed.
S&F in repair of MCCB 4 Pole, 415 V, Adjustable type, 200 Amps with breaking capacity 36 KA complete all as specified & directed.
S&F in repair of MCCB 4 Pole, 415 V, Adjustable type, 250 Amps with breaking capacity 36 KA complete all as specified & directed.
Excavation in trenches in soft/loose soil not exceeding 1.5 metre wide and not exceeding 1.5 metre in depth for route of cable and getting out complete all as specified and as directed by the Engineer-in-Charge.
Returning, filling in soft/loose soil including spreading, levelling, watering and well ramming, in layers not exc 25 cm complete all as specified and as directed by the Engineer-in-Charge.
Removing of surplus soil to a distance not exc. 50 meter and depositing where directed at a level not exc.1.5 metre above the starting point complete all as specified and as directed by the Engineer-in-Charge.
M&L for stone slab 40 to 50 mm thick rough dressed Jodhpur stone slab cover in trenches for protection of cable 25 to 30 cm wide and not less than 50 cm in length laid dry abutting each other with gap between adjacent slab not exceeding 10 mm over sand cushioning all as specified and directed by Engr-in-Charge.
M&L Local tibba dry sand cushioning and cover (8 cm thick layer of sand before laying of cable and 15 cm thick layer of sand after laying of cable) for protection of cable, material and labour complete all as specified and as directed by Engineer-in-Charge. Notes : (i) Approved local Tibba dry sand free from vegetations, grass and other deleterious substances shall be used. (ii) For the purpose of payment, only consolidated thickness shall be measured.
Supply, laying, jointing and testing LT XLPE insulated screened, bedded, errazzo steel strip or wire armoured heavy duty electric cable with aluminium stranded conductor 1100 Volt grade cross sectional area 25 sqmm 4 core laid in trenches/ducts, through pipe, under floors or roads/ along poles etc complete all as specified including dismantling & taking out old unserviceable cable. Notes :- (i) Sand cushioning, cable protection and excavation & earth work shall be measured & paid for separately. (ii) Road cutting/floor cutting /cutting holes etc in walls required for laying/fixing of cable etc shall be made good as per existing. Nothing extra shall be admissible on this account. Quoted rates shall be inclusive of the above provisions.
S&F sheet metal enclosure distribution board for 240 volts, 8 way horizontal type, double door, single pole and neutral with 200 Amps rated neutral copper bus bar for housing MCB and fixed flush in wall surface, and tested on completion complete including taking out old all as directed.
S&F sheet metal enclosures with socket plug top, and MCBs single pole and neutral enclosure with a two pin and earth plug and socket complete with one single pole MCB upto 20 Amps, 240 Volt capacity fixed flush to wall surface including making good to damaged surface of wall to match with existing specification and tested on completion complete including taking out old all as directed.
S&F Sheet metal enclosure distribution board TPN, 415 volts, 4 way Horizontal/vertical type as per site requirement, double door type, 200 Amps rated neutral copper bus bar for housing MCBs and including provision for fixing TPN MCB as incomer, DB fixed flush or in wall surface including making good to damaged surface of wall to match with existing specification complete including taking out old all as specified all as specified and directed. Note : MCB SP/SPN/TPN will measured and paid separately under relevant item.
Taking down carefully light fitting any type from surface/recessed/wall mounting type stacking at site for re-use or shifting unserviceable lights to store for taking credit all as directed and specified.
S&F in repair compact commercial LED Tube light batten suitable for T8 LED tube rod, batten fixed using 2 Nos round or square box PVC heavy duty, connecting up with three core flexible copper conductor cable of suitable size from ceiling rose complete all as specified & directed. Make : Crompton Model UNILITE Cat part No DMLN1LT16 and hight efficiency LED Tube model Ultron Plus Cat Part No LT8-18-865-(3) or equivalent in approved makes.
S&F LED luminaire 600 mm x 600 mm, 35/36 watt, 220 V AC recessed type with high efficiency PMMA diffuser soft glare free light complete with driver, holders & LED lamp suitable for roof ceiling including connecting up with driver three core flexible copper conductor cases of suitable size complete all as specified & directed. Make: Crompton cat ref no. LCTLR-36-FO-CDL or equivalent in approved makes.
S&F LED light fitting 1 x 10W bulkhead luminaires including LED light driver perfect interior and exterior application connecting up with three core flexible copper conductor cable of suitable size complete all as specified & directed. Make: Crompton cat ref no. LBHP-10-CDL or equivalent in approved makes.
S&F Building security light fittings, with pressure die cast aluminium housing, suitable for 35 W LED, complete pre-wired, including suitable bracket for fixing light on wall or any indicated location all as specified and as directed by Engr - in Charge. Make: Havells Cat No: ENDURAPEARLSL35W or equivalent model approved makes.
S&F Building security light fittings, with pressure die cast aluminium housing, suitable for 60 W LED, complete pre-wired, including suitable bracket for fixing light on wall or any indicated location all as specified and as directed by Engr - in Charge. Make : Havells Cat No: ENDURAPEARLSL60W or equivalent model approved makes.
M&L for SPN/DP RCBO 40 Amps 240 volts, 30 mA capacity and 10 kA rupturing capacity providing in DB complete including connection & testing all as specified. Make- Havells cat part no-DHCEACSN2030040 or equivalent model approved makes.
S&F pyramid shape integral decorative as garden light with ip 65 degree of protection of capacity 9 watt LED with all accessories complete erect/fixed/mount properly at directed place with required fixing/mounting arrangement and connecting/testing complete all as specified by Engr-in-Charge. Make –Crompton or equivalent model approved makes.
Supply and fixing post top lantern LED type 40 watt 230 watt volts AC outdoor type with decorativepost top for 360 degree indirect light IP 65 protection with impact and corrosion resistant complete with driver and lamp complete.
NOTES FOR LED LIGHT FITTINGS & BULBS : (i) All LED light/luminare shall meet the provision laid down in IS - 16101, 16102 Part-I/II, 16103 Part-I, 16104, 16105, 16106, 16108/2012 and 15885 Part -II / Section 13. (ii) Contractor shall submit test report of LED street light fitting from Government accredited test laboratory for LM-79 and LM-80. (iii) Contractor has to furnish a replacement warranty of 02 years for LED light fittings complete including lamps from the date of completion of contract. The product will be replaced on site free of cost in the following case :- (a) Manufacturing defects. (b) Failure due to mechanical and electrical impact. (c) Drop in lumen (or lux at 1 m) below 90% of claimed values of lumen (or lux at 1 m) of the LED /Luminaries.
S&F PVC flat twin core cable, black sheathed, stranded aluminium conductor 4.0 Sqmm complete all as specified and directed.
S&F PVC flat twin core cable, black sheathed, stranded aluminium conductor 6.0 Sqmm complete all as specified and directed.
S&F PVC flat twin core cable, black sheathed, stranded aluminium conductor 10.0 Sqmm complete all as specified and directed.
M&L for Sub main wiring with approved colour coding as per IS, single core FRLS PVC insulated flexible multi-stranded copper conductor 1.1 KV grade drawn through & including PVC grey conduit heavy duty with necessary accessories (like bend, junction boxes etc.) including taking down old unserviceable sub main wiring complete all as specified for following sizes of wires :-. (Note :GI saddle shall be used to fix PVC conduit and distance between two saddle shall not be exceed 1.2 mtr)
Two runs of 6.0 Sq.mm main cable alongwith one run of single core 6.0 Sq.mm for continuous earth wire
new india engineers
Shri Electrical Enterprises
M/S VENUS BUILDER
J AND T Enterprises
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .