Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | 1₹2.2 CrAccepted-AOC | ₹2.2 Cr | 1 | Accepted-AOC O.K. |
| 2 | 2₹2.3 CrRejected-AOC | ₹2.3 Cr | 2 | Rejected-AOC O.K. |
| 3 | 3₹3.1 CrRejected-AOC | ₹3.1 Cr | 3 | Rejected-AOC O.K. |
| 4 | 4₹3.1 CrRejected-AOC 16 PRATAP NAGAR CHARBHUJA RAWATBHATA RAJASTHAN 323307 | RAWATBHATA | CHITTORGARH | RAJASTHAN | 323307 | ₹3.1 Cr | 4 | Rejected-AOC O.K. |
Tender Value
₹3.1 Cr
EMD Value
₹3.1 L
Closing Date
24 Sept 2018, 5:00 pmClosed
S.E., E.T.C., Bareilly
Superintending Engineer Hydel Campus, Near L.I.C. Office Rampur Garden, Bareilly
Construction, Restoration and Completion of 132KV Pilibhit-Bisalpur S.C. Transmission Line on D.C. Towers (that was under Construction by M/s. Accord Industries Ltd. against R.E.C. Financing Scheme) alongwith associated Works under ETD-II, Bareilly o
2018_UPTCL_251253_1
Short Term E-Tender No. 52 / W / ETC(B) /2018-19
Open Tender
Electrical Works
120 days
Bareilly
Please refer Tender documents.
2 documents required · 2 mandatory
₹11,800
A/c No 10897666087 IFSC SBIN0000615 S.B.I. Bly
₹3.1 L
8 Sept 2020
17 Sept 2018
25 Sept 2018
17 Sept 2018
24 Sept 2018
17 Sept 2018
17 Sept 2018 - 24 Sept 2018
Amount
Construction, Restoration & Completion of 132KV Pilibhit-Bisalpur S.C. Transmission Line on D.C. Towers (that was under Construction by M/s. Accord Industries Ltd. against R.E.C. Financing Scheme) alongwith other associated Works, with all Cost of Men, Materials, Misc. Consumables, T&Ps etc. including Transportation of Materials Required for Satisfactory Completion of the Work as per Technical Specifications, Drawing / Sample and Direction of the Supervising Engineer, as per Details below : (1) Compression type Double Tension Fitting Assembly, suitable for ACSR Panther Conductor consisting of Compression Dead End Clamp with Jumper Terminal (Cone), Anchor Shackle (2 No.), Yoke Plate (2 No.), Chain Link, Socket Clevis, Clevis Eye, Line side Arcing Horn, Tower side Arcing Horn complete with Bolts-Nuts-Spring Washers, Split Pin etc. as per Technical Spec. & Sample.
(2) Double Suspension Fitting Assembly, suitable for ACSR Panther Conductor consisting of Suspension Clamp, Ball Hook, Socket Eye (HH type), Line side Arcing Horn complete with Bolts-Nuts-Spring Washers, Split Pin etc. as per Technical Specifications & Sample.
(3) Compression type Single Tension Fitting Assembly, suitable for ACSR Panther Conductor consisting of Compression Dead End Clamp with Jumper Terminal (Cone), Anchor Shackle, Ball Clevis (HH type), Socket Clevis (HH type), Line side Arcing Horn, Tower side Arcing Horn complete with Bolts-Nuts-Spring Washers, Split Pin etc. as per Technical Specifications & Sample.
(4) Single Suspension Fitting Assembly, suitable for ACSR Panther Conductor consisting of Suspension Clamp, Ball Hook, Socket Eye (HH type), Line side Arcing Horn complete with Bolts-Nuts-Spring Washers, Split Pin etc. as per Technical Specifications & Sample.
(5) Mid Span Compression Joint, suitable for ACSR Panther Conductor consisting of extruded Aluminium Outer Sleeve (OD 38±1 mm, ID 23±0.2 mm, L 610±5 mm) and Mild Steel Inner Sleeve (OD 18±0.5 mm, ID 9.5±0.2 mm, L 203±5 mm) as per Technical Specifications & Sample.
(6) Repair Sleeve suitable for ACSR Panther Conductor duly made of extruded Aluminium Sleeve (OD 38±1 mm, ID 23±0.2 mm, L 241±5 mm) as per Technical Specifications & Sample.
(7) Stock Bridge Vibration Damper (4R type) suitable for ACSR Panther Conductor as per Technical Specifications & Sample.
(8) Performed Armour Rod Set, suitable for ACSR Panther Conductor consisting of 11 No. Al. Alloy Rods each of dia. 6.35(+)0/(-)0.1 mm & length 1950±25 mm as per Technical Specifications & Sample.
(9) Compression type Tension Fitting Assembly, suitable for 7/10 SWG Earth Wire consisting of Dead End Tube, Jumper Tube, Anchor D-Shackle complete with Bolts-Nuts-Spring Washers, Cotter Pin etc. as per Technical Specifications & Sample.
(10) Suspension Fitting Assembly, suitable for 7/10 SWG Earth Wire consisting of Suspension Clamp, Anchor Shackle, Keeper Piece, U-Bolt complete with Bolts-Nuts-Spring Washers, Split Pin etc. as per Technical Specifications & Sample.
(11) Mid Span Compression Joint, suitable for 7/10 SWG Earth Wire duly made of Mild Steel Tube (OD 18±0.2 mm, ID 10.3±0.2 mm, L 203±0.2 mm) as per Technical Specifications & Sample.
(12) Stock Bridge Vibration Damper (4R type), suitable for 7/10 SWG Earth Wire as per Technical Specifications & Sample.
(13) Flexible Copper Bond of size 12 mm x 570 mm duly made of Electrolytic Copper and crimped with Copper Lugs at both ends as per Technical Specifications & Sample
(14) Bird Guard of Saw Tooth type duly made of 18 SWG M.S. Sheet and Hot Dip Galvanized complete with G.I. Bolts - Nuts - Spring Washers etc., suitable for fixing on Cross Arm of 'A' type 132 KV Towers of KPTL design as per Technical Specifications & Sample.
(15) Number Plate in size of 165 mm x 150 mm duly made of 16 SWG M.S. Sheet with Letters and Numerals in enameled Red colour on White colour enameled background indicating name of Transmission Line in short (in English Letter of size 35 mm height) and Tower No. (in English Letter of size 65 mm height) as per requirement alongwith 2 No. 16 mm x 40 mm size G.I. Bolts - Nuts - Spring Washers with of 2 No. holes in Number Plate for fixing as per Technical Specifications & Sample and Instruction of Supervising Engineer.
(16) Phase Plate in Sets of both sides enamelled Red, Yellow & Blue colour Circular Discs of dia. 100 mm duly made of 16 SWG M.S. Sheet alongwith 1 No. 16 mm x 40 mm size G.I. Bolt - Nut - Spring Washer with 1 No. hole in Phase Plate for fixing as per Technical Specifications & Sample.
(17) Danger Plate in size of 380 mm x 250 mm duly made of 16 SWG M.S. Sheet written 'DANGER' in English letter of size 35 mm height, '[krjk' in Hindi Letter of size 45 mm height, '132000 Volt' in English Letter of size 30 mm height indicating 'Sign of Danger' in size of 70 mm x 80 mm all shown symmetrically in enamelled Red Colour on White Colour Enamelled background alongwith 2 No. 16 mm x 40 mm size G.I. Bolts - Nuts - Spring Washers with 2 No. holes in Danger Plate for fixing as per Technical Specifications & Sample.
(18) Pipe type Earthing Equipment Set consisting of 32 mm dia. 3050 mm long heavy duty perforated 'C' Class G.I. Pipe, 50 mm x 6 mm size & 4750 mm long Galvanized Steel Flat, 2 No. 12 mm x 40 mm size G.I. Bolts - Nuts - Spring Washers etc. as per Technical Specifications & Sample.
(19) Survey including making of Location Route, Preparation of Profile, Tower Schedule, Schedule of Materials for 132KV S.C. Pilibhit-Bisalpur Line on D.C. Towers.
(20) Check Survey & Peg marking of Tower / Gantry Locations.
(21) Excavation of Foundation Pits for 132KV Towers / Gantries including all Earth work, Back Filling, Leveling etc.
(22) Setting of Stubs of 132KV D.C. Towers including all Foundation Work but excluding the Cost of Concerting & Excavation as per Details below : (a) A+0' type Tower
(b) A+5' type Tower
(c) B+0' type Tower
(d) B+5' type Tower
(e) C+0' type Tower
(f) C+5' type Tower
(g) C+25' type Tower
(23) Concreting of Foundations using M20 Grade Cement - Concrete - Coarse Sand mixture in the Ratio of 1:2:4 with 20 mm Stone Metal for Towers & Gantries including Cost of Materials, De-watering, Shoring, Shuttering, Framing, Curing etc.
(24) Installation of Steel Reinforcement Bars in R.C.C. Foundation for Towers & Gantries including Cost of Steel Reinforcement Bars with due Cutting, Bending, Placing, Binding etc.
(25) Transportation of new Tower Parts, Gantry Structures, ACSR Panther Conductors, 7/10 SWG Earth Wire, Disc Insulators / Polymer Insulator Strings, Hardware Fittings etc. from designated Sub Stations in Bareilly / Pilibhit Districts to Line Site, Line Site to Line Site as per direction of the Supervising Engineer including Loading, Unloading & Stacking etc. (Total Weight of material is Approx. 1000 MT)
(26) Erection of Super Structures of above 132KV Towers, their Extensions wherever required and Gantries including all work above Ground Level with proper Fixing & Tightening of all Tower Parts including Fitting of Danger Plate, Phase Plate, Number Plate, Bird Guard etc. but excluding the Hoisting of Insulators, Fixing of Hardware Fittings, Conductor / Earth Wire Fittings / Accessories etc.
(27) Laying, Stringing, Tensioning, Clamping of 7/10 SWG Earth Wire including Fixing of Tension Fittings, Suspension Fittings, Vibration Dampers etc. between Section Towers, Section Tower to Gantry, Gantry to Section Tower on new Line Route.
(28) Laying, Stringing, Tensioning, Clamping of ACSR Panther Conductor in all the 3 Phases including Hoisting of Tension / Suspension Insulator Strings, Double / Single Tension Fittings, Single Suspension Fittings, Vibration Dampers etc. between Section Towers, Section Tower to Gantry, Gantry to Section Tower on new Line Route.
(29) Tack Welding of all the Bolts - Nuts upto 2nd Section of the Towers & upto 5 Meter height of Gantries from Ground Level with 3 Tacks of 10 mm thickness & finally, applying of Zinc Rich Aluminium Paint on the affected surface.
(30) Earthing work including Earth Work etc. for Pipe type Earthing of new Section Towers / Gantries including cost of Coke, Salt etc.
(31) Replacement of Tower Parts in Place of Missing ones after Fabrication of Tower Parts as per Sample from ‘Off’ sizes G.I. Angles with due Cutting, Drilling etc. and then, Fixing the same at Required Places at different Tower Locations of 132KV Pilibhit - Bisal Pur S.C. Transmission Line on D.C. Towers with proper Tightening & Chamfering etc. as per Technical Specification including Transportation of Tower Parts from Storage Place to Line Site and Back the Unutilized Materials to respective Stores.
(32) Cutting of various type of tree falling in the Corridor of 132KV Pilibhit - Bisal Pur S.C. Transmission Line on D.C. Towers having Girth between 0.0 - 2.0 Meter of Samul, Popular, Mango, Neem, Sheesham, Eucalyptus etc. to Provide Minimum Clearance of 8 Meter between Tree and Conductor on the both side of Towers / Conductors of the Transmission Line, with all due care of Safety & Precautions to Avoid any Damage to nearby Buildings, Power & Telephone Lines passing nearby, Crops, other nearby Trees etc. The Work also includes Removing, Eliminating and Cleaning the Line Sites after Lopping & Chopping of the Trees. (a) Trees having Girth between 0.5 - 1.0 Meter
(b) Trees having Girth between 1.0 - 2.0 Meter
(33) Lopping & Chopping of Branches of different types of Trees like Mango, Neem, Sheesham, Peepal, Semal, Eucalyptus, Popular etc. Falling in the Range of Corridor of the 132KV Pilibhit - Bisal Pur S.C. Transmission Line on D.C. Towers (Line length approx. 46.5 Km) to Provide Minimum Clearance of about 8 Meter between the Tree & Conductors on both sides of the Towers / Conductors of the Transmission Line with all due care of Safety & Precautions to Avoid any Damage to nearby Buildings, Power & Telephone Lines passing nearby, Crops, other nearby Trees etc. The Work also includes Removing, Eliminating and Cleaning the Line Sites after Lopping & Chopping of the Trees.
Bhagwati Traders
Jyoti Engineering Works
Gupta Construction Co.
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Download all tender documents and submit your bid