Loading…
Tenderkart now works inside Claude and ChatGPT: search and analyse tenders right from your chat
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹23.0 LAccepted-AOC | L1 | Accepted-AOC Competent committee approved the tender in favour of Ist Lowest Bidder | |
| 2 | L2₹23.9 L+₹89,198.10 (3.88%)Rejected-AOC A 04 ADGNJ CHANDAN NAGAR OPP IOCL PETROL PUMP RAMPUR ROAD BAREILLY U P 243001 | BAREILLY | BAREILLY | UTTAR PRADESH | 243001 | L2 | Rejected-AOC Competent committee rejected the file due to higher rates | |
| 3 | L3₹27.1 L+₹4.1 L (17.9%)Rejected-AOC | L3 | Rejected-AOC Competent committee rejected the file due to higher rates |
Tender Value
₹23 L
EMD Value
₹23,000
Closing Date
7 Feb 2023, 12:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
SUPERINTENDING ENGINEER
ELECTRICITY DISTRIBUTION CIRCLE, KATJU MARG, BAREILLY
For System Improvement in Tuiliya at 33/11 KV S/s Nadausi in under EDD-I, Bareilly
2023_MVVNL_768975_1
77/EDCB/2022-23
Open Tender
Electrical Works
Item Rate
90 days
WORK
AS PER TENDER FORM
3 documents required · 3 mandatory
₹3,540
SE,EDC
₹23,000
21 Nov 2023
25 Jan 2023
8 Feb 2023
25 Jan 2023
7 Feb 2023
25 Jan 2023
Amount
The work of safe carriage of the following material from CB Ganj store center to work site under the jurisdiction of EDD-I Bareilly Approx. distance upto 25 Km. Including safe loading and unloading.
ST Pole 11 Mtr
PCC Pole 8.5 Mtr Long
11 KV XLPE Cable 3x120 Sq mm
AB Cable 3x95 sqmm
Outdoor Cable Box for 11 KV XLPE Cable 3x120 Sq mm
Straight Through Cable Jointing Kits for 11 KV XLPE Cable 3x120 sqmm
ACSR Weasal Conductor
ACSR Raabbit Conductor
11/0.4 KV 3 Phase 250 KVA T/F
11/0.4 KV 3 Phase 100 KVA T/F
Other Line material i.e., 33 KV & 11 KV pin insulater/stay/earthing complete/Disc Fitting/Disc Insulators/Dropper Channel/Crossing Bracing/ Top Channel/Binding Wire/Danger Board/Barbed Wire/numberplate/stone pad/Control Cable etc
Construction of T/F plinth 1.5x1.5x2 m3 for mounting 250 KVA T/F including foundation work (below ground 0.5 M), Brick work, RCC slab of 4” thickness and plastering in 1:6 ratio with 02 Nos channel pieces of 1.5 mtr long of size 100x50x6 mm compete in all respect
Cage fencing of 250 KVA Plinth mounted transformer in Town areas to avoid electrical human/cattle accidents by fabrication of cage (1 Inch Sq wiremesh) made of 10 No gauge in suitable size angle iron frame of size 7.5'(L)x5'(W)x8’(H) by strenghtening of wire mesh 20x3 mm M.S. flat haorizentally as well as vertically, Grouting the panel with 1:2:4 cement/coorse send/brick ballast. The Frame should be bolted on angles at the four corners so that frame may be un-bolted/bolted at the time of replacement of the transformer. Provision of 1 gate should be there for maintenance of the transformer. Painting (1 coat of red oxide + 2 coat of Bus green enamel paint). The wire mesh should be earthed with 50x6 mm MS earthing strip with existing earthing of Transformer Body. All men, material and T&P provided by the contractor to complete the fabrication, transportation and installation.
Mounting of 250 KVA T/F Transformers as per norms complete in all respect -
Mounting of 100 KVA T/F Transformers as per norms complete in all respect -
Pipe Earthing of VCB & Transformer (By boring of 4 inch diameter 20 m deep, 40 mm diameter A class GI pipe is inserted to a depth of 20 m and a holed pipe of 1.5 m length is inserted at the bottom. Tighten one end of the MS strip of size 50x6mm with the nut bolt with the neutral of the converter and weld the other end with the GI pipe inserted in the boring for earthing. Putting a socket on the upper part of the pipe (mouth) so that water can be poured into it to retain moisture. To complete the work Contractor will provide all material, Manpower, T&P, safe carriage of material to worksite. Above work will be carried out under supervision of concerned JE/SDO/EE)
Erection of Single/Double pole in H.T/L.T lines including fitting of all accessories as per RESSPO Norms
ST Pole 11 Mtr long (Single)
PCC Pole 8.5 Mtr Long (Single)
ST Pole 11 Mtr long (Double)
PCC Pole 8.5 Mtr Long (Double)
Grouting of following Pole with 1:4:8 mixture in size(450x450x1500mm.) including cost of cement/BB & sand Required as per RESSPO Norms
ST Pole 11 Mtr long (Single)
PCC Pole 8.5 Mtr Long (Single)
ST Pole 11 Mtr long (Double)
PCC Pole 8.5 Mtr Long (Double)
The work of Driving the earthing electrode and making connections with 6 S.W.G. GI wire as per RESSPO Norms
Laying, Stringing & Sagging of Following Conductor complete in all respect
ACSR Weasal Conductor
ACSR Rabbit Conductor
AB Cable 3x120 sqmm
AB Cable 3x95 sqmm
Under ground laying of 11 KV XLPE 3x185 sq mm cable in Single circuit complete in all respect Along with road restoration
laying of LT XLPE cable 1x400 sqmm complete in all respect
Hoisting of 11 KV XLPE Cable (3x185 Sqmm) on double pole bote with GI pipe of size 6" dia including the jumpering complete with clamps , nut and bolts
Supply & Laying of 6" dia G Pipe at various places i.e road crossing & Hoisting etc. complete in all respect ((ISO certified GI pipe 150 NB 3 mm thick dia 6" would be Provided by contractor through approved vendors of Discom at his own cost)
Fixing of Outdoor11 KV Cable Boxes for 3x120 sqmm XLPE Cable complete in all respect
Fixing of 11 KV Straigh through Jointing Kits for 3x120 sqmm XLPE Cable complete in all respect
The work of digging of pits, erection of Stay Clamp, Insulator etc.
Grouting of stays, 1:4:8 cc ratio (600x600x300mm.) as per RESPO norms.
Fixing of 3 Phase Distribution Boxes complete in all respect
Supply and Fixing of Following Material as per RESPO norms complete in all respect (would be Provided by contractor through approved vendors of Discom at his own cost)
Stone Pad 300x300x75 mm
X-Arm M.S. Angle 65x65x6 mm V-Type
Cross Arm Holding Clamp
11 KV Pin Insulator
11 KV Pin with Nut
F Bracket
Aluminium Tape
Aluminium binding wire
Jointing Sleev For ACSR Weasal
Jointing Sleev For ACSR Rabbit
Danger Board With Clamp
Barbed Wire
Number Plate
Top Channel 100x50x2240mm 9.6 KG/Mtr
Top Channel
Holding Clamp for Top Channel, TPMO & Fuse Set etc With Nut & bolts
T-Off Channel
Dropper Channel
Cross Bracings M.S. Angle
Stay Set Complete
Earthing Complete
3 Phase Distribution Box with 2 Nos Clamp
Danger Board With Clamp
M.S. Angle Iorn 75x75x6x2028 mm
Off Size Nut & Bolts with washer
Aluminium Lug 400 sqmm with Nut&Bolt
11 KV Pin
11 KV Pin Insulator
11 KV TPMO
11 KV Disc Insulator
11 KV Disc Fitting
11 KV Disc Insulator with fitting
11 KV Disc Insulator B&S Type
11 KV Pin Insulator with Nut & Bolt
Clamp With Nut & Bolt
Clamp With Nut & Bolt
PG Clamp
BHARAT ELECTRICAL TRADERS
TYCOON ENGINEERS
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .