EXECUTIVE ENGINEER, ELECTRICAL (R&B) DIVISION, GODHARA
Providing and Erecting Temporary EI with standby DG set and AC Machine for Side Domes (Dome 1&3) of upcoming Hon.PM visit in Panchamahal or Dahod or Mahisagar District under Godhra electrical R&B Division with 2 Day Rehearsal
336870
E Tender Notice No.TC/03/02 of 2025-26
Open
Electrical
Works
Panchmahal
8 documents required · 8 mandatory
₹2,400
EXECUTIVE ENGINEER, ELECTRICAL (R&B) DIVISION, GODHRA
₹56,000
21 Aug 2026
21 Aug 2026
21 Aug 2026
3 Sept 2026
21 Aug 2026
Name of Work:- Providing and Erecting Temporary E.I. with Standby DG Set and AC
Machine for Side Domes ( Dome 1 & 3 ) of Upcoming Hon'ble Prime Minister Visit in
Panchmahal or Dahod or Mahisagar District Under Godhra Electrical R&B Division. ( With
Days Reharsal )
Qty. Description. Per. Amount.
No. In Figure In Words
960 1st Day 1 Hire charges for providing electing and 745.38 Rupees Seven 1st Day
/Nos dismentling after use of good running condition hundred Forty /Nos
of 1200mm /1400 mm size ceilling fan with down Five Paise Thirty
rod of 8ft to 20ft height with necessary wiring Eight Only
for germon Structure dome complete with check
nuts, fan down road clamp with covered PVC
20 1st Day 2 Higher charges for providing erecting and 443.89 Rupees Four 1st Day
/Nos Removing after use of good running condition hundred Forty /Nos
300 mm/ 400 mm size low noise oscillation type Three Paise
pedestal fan of good condition. Eighty Nine
332 1st Day 3 Hire charges for providing for temporary plug 39.40 Rupees Thirty 1st Day
/Nos point with 5/15Amp plug switch combined, Nine Paise Forty /Nos
erected in wooden board complete Only
42 1st Day 4 Hire charges for providing erecting and 446.93 Rupees Four 1st Day
/Nos dismantling after use in good running condition hundred Forty /Nos
with necessary interconnecting wire/cable on Six Paise Ninety
panel board. (R) MCB Distribution boards Three Three Only
phase 230V(i) 4 -6 -8 Way
29 1st Day 5 Hire charges for providing erecting and 463.60 Rupees Four 1st Day
/Nos dismantling after use in good running condition. hundred Sixty /Nos
Section pillar fabricated from 16 SWG thick M.S. Three Paise
Sheet with 40 x 40 x 6 mm thick angle iron legs Sixty Only
with 12 mm thick bakelite / wooden sheet
erected complete with following sizes
(b) Section pillar having size 75 x 60 x
DTP of EI Side Dome Page 1 of
16 1st Day 6 Hire charges for providing erecting and 263.62 Rupees Two 1st Day
/Nos dismantling after use in good running condition. hundred Sixty /Nos
Section pillar fabricated from 16 SWG thick M.S. Three Paise
Sheet with 40 x 40 x 6 mm thick angle iron legs Sixty Two Only
with 12 mm thick bakelite / wooden sheet
erected complete with following sizes
(c ) Section pillar having size 60 x 30 x
3136 1st Day 7a Hire charges for providing, erecting & 6.06 Rupees Six 1st Day
/Rmt dismantling after use of good running condition Paise Six Only /Rmt
for PVC copper /Aluminium wire mains with
suitable copper PVC 1.5 / 2.5 Sq.mm earth wire
of following size (A) 2 wire 1 /1.5 / 2.5 Sq.mm
1352 1st Day 7b (C) 2 wire 4 /6 Sq.mm Copper 7.57 Rupees Seven 1st Day
/Rmt Paise Fifty /Rmt
6720 1st Day 7c (E) 4 wire 4 Sq.mm Copper 12.12 Rupees Twelve 1st Day
/Rmt Paise Twelve /Rmt
1668 1st Day 7d (G) 4 wire 6 Sq.mm Copper 18.18 Rupees 1st Day
/Rmt Eighteen Paise /Rmt
780 1st Day 8a Hire charges for providing erecting as per 19.69 Rupees 1st Day
/Rmt direction of Engineer in charge dismantling after Nineteen Paise /Rmt
use of good running condition for temporary Sixty Nine Only
power supply the XLPE insulated armoured cable
Aluminium conductor of following size.(A) 2 Core
1152 1st Day 8b (B) 4 Core 4 / 6 / 10 Sq.mm 25.75 Rupees Twenty 1st Day
/Rmt Five Paise /Rmt
3024 1st Day 8c (C) 4 Core 16 / 25 Sq.mm 28.79 Rupees Twenty 1st Day
/Rmt Eight Paise /Rmt
1512 1st Day 8d (D) 3 1/2 Core 35 Sq.mm 34.85 Rupees Thirty 1st Day
/Rmt Four Paise /Rmt
4356 1st Day 8e (E) 3 1/2 Core 50 / 70 Sq.mm 46.97 Rupees Forty 1st Day
/Rmt Six Paise Ninety /Rmt
DTP of EI Side Dome Page 2 of
1512 1st Day 8f (F) 3 1/2 Core 95 / 120 Sq.mm 71.21 Rupees Seventy 1st Day
/Rmt One Paise /Rmt
1008 1st Day 8g (G) 3 1/2 Core 150 / 185 Sq.mm 93.94 Rupees Ninety 1st Day
/Rmt Three Paise /Rmt
22 1st Day 9 Hire charges for providing, erecting with 293.92 Rupees Two 1st Day
/Nos necessary connection and dismantling after user hundred Ninety /Nos
of good running ELCBs/RCCBs conforming to IS Three Paise
12640 and having sensitivity of 30 ma and short Ninety Two
circuit withstand capacity of 6 KA and Suitable for Only
operation on 3 Phase and neutral 415V having
characteristic of quick action & tripping with all
advance feature & do not incorporate any
electronic component for following Max rating
(B) 63 Amps FP [Cat.II]
4 1st Day 10a Hire charges for Providing & erecting weather proof, 33896.62 Rupees Thirty 1st Day
/Nos dust & vermin proof / floor mounted Front operated Three /Nos
outdoor type cubical Panel board having IP 64 Thousand Eight
protection made from 14 SWG thick CRC MS sheet for
outer body and doors, 16 SWG thick CRC MS Sheet for
Six Paise Sixty
internal partition with neccessary supporting angles,
flats including cutting.bending , drilling, welding Two Only
revetting, with internal Partition and cable alley as per
requirement & instruction of Engineer in charge with
SUPPLY AND ERECTION OF of following type
switchgears /busbars with suitable size of inter
connecting PVC copper wire/ copper strips,rubber
grommets,rib,earth bus and earth bolt, foundation
flange- bolts - base plates, sufficient Nos. of Hinged
doors, handles with locking arrangement &rubber
gasket complete .The panel shall be painted with
epoxy powder coating and have Cu. Busbar strips
. Each bus bar should insulated by color coded sleeve.
WITH PHASE INDICATING Lamps--- Digital Multi
function meter - Voltage, Amperes & Frequency only)
with CTs coils) Each panel will contain earth bus and
earth bolts with danger notice board. [A] Cubical
panel with main interior 400 A 4 pole on load
Changeover switch and 400 A SFU/MCCB with four
nos of 40 A DP MCB and four nos of 40 A FP MCB as
standard outgoing. Other outgoing is to be
incorporated as demanded by engineer in charge and
rate for the same is to be taken extra in addition to
this. (With additional Earth Fault Relay)
DTP of EI Side Dome Page 3 of
6 1st Day 10b [B] Cubical panel with main interior 250 A 4 pole 18489.06 Rupees 1st Day
/Nos on load Changeover switch and 250A SFU/MCCB Eighteen /Nos
with four nos of 40 A DP MCB and four nos of 40 Thousand Four
A FP MCB as standard outgoing. Other outgoing hundred Eighty
is to be incorporated as demanded by engineer in Nine Paise Six
charge and rate for the same is to be taken extra Only
in addition to this. (With additional Earth Fault
18 1st Day 10c [C] Power Distribution Cubical Panel with main 12326.04 Rupees Twelve 1st Day
/Nos incomer 125A also with change over switch of Thousand Three /Nos
125A TPN MCCB - 1 Nos., 200 A Alum. Busbar, hundred
Outgoing 16A SP MCB 10 KA - 6 Nos, [Panel size Twenty Six
800mm H x 600 mm W x 350 mm D] (With Paise Four Only
additional Earth Fault Relay)
100 1st Day 11 63/100 A Four Pole Moulded Case Circuit Breaker 1365.01 Rupees One 1st Day
/Nos with spreader terminal and indication lamp Thousand Three /Nos
mounted on cubical panel with complete proper hundred Sixty
termination . Five Paise One
16 1st Day 12 200 A Four Pole Moulded Case Circuit Breaker 2954.26 Rupees Two 1st Day
/Nos with spreader terminal and indication lamp Thousand Nine /Nos
mounted on cubical panel with complete proper hundred Fifty
termination . Four Paise
336 1st Day 13 Hire charges for providing and erecting Miniature 18.48 Rupees 1st Day
/Nos circuit breaker single pole 6A to 25A suitable to Eighteen Paise /Nos
operate on 240 V A.C. system and having Forty Eight
breaking capacity 10 KA to be erected in existing Only
box. confirming to IS 8828/1996 with ISI Mark
1796 1st Day 14 Hire charges for Supplying and erecting ISI mark 6.06 Rupees Six 1st Day
/Rmt Medium class RIGID PVC /Flexible Pipes erected Paise Six Only /Rmt
on/in wall or ceiling erected with necessary
fittings & boxes fixed with adhesive solution &
Clamps in approved manner as directed
DTP of EI Side Dome Page 4 of
1680 1st Day 15 Hire charges for LED Flood Light Fittings with 1492.27 Rupees One 1st Day
/Nos High Power White LEDs wattage of 1 Watt and Thousand Four /Nos
above assemble on single MCPCB, efficiency hundred Ninety
more than 130 Im/w and corrosion free high Two Paise
pressure die cast aluminium housing with Twenty Seven
smooth finish powder coated and heat sink Only
extruded aluminium with diffuser and
Polycarbonate optics/lenses with company
mark/name engraved or embossed 120 to 300 V,
Power factor more than 0.95, THD<10%, CCT
5000 K to 5700K, Uniformity ratio >0.45,
Luminaire efficiency > 85 Lumens/Watt, LED
driver efficiency >85%. (Each fitting required LM-
79 & LM-80 Certificates) (B) Flood Light (IP-65),
Surge -4KV ( e ) Above 150 watts to 240 watts
143 1st Day 16 Hire charges for providing & dismantling earth 1155.95 Rupees One 1st Day
/Nos pit of minimum bore dia.150mm size approved Thousand One /Nos
make Earthing Electrode consisting Pipe-in-Pipe hundred Fifty
Technology as per IS 3043-1987 made of Five Paise
corrosion free G.I.Pipes having Outer pipe dia of Ninety Five
50mm having 80-200 Micron galvanizing, Inner Only
pipe dia of 25 mm having 200-250 Micron
galvanizing, connection terminal dia of 12mm
with constant ohmic value surrounded by highly
conductive compound with high charge
dissipation suitable for following type of
applications(a) For Electrical Installation up to
440V in normal soil
Length of pipe - 1 Mtr
Back filling compound - 1 Nos Bag of 15 Kg.
40 1st Day 17 Hire charges for providing erecting and 3466.32 Rupees Three 1st Day
/Nos dismantling after use of good running condition Thousand Four /Nos
Industrial Air Cooler With Water filling erected as hundred Sixty
per instruction of engineer-in -charge Six Paise Thirty
6 1st Day 18a Hire charges for440V A.C generating set following 36978.12 Rupees Thirty 1st Day
/Nos capacity with necessary fuel, mains, switchgears Six Thousand /Nos
& accessories complete running on load / no load Nine hundred
with acoustic sound proof enclosure etc as per Seventy Eight
requirement. With transportation charges up to Paise Twelve
30 kms.[F] 125 KVA Only
DTP of EI Side Dome Page 5 of
4 1st Day 18b [G] 250 KVA 58548.70 Rupees Fifty 1st Day
/Nos Eight Thousand /Nos
620 1st Day 19 Hire charges for providing, erecting, and 42.42 Rupees Forty 1st Day
/Rmt dismantling after use Flexible PVC insulated Two Paise Forty /Rmt
multistrand multi core 1.1 kv grade lSl marked Two Only
copper wires for sound system of following size.
(A).2 5 Sq.mm 3 core round l PVC sheathed
12 1st Day 20 Hire charges for providing and erecting the Iron 7703.77 Rupees Seven 1st Day
/Nos Scaffold tower of size 5' x 5'-0" x 25'-0" (High) Thousand /Nos
with necessary supports and cross arms with Seven hundred
necessary accessories as per requirement on site Three Paise
for erection of horns and halogen fittings as Seventy Seven
(Signature of Contractor)
Executive Engineer
Godhra Electrical Division
R & B Deptt. Godhra
DTP of EI Side Dome Page 6 of
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
RAW_HTML
01.Notice Inviting Online tender Upcoming PM EI side dome.pdf
02.SBD SIDE DOME.pdf
03.SCHEDULE-B SIDE DOME.pdf
04.PQ Criteria For UP coming PM-EI SIDE DOME.pdf
05.Online Tender Notice TC-03 of 2026-27.pdf
06.Special Condition for EI Work.pdf
07.FORMATE OF AFFIDAVIT ANNEXEURE-I Not Blacklisted.pdf
08.FORMATE OF AFFIDAVIT ANNEXEURE-II L1 Rate.pdf
09.Performance Securities and APS Ammendment.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at [email protected].