Shri Santosh Kumar Rai IDSE SE CWE NB
Commander Works Engineer NB Kochi Kataribagh Naval Base PO Kochi 682 004
SPECIAL REPAIRS TO SCADA SYSTEM FOR WATER SUPPLY AT SMA RAMESWARAM UNDER GE FORT KOCHI
2024_MES_662391_1
81127
Open Tender
Miscellaneous Works
Item Rate
180 days
FORT KOCHI
AS PER TENDER DOCUMENT
7 documents required · 7 mandatory
₹0
₹49,100
Yes
24 Oct 2024
27 Jun 2024
5 Sept 2024
27 Jun 2024
3 Sept 2024
10 Jul 2024
Amount
Supply, Installation, Testing and Commissioning of 250 mm dia, three phase, Motor Actuated sluice valve, hand wheel for manual operation and having 02 Nos limit switches for Open / Close condition, 2 torque switches and valve position indicator including taking down complete, the mounting shall be direct/ indirect type using specialized extended type arrangement of GI pipe / plate of suitable size/thickness, angle irons and indirect mounting adaptors including raising of existing chamber if required so that actuator mounting is at least 12 inches above ground level complete all as specified and directed by Engr-in-Charge. Make: EMTORK/ABB/SEIMENS/L&T/SCHNEIDER or equivalent as directed by GE.
M&L for servicing of solenoid valve of any size i.e. removing, cleaning, greasing to wear and tear parts and refixing and make it operational from PLC control panel complete all as specified and directed by Engr-in-Charge.
Servicing of motorised butterfly valve of 100mm line size with shaft and complete parts i.e. removing, cleaning, greasing to wear and tear parts and refixing the same back in position or another location as directed by the Engineer-In -Charge and make it operational from PLC control panel complete all as specified and directed by Engr-in-Charge.
Programming of PLC's of slave control panels for GPRS modem and for existing static IP and if there any change in pumping sequence/logic as per site requirement as well as configuration of GPRS modems for existing static IP complete all as specified and directed by Engr-in-Charge. Note: All the cables i.e. programming cables, PLC to GPRS Modem cables and syntex box are included in the quoted rates.
SCADA programming for GPRS operated slave PLC control panels and if there is any upgradation in the existing screens or generation of soft keys and comprehensive maintenance of SCADA PC during entire contract period having hardware (CPU, monitor, keyboard, mouse), printer, UPS, display software (OS & SCADA), antivirus etc. complete all as specified and directed by Engineer-in-charge. Static IP charges for one year are included in this item as directed by Engineer-in-charge. Note: Spares will be measured and paid separately.
Supply, Installation, Testing and Commissioning of relay with base-4 C/O, 240V AC including taking down of old item complete all as specified and directed by Engr-in-Charge. Make: IDEC/Salzer/Omron/L&T or equivalent as approved by GE.
Supply, Installation, Testing and Commissioning of relay with base-4 C/O, 24V DC including taking down of old item complete all as specified and directed by Engr-in-Charge. Make: IDEC/Salzer/Omron/L&T or equivalent as approved by GE.
Supply, Installation, Testing and Commissioning of 3 pole 9Amp contactor including taking down of old item complete all as specified and directed by Engr-in-Charge. Make: L&T/Siemens/Schneider or equivalent as approved by GE.
Rewiring of PLC control panel for 3 phase actuators with 1.5 sqmm flexible wire including taking down of old item complete all as specified and directed by Engr-in-Charge.
Supply & Fixing of SMPS of 24 V DC, 5 Amp including taking down of old item complete all as specified and directed by Engr-in-Charge. Make: Schneider/ Meanwell/ABB or equivalent as approved by GE.
Supply & fixing of indicator lamp of 24 V DC/ 240 V AC of colour: RED/YELLOW/ GREEN /BLUE complete all as specified and directed by Engr-in-Charge. Make: L&T/Seimens/C&S or equivalent as approved by GE.
Supply & Fixing of push button with LED Indicator- 240V AC of Colour: RED/YELLOW/ GREEN including taking down of old item complete all as specified and directed by Engr-in-Charge. Make: L&T/Seimens/C&S or equivalent as approved by GE.
Repair and maintenance with rewiring if required and make fully functional the MIMIC panel with all the signal LED's and RS422/RS485 To RS232 converter required to make it complete operational all as specified and directed by Engr-in-Charge.
Supply, Installation, Testing and Commissioning of UPS of 1500VA, 865 Watt, 230V for minimum 60 minutes of battery backup for running of SCADA computer and all PLC panels including taking down of old item complete all as specified and directed by Engr-in-Charge. Make: Dell/Samsung/ HP or equivalent as approved by GE.
Supply, Installation, Testing and commissioning of Flow/Pressure transmitter 1-10 KG/sqcm with Pressure Guage and necessary fittings with proper wiring including taking down of old item complete all as specified and directed by Engr-in-Charge. Make: INDFOSS/DANFOSS/RAPID CONTROL or equivalent as approved by GE.
Supply, Installation, Testing and commissioning of rust proof, maintenance free Magnetic float switch sensors for OH tanks with specifications as Principle: Magnetic, Magnet: Ferrite Ring: Float and Guide: ABS, Switch: Reed, Connection cable: 2 core Teflon Cable including taking down of existing unserviceable sensors complete all as specified and directed by Engr-in-Charge. Make: CRYSTAL/RDS/ MAHALAXMI or equivalent as approved by GE.
Supply, Installation, Testing and commissioning of air releasing solenoid valve having 10mm dia, 230 V AC operated coil including taking down of old item complete all as specified and directed by Engineer-in-charge. Make :- ROTEX/AVCON/JOHNSON CONTROLS/ASCO or equivalent as approved by GE.
Supply, Installation, Testing and commissioning of priming solenoid valve/Actuator having 25mm dia, 230 V AC operated coil including taking down of old item complete all as specified and directed by Engineer-in-charge. Make:- ROTEX/AVCON/JOHNSON CONTROLS/ASCO or equivalent as approved by GE.
Supply, Installation, Testing and commissioning of electric motor suitable for 100mm dia size actuator including suitable PVC/metal casing for protection with locking arrangement from rain etc and taking down of old item complete all as specified and directed by Engineer-in-charge. Make: EMTORK/ABB/SEIMENS/L&T/SCHNEIDER or equivalent as directed by GE.
Supply, Installation, Testing and commissioning of resistor and capacitor set for 100mm/200mm line size actuator including taking down of old item complete all as specified and directed by Engr-in-Charge.
Supply, Installation, Testing and commissioning of Limit Switch with 1 NO, NC including taking down of old item complete all as specified and directed by Engineer-in-charge. Make: Honeywell/Schneider/L&T or equivalent as approved by GE.
Supply, Installation, Testing and commissioning of 4G/5G GPRS Modem with power supply adaptor and high gain omnidirectional antenna up to 16 DB. Modem should connect with PLC through RS485/MODBUS Protocol with syntex box of size upto 700x500x200 mm for accomadating complete set of modem box including taking down of old item complete all as specified and directed by Engineer-in-charge. Make: L&T/HPL/Elmeasure or equivalent as approved by GE. Note: Modem cost includes GPRS communication charges for 1 year also.
Supply, Installation, Testing and commissioning of motorized actuator with the following specifications with all accessories including taking down of old item complete all as specified and directed by Engineer-in-charge. (a) Valve size 100mm dia. (b) Designed line pressure 6 kg/Sqcm (c) Operating Angle: 90 degrees (d) Disc material CI with nylon coating (e) Limit switches: 02 Nos for open and close (f) Mounting: Splash Proof-Direct on valve/ Extended type as per site requirement. (g) Input Supply: 230V, AC, 50 HZ (h) In built wireless modem compatibility for remote communication (i) Valve position indication with an output of 4-20m A (j) The actuator should be capable of accepting 4-20m A of input of regulating purposes (k) Manual Operation: Hand Wheel/Rapid Control Make: Crawley/Leader/Intervalve/Audco or equivalent as approved by GE.
Supply, Installing, Testing and Commissioning of Ultrasonic Level Transmitter of specification as Range: 0-5 metres Accuracy: 0.5 % minimum Supply Voltage: 24V DC Output: 4-20 mA Ultrasonic Frequency:75 kHz burst, rep. rate 96 msec Delay at Power-up: 1.5 seconds Temperature Effect: Uncompensated: 0.2% of distance/°C and compensated: 0.02% of distance/°C Delay at Power-up: 1.5 seconds Resolution: 1.0 mm Output Response Time: 100 msec to 2300 msec Minimum Window Size: 20 mm Environmental Rating: Leakproof design is rated IEC IP67; NEMA 6P Operating Conditions: Temperature: –20 °C to 70 °C (–4 °F to 158 °F) Maximum relative humidity: 100% including taking down of old item complete all as specified and directed by Engineer-in-charge. Make: L&T/SIEMENS/HONEYWELL/ABB or equivalent as approved by GE.
Supply & fixing in replacement 6 core, 1.5 sqmm cross sectional area armoured copper conductor cables, 1100 volts grade heavy duty cable PVC insulated and PVC sheathed with suitable dia DWC HDPE pipe laid in trenches/ laid under floor or fixed make with walls / on poles/in ducts/in GI pipes etc including taking down of old item complete all as specified and directed by Engineer-in-charge Note : Rate deemed to be inclusive of rate of DWC HDPE pipe of suitable dia for protection of the cable. . Make: Polycab/FSC/Finolex or equivalent as approved by GE.
Supply & fixing in replacement 4 core, 1.5 sq.mm cross sectional area copper conductor cables, 1100 volts grade heavy duty cable PVC insulated and PVC sheathed with suitable dia DWC HDPE pipe , laid in trenches/ laid under floor or fixed make with walls / on poles/in ducts/in GI pipes etc including taking down of old item complete all as specified and directed by Engineer-in-charge. Note : Rate deemed to be inclusive of rate of DWC HDPE pipe of suitable dia for protection of the cable. . Make: Polycab/FSC/Finolex or equivalent as approved by GE.
Supply & fixing in replacement 5 Pair, 0.5 sq.mm cross sectional area copper conductor cables, 1100 volts grade heavy duty cable PVC insulated and PVC sheathed with suitable dia DWC HDPE pipe , laid in trenches/ laid under floor or fixed make with walls / on poles/in ducts/in GI pipes etc including taking down of old item complete all as specified and directed by Engineer-in-charge. Note : Rate deemed to be inclusive of rate of DWC HDPE pipe of suitable dia for protection of the cable. Make: Polycab/FSC/Finolex or equivalent as approved by GE.
Supply & fix cable joint kit suitable for cable size upto 6 core 1.5 sqmm complete all as specified and directed by Engr-in-Charge.
M&L for PVC/metal body cover for motorised operated valve complete including locking arrangement including taking down of old item complete all as specified and directed by Engr-in-Charge. Note for item Nos 1 to 29:- All equipments and components, etc for item Nos 1 to 29 above shall be made in India only.
Excavation in trenches n. exc 1.5 m wide and n. exc 1.5 m in depth for laying/removing of cable/erection of poles and getting out in soft loose soil complete all as specified and directed by Engr-in-Charge.
Returning, filling in, including spreading, levelling, watering and well ramming in layers n. exc. 25 cm thick complete all as specified and directed by Engr-in-Charge.
Removing excavated soil to a distance not exceeding 50 m and depositing where directed at a level not exceeding 1.5 m above the starting point complete all as specified and directed by Engr-in-Charge.
OM ENTERPRISES (BID ID -3064558)
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.PDF
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .