Loading…
Loading…
| # | Company | Status |
|---|---|---|
| 1 | Admitted-Finance | Admitted-Finance |
| 2 | Admitted-Finance NO 2254 RAGHAVENDRA COLONY SHAKTINAGAR RAICHUR RAICHUR KARNATAKA 584170 | RAICHUR | KARNATAKA | 584170 | Admitted-Finance |
| 3 | Admitted-Finance IX 526 527 HILL PALACE ROAD KARINGACHIRA IRUMPANAM P O TRIPUNITHURA ERNAKULAM KERALA 682309 | ERNAKULAM | KERALA | 682309 | Admitted-Finance |
| 4 | Rejected-Technical PB NO 04 KARUNAGAPALLY KOLLAM 690 518 | KARUNAGAPALLY | KOLLAM | KERALA | 690518 | Rejected-Technical The submitted documents does not meet PQ criteria. |
Tender Value
Refer Docs
EMD Value
₹65,000
Closing Date
23 Aug 2022, 11:00 amClosed
SM(Mat)-C
Contracts Dept. Corporate Materials FACT Udyogamandal
Repair of Economiser tubes of KHI boiler F4101, by replacing the lower portion of the tube from the bottom header during ATA 2022/2023.
2022_FACT_702757_1
05061/2022-2023/E25922
Open Tender
Miscellaneous Works
Works
30 days
FACT Udyogamandal
Please refer Tender documents.
7 documents required · 7 mandatory
₹0
₹65,000
Yes
28 Sept 2022
25 Jul 2022
24 Aug 2022
25 Jul 2022
23 Aug 2022
25 Jul 2022
Replacement of the bottom portion of economiser tubes from the first and second economiser Bottom headers of KHI Boiler, in Petro Plants that including: making necessary arrangements for accessing the economiser headers, removing the baffle plates required etc, cutting and removing the bottom portion of the economiser tubes (including bend portion) up to a height of 1000mm from the economiser header centre line, gouging the tube from the economiser header, fit-up of new tubes, TIG welding of new tube segments to old economiser tubes (240 joints – 120 on each header - Butt Welding), TIG welding other end of the tube to economiser header (240 Joints – branch weld), 100% radiographic testing of the welded butt joints, 100% ultra-sonic flaw detection test of branch welds, hydro testing of the boiler for leak testing., further repair if any. Tube Dimension: 50.8mm dia X3.2mm thk Material : ASTM A226
Fabrication and Supply of IBR certified tube segments as per the attached drawing. Tube Dimension: 50.8mm dia X3.2mm thk Material : ASTM A226 Approx length : 1000 mm TYPE 1 : 120 Nos TYPE 2 : 120 Nos
Repair of boiler tubes by replacing the damaged portion including 100% radiographic testing of the welded joints. (Rate shall be quoted for inch dia)
P SUNNY ENGINEERING CONTRACTOR
S K BOILERS PVT LTD
stage.html
html • 0.03 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .