Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹2.6 LAccepted-Finance | L1 | Accepted-Finance LOWEST RATE QUOTED | |
| 2 | L2₹3.0 L+₹41,862.12 (16.1%)Rejected-Finance | L2 | Rejected-Finance HIGHER RATE QUOTED | |
| 3 | L3₹3.2 L+₹58,252.11 (22.5%)Rejected-Finance 30 1 PULIN KHATICK ROAD TANGRA TANGRA KOLKATA WEST BENGAL 700015 | KOLKATA | WEST BENGAL | 700015 | L3 | Rejected-Finance HIGHER RATE QUOTED | |
| 4 | L4₹3.2 L+₹58,565.28 (22.6%)Rejected-Finance | L4 | Rejected-Finance HIGHER RATE QUOTED | |
| 5 | L5₹3.7 L+₹1.1 L (41.9%)Rejected-Finance | L5 | Rejected-Finance HIGHER RATE QUOTED |
Tender Value
₹3.2 L
EMD Value
₹6,353
Closing Date
12 Oct 2022, 5:00 pmClosed
Regional Manager, Purba Burdwan Regional Office
Regional Manager Purba Burdwan Regional Office
Construction of 33 KV Outdoor terminal including erection of 33 KV CT, 33 KV PT, 33 KV VCB, 33 KV Panel with laying of control cable and other allied works for effecting 33 KV Bulk connection to Shyam Ferro Alloys Ltd at palitpur, Dewandighi, Burdwan
2022_WBSED_410078_1
RM/BDN/SHYAMFERRO/22-23/577
Open Tender
Miscellaneous Services
Item Rate
30 days
Shyam Ferro Alloys Ltd at palitpur, Dewandighi
Please refer Tender documents.
2 documents required · 2 mandatory
₹0
₹6,353
Yes
18 Oct 2022
23 Sept 2022
14 Oct 2022
24 Sept 2022
12 Oct 2022
24 Sept 2022
Amount
Erection of four pole structure with 9 mtr long PCC pole with cement concrete foundation from 1500mm below and upto 300mm above the G.L with centreing,plastering & net finishing above ground level for base protection of PCC pole including complete fittings with pole and structure paint as per WBSEDCL specified 33/11KV substation structure for 33KV gantry cum isolator & L.A support. (Struc. Drg. No- RE/SS/39)
Erection of four pole structure with 8mtr long PCC pole with cement concrete foundation from 2500mm below and upto 300mm above the G.L with centreing,plastering & net finishing above ground level for base protection of PCC pole including complete fittings with pole and structure paint as per WBSEDCL specified 33/11KV substation structure for for 33KV Low Level isolator support(Struc. Drg. No- RE/SS/41)
Suuply & Erectionof 33 KV CT G.I. Lattice structure as per approved drawing(PLN-DSS/57) in existing foundation.
Suuply & Erectionof 33 KV PT G.I. Lattice structure as per approved drawing(PLN-DSS/57) in existing foundation.
Fixing of 33 kv CR Type 400A HL Isolator with earth switch alongwith fixing of isolator handle and associated parts with proper adjustment for smooth opeartion with supply of compression type isolator pad to panther connector at High Level support structure
Fixing of 33 kv CR Type 400A LL Isolator w/o Earth Switch alongwith fixing of isolator handle and associated parts with proper adjustment for smooth opeartion with supply of compression type isolator pad to panther connector at Low Level support structure
Fixing of 42 kv 1 phase station class LA, jumpering from busbar, hardware etc. as required on existing structure as per approved drawing of WBSEDCL and scope of work.(1set-03nos.) with supply of connector
Fixing of 33 kv Pin Insulator with pin
Fixing of 33 kv Disc Insulator with hardware fittings (1set-03nos.) including supply of compression type tesion fittings and jumpering cone (Hardware)
Stringing & sagging of 200 sqmm ACSR (Panther) conductor,3 wire
Erection of 33 kv VCB scada compatible on existing plinth including fixing of structure with proper adjustment,earthing and control wire terminal connections, HT terminal connections including supply and fixing of compression type connector
Erection of 33 kv C&R panel for FDR control in control room which includes fixing of relays and meters, panel wiring and control wire connection etc. with supply an fixing of ferrule, connectors and other accessories.
Erection of 33 kv 2 core,dual ratio, 400-200/1-1-1A O/D CTs on existing structure which includes HT terminal connection,earthing and control wire termninal connection by suppling CT junction box & necessary pad connection(1 set-3nos.) with supply of compression type Panther to Stud connector
Erection of 33 kv/110v PTs which includes HT terminal connection,earthing & control wire terminal connection by supplying necessary connection (1 set-3nos.) with supply of compression joint
laying & crimping of 4x2.5sqmm armoured,stranded,copper conductor,PVC insulated & PVC sheathed cable
laying & crimping of 8x2.5sqmm armoured,stranded,copper conductor,PVC insulated & PVC sheathed cable
Laying of earth strip with MS Flat including cold bending to shape as require, after excavation of soil upto 0.5 M below the G.L. and back filing. Running welding of GI strip should be minimum 100 mm lapping. Electrode for welding should be approved by site Engineer
Construction of inspection pit 300x300x300 mm size(inside) with 250 mm thick brick work in cement mortar (1:4) 12 mm thick cement plaster in the inner and outer surface. Pit shall be covered with precast R.C.C slab 75 mm thick rainforced with 10 mm dia M.S. rod @ 100 mm center-to-center both ways including lifting lugs of 10 mm dia M.S. rod at middle.
Supply and Drawl of earth riser by 50x6 mm G.I Flat for earthing by welding sub-station structure & equipments, Isolator handle as per direction of site Engineer.
Painting of jointing portion of earth strip by bituminus after scrapping & smoothing of surface.
Supply and Fixing of Panther to Dog T connector for PT connection (1 set=3 nos)
MS DIPTI ELECTRICAL ENGINEERS
MS DAS AND CO
STAR LIGHT HOUSE
EPCON ENTERPRISES
stage.html
html • 0.05 MB
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .