GE AF TEZPUR
GE AF TEZPUR ,PO-SALONIBARI,DIST-SONITPUR,ASSAM
REPAIR/REPLACEMENT AND PERIODICAL MAINTENANCE OF TRANSFORMER,POWER TRANSFORMER
2022_MES_537758_5
8663/E8
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
TEZPUR
AS PER NIT
8 documents required · 8 mandatory
₹500
GE (AF) TEZPUR
₹90,000
Yes
9 Feb 2023
13 Oct 2022
31 Oct 2022
13 Oct 2022
29 Oct 2022
17 Oct 2022
Amount
Dismantling of ACSR or AAC conductors, service feeder or distributor span complete all as directed.
Dismantling insulator any type, any size complete all as directed.
Dismantling cross arms of M S channels or angle sections etc complete all as directed.
Taking down existing, galvanized steel tubing, 80 mm bore, of any grade, in trenches or fixed to poles/Walls etc,including all fittings, complete all as directed.
Taking out existing, U/G cables, 11000 Volts grade from trenches/ducts/ poles etc of size 95 Sq. mm 3 Core complete all as directed.
Taking out existing, U/G cables, 11000 Volts grade from trenches/ducts/ poles etc of size 185 Sq. mm 3 Core complete all as directed.
Demolition of brickwork or stone/boulder masonry, built in cement mortar or cement lime mortar including all quoins, arches, pillars,etc, but excluding ashlar facings, dressed stonework and precast concrete articles complete all as directed.
Demolition of cement concrete (un reinforced) of any description and in any position not otherwise specifically provided for,complete all as directed.
Excavating in trenches, n exc 1.5 m wide and n exc 1.5 m in depth; for foundation, etc. or for shafts, wells, cesspits, manholes, pier holes, etc. n exc 10 sq m on plan and n exc 1.5 m in depth and getting out in soft/loose soil ,complete all as specified and directed.
Returning filling in soft/loose soil, including, spreading levelling watering and well ramming in layers not exc. 25 cm complete all as specified and directed.
Removing excavated soils to a distance not exceeding 50 Metres and depositing where directed at a level n. exc. 1.5 M above the starting point complete all asspecified and directed.
Materials and Labour for plain cement concrete (1:2:4) type B0 using 12.5 mm graded aggregate in lintels up to 1.5m clear span, cills, steps; seismic and other similar bands, plinth courses, string courses, lacing courses, parapets and railings up to 60 cm in height, copings, kneelers, apex stones, bed plates, kerbs, water troughs and the like including weathering, slightly rounded or chamfered angles and throating, as directed including necessary from work complete all as specified and directed.
Materials and Labour for brick work with Sub Class ‘B’ bricks straight or curved on plan exceeding 6M mean radius built in cement mortar (1:6),complete all as specified and directed.
Materials and Labour for Pea gravel 10mm size deposited, spread and levelled in layers not exceeding 15 cm thick,complete all as specified and directed.
Supply, laying, jointing and testing of, XLPE insulated, screened, PVC bedded, galvanized steel wire or tape armoured, heavy duty electric cables with aluminium conductor, 11000 Volts (Earthed) Grade, cross sectional area 95 Sq. mm, 3 core, complete all as specified and directed.
Supply, laying, jointing and testing of, XLPE insulated, screened, PVC bedded, galvanized steel wire or tape armoured, heavy duty electric cables with aluminium conductor, 11000 Volts (Earthed) Grade, cross sectional area 185 Sq. mm, 3 core, complete all as specified and directed.
Re-laying, jointing and testing of, XLPE insulated, screened, PVC bedded, galvanized steel wire or tape armoured, heavy duty electric cables with aluminium conductor, 11000 Volts (Earthed) Grade, cross sectional area 95 Sq. mm, 3 core, complete all as specified and directed. NOTE:-Old Serviceable HT Cables obtained from taking out vide BOQ/Schedule-A Serial Item No.5 here in before shall be re-used.
Supply and filling in dry sand in cable trenches before and after the cables are laid, as in sand cushioning to cables complete all as specified and directed.
Supplying and laying un-reinforced precast concrete cable cover,class HV, Type 1, flat, size 300mmx 180mm x 40mm,complete all as specified and directed.
Re-laying old serviceable un-reinforced precast concrete cable cover, in cable trenches, as cable protection complete all as specified and directed. Note:-Old serviceable cable covers obtained from taking out vide BOQ/Schedule-A Serial Item No. 5 & 6 here in before shall be re-used.
Supply and Laying galvanized steel tubing, 80 mm bore, light grade, in trenches or fixed to poles/Walls etc, for cable protection, complete all as specified and directed.
Supply and Fix in repair,cable jointing kit for 11 KV (Earthed) grade cable for indoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 50 sqmm to 95 sqmm,complete all as specified and directed.
Supply and Fix in repair,cable jointing kit for 11 KV (Earthed) grade cable for indoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 120 sqmm to 185 sqmm,complete all as specified and directed.
Supply and Fix in repair,cable jointing kit for 11 KV (Earthed) grade cable for outdoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 50 sqmm to 95 sqmm,complete all as specified and directed.
Supply and Fix in repair,cable jointing kit for 11 KV (Earthed) grade cable for straight through heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 50 sqmm to 95 sqmm,complete all as specified and directed.
Supply and Fix in repair,cable jointing kit for 11 KV (Earthed) grade cable for straight through heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 120 sqmm to 185 sqmm,complete all as specified and directed.
Supply and Fix,aluminium strip 25 x 3.15mm with saddles and fixing screws etc. for roof conductors and down conductors above ground, complete all as specified and directed.
Supply and Fix,copper strip 20 x 3.15mm with saddles and fixing screws etc.for roof conductors and down conductors above ground,complete all as specified and directed.
Supply and Laying,copper strip 32 x 6mm buried in ground,complete all as specified and directed.
Materials and Labour for cross arms, bracings, supports clamps and back plates fabricated from structural steel section including nuts, bolts, washers,welding, bending cold or hot, drilling holes for bolts in any shape or size as indicated or directed and inclusive of two coats of Aluminium paint over a coat of red-oxide, zinc chrome primer complete all as specified and directed.
Materials and Labour for drawing aluminium conductor,steel reinforced of any description including fixing of copper binding wire or aluminium tapes and including jointing, provision of jumpers etc complete all as specified and directed.
Supply and Fix,pin type, porcelain, vitreous, white,brown or green insulator including one galvanised mild steel spindle,two galvanised iron washers and one galvanised iron nut, 150mm height, 150 mm dia for 11000 volts grade,complete all as specified and directed.
Supply and Fix, composite polymer disc insulator,11 KV,creepage distance 340 mm,cantilever strength 70/90 kN,conforming to IEC: 61109,complete all as specified and directed. [Cat No. REE-PL-01-24F-11 of Make ‘Rashtriya’ or equivalent Model of Make ‘Jaipuria/BHEL/Supreme’]
Dismantling air break gang operated switches,triple pole,current rating up to 400 Amp, 11000 Volts Grade,vertical/horizontal mounted including insulators and operating mechanism for repair/ replacement of broken/worn out components and insulators etc.or carrying to MES store, complete all as specified and directed. Note:- Spare/components for replacement will be measured seperately under respective items of this BOQ.
Disconnecting all electrical connections form Control Room (MRS), taking down carefully parts (such as fixed contract, moving contact,spring with Teflon insert, phase coupler rod,rocker system with nylon bushes,arcing horn etc.) of switches air break,gang operated,triple pole,current rating up to 400 Amp,33000 Volts Grade,vertical/horizontal mounted,servicing lifting/ drawing mechanism by lubricating with petroleum jelly,readjustment of connection mechanisms, reconnection,commissioning and testing after repairs,complete all as specified and directed.
Supply and Fix in repairs,switches air break, gang operated, triple pole, mechanically operated, mounted on insulator and steel frame, with operating mechanism worked from ground level, for current rating up to 200 Amp, 11000 Volts Grade,complete all as specified and directed.
Supply and Fix in repairs,switches air break, gang operated, triple pole, mechanically operated, mounted on insulator and steel frame, with operating mechanism worked from ground level, for current rating up to 400 Amp, 11000 Volts Grade, complete all as specified and directed.
Supply and Fix in repairs,drop out fuse (DO Fuse),11000 Volts grade with mounting channel,post insulator caps,DO Fuse barrel holder,fiber glass tube DO fuse barrel with heavily tinned non ferrous metal parts at both the ends,DO fuse hook, brush type phosphorous bronze DO female contact, DO female contact holder,flexible copper wire,02(Two) Nos 11KV porcelain post insulators,complete all as specified and directed. [Cat No. REE-DO-01-11 of Make ‘Rashtriya’ or equivalent Model of Make ‘Jaipuria/BHEL]
Supply and Fix,lightning arresters metal oxide type,consisting of a stack of zinc oxide discs encapsulated in heat shrinkable sleeve,arranged in hermatically sealed porcelain housing,complete with all fittings,distribution class,discharge capacity 65 kilo amp,suitable for 11000 Volts,complete all as specified and directed.
Locating fault in existing HT (11000 Volts Earthed) underground cable network by means of cable fault locator with fault-distance accuracy less than 0.75 M (depending on displayed range) with computer-controlled automatic sectionalizing and fault locating with a simple “turn and click” operation and submission of report to Engineer in Charge, complete all as specified and directed.
Cutting of tree branch of girth exc. 20 cm but n.exc. 30 cm for clearing obstruction upto 3.00 metres from HT overhead lines throughout the route including cleaning away grass, vegetation saplings, shrubs, brush wood, around poles and stay assembly and including removing rubbish up to a distance of 50 meters out side the periphery of the area under clearance, complete all as specified and directed.
Material and Labour for preparation of surfaces and applying one coat of aluminium paint on old painted surfaces of steel tubular swaged poles, type 410 SP-22 (8.50 Metres Long) including cross arms, bracings, clamps etc. up to 1.5 M above PCC base and marking alternate strip horizontally of width 15 cm with one coat of synthetic enamel paint black & yellow colour above PCC base up to 1.5M height and numbering of poles with letters and figures of height 75 mm at a height 2.60 metre from ground level,complete all as specified and directed.
Material and Labour for complete removal of existing painting,preparation of surfaces and applying two coats of aluminium paint over a coat of red oxide zinc chrome primer on prepared surfaces of steel tubular swaged poles, type 410 SP-55 (11.00 Metres Long) in HT Two Pole Structure up to PCC base including cross arms, bracings,clamps etc.,complete all as specified and directed.
Material and Labour for complete removal of existing painting,preparation of surfaces and applying two coats of aluminium paint over a coat of red oxide zinc chrome primer on prepared surfaces of steel tubular swaged poles, type 410 SP-55 (11.00 Metres Long) in HT Three Pole Structure up to PCC base including cross arms, bracings, clamps etc.,complete all as specified and directed.
Material and Labour for complete removal of existing painting,preparation of surfaces and applying two coats of aluminium paint over a coat of red oxide zinc chrome primer on prepared surfaces of steel tubular swaged poles, type 410 SP-55 (11.00 Metres Long) in HT Four Pole Structure up to PCC base including cross arms,bracings,clamps etc.,complete all as specified and directed.
Material and Labour for complete removal of existing painting,preparation of surfaces and applying two coats of aluminium paint over a coat of red oxide zinc chrome primer on prepared surfaces of steel tubular swaged poles, type 410 SP-55 (11.00 Metres Long) in HT Twenty Four Pole Structure up to PCC base including cross arms,bracings,clamps etc., complete all as specified and directed.
Comprehensive Maintenance of existing HT 11 KV,400/630/800 Amps rating VCBs (Make : Crompton Greaves/ Areva ‘Alstom’/ Schneider/ Seimens/ ITE/Andrew Yule) by removing from housing, overhauling the mechanical parts and periodic maintenance servicing of 11KV indoor/ outdoor VCBs, checking of quality of vacuum interrupter, insulation resistances, static contact resistance, testing ( IR value, Ratio Test, Polarity) and connection checking of 11 KV Current Transformer ( Set of Three) by primary injection kit ,testing and calibration of relay ( Set of, Two Over Current and One Earth Fault Relays) by secondary injection kit including,all other functional tests of the VCB panels including for CTs, PTs, complete all as specified and directed. Notes:- (i) The work shall be carried out through Authorised Original Equipment Manufacturer's Service Centre Engineers or through OEM Certified Agencies as approved by the Engineer in Charge. (ii) Calibration and Testing(s) shall be done through State Electrical Licencing Board's valid electrical licence holder for the appropriate class/category of the work as approved by the Engineer in Charge. (iii) Spare Parts for replacement will be measured and paid seperately under respective items of this BOQ here in after.
Comprehensive Maintenance of existing HT 33 KV,1250 Amps rating VCBs (Make : Areva ‘Alstom’) by removing from housing, overhauling the mechanical parts and periodic maintenance servicing of 33 KV indoor outdoor VCBs,checking of quality of vacuum interrupter, insulation resistances, static contact resistance, testing ( IR value, Ratio Test, Polarity) and connection checking of 11 KV Current Transformer ( Set of Three) by primary injection kit ,testing and calibration of relay ( Set of, Two Over Current and One Earth Fault Relays) by secondary injection kit including,all other functional tests of the VCB panels including for CTs, PTs,complete all as specified and directed. Notes:- (i) The work shall be carried out through Authorised Original Equipment Manufacturer's Service Centre Engineers or through OEM Certified Agencies as approved by the Engineer in Charge. (ii) Calibration and Testing(s) shall be done through State Electrical Licencing Board's valid electrical licence holder for the appropriate class/category of the work as approved by the Engineer in Charge. (iii) Spare Parts for replacement will be measured and paid seperately under respective items of this BOQ here in after.
Supply Only, panel indicating lamp fitting, LED type suitable for110 volt/ 230 volt AC with base complete all as specified (Make: L&T / Siemens / STS/AE)
Supply Only, Breaker Control Switches,TNC (Trip,Neutral and Close), rating 25 Amps with contact arrangement 1Trip + 1Close, barrel lock mounting type, suitable for 11 KV VCB panels, complete all as specified. (Cat No 73257SEB90PGBB of Make L&T or equivalent Model of Make: Switron / Recom /Kaycee / Areva)
Supply Only, heater with heater switch & thermostat suitable for 11KV VCB panels, 80 watts, as per OEM's specifications,complete all as specified. (OEMs:-Crompton Greaves/ Areva ‘Alstom’/Schneider/ Seimens/ITE/ Andrew Yule)
Supply Only, HT Current Transformers, single phase indoor solid state (Resin cast) 11 KV, ratio 300/5A, accuracy class 5P10, rated burden 15VA, STC 13.1 KA for 1second,suitable for VCB Panels as per OEM's specifications,complete all as specified. (OEMs:-Crompton Greaves/ Areva ‘Alstom’/Schneider/Seimens/ITE/ Andrew Yule)
Supply Only,microprossesor based feeder protection neumerical relay with overcurrent, earth-fault, phase-discontinuity, negative-phase sequence and thermal-overload protections, inrush current detection, reclosing and measurement,preconfigured functionality facilitates, configurable binary inputs/outputs using local HMI or communication interface,modbus and IEC 60870-5-103 protocols supports,universal power supply 24-265 V AC/DC,suitable for 11 KV VCB panels,complete all as specified. (Cat No REJ601 of Make ABB or equivalent Model of Make: Schneider/ Seimens)
Supply Only,auxiliary relay with high-speed operation,rated voltage 24Volts DC,operating range - 30% to +10% of rated voltage,frequency 50 Hz +/-5%,pick-up voltage < 80%,Drop-off voltage > 20% ,Pick-up time 20-30ms,contacts 6N/O + 1N/C,suitable for 6.6 KV VCB panels,complete all as specified. (Type PQ8n of Make ABB or equivalent Model of Make: Schneider/ Seimens)
Supply Only,Vacuum Interrupter Assembly with Flex connection (R Phase, Y Phase & B Phase) suitable for 11 KV,630/800 Amps VCB Panels as per OEM's specifications,complete all as specified. (OEMs:-Crompton Greaves/ Areva ‘Alstom’/Schneider/Seimens/ITE/ Andrew Yule)
Supply Only base mounting type power pack with capacitor back up unit input voltage 230 V, output voltage 110 Volt DC, stored output 100 W sec, non store output 100W, with mains ON indicator,suitable for 11 KV VCB panels,complete all as specified. [Cat No. “CPP-1-U110-W100” of Make “Alen” or equivalent Model of Make ‘Jyoti/GE’]
Supply Only, fibre panel spout, 12Kv,50/60 Hz,suitable for 11 KV, 630/800 Amps VCB Panels (ABB VD4 11KV Monobloc 1250Amps) as per OEM's specifications,complete all as specified. (OEMs:-Crompton Greaves/ Areva ‘Alstom’/Schneider/Seimens/ITE/ Andrew Yule)
Supply Only, Epoxy Body,suitable for 11 KV, 630/800 Amps VCBs (Vacuum Switchgear Type VMX) as per OEM's specifications,complete all as specified. (OEMs:-Crompton Greaves/ Areva ‘Alstom’/Schneider/Seimens/ITE/ Andrew Yule)
Supply,installation,testing and commissioning of, Motor with Gear Assembly,110 Volts/230 Volts AC (Make Bosch/ Webtool/Ralliwolf) suitable for 6.6 KV VCBs as per OEM's specifications,complete all as specified and directed. (OEMs:-Crompton Greaves/ Areva ‘Alstom’/Schneider/Seimens/ITE/ Andrew Yule)
Supply,installation,testing and commissioning of,Non Latching Self Powered Numerical Protection Relay,for VCB/RMU,18 To 52 V & 75 To 250 V designed for use in unmanned substations where a dependable auxiliary power source is not available,designed to derive power for its operation from main current transformers,comprising integrated communication protocols for SCADA compliance,features of IDMT,as well as instantaneous protection for both over current & earth elements,suitable for accomplishing Digital filtering of measured quantities by using discrete Fourier analysis to suppress high frequency harmonics and transient DC components induced by faults or system operations and with front panel features of a 8-button keypad & a 16x2 LCD display for providing an easy user interface,complete all as specified and directed. [Cat No.CGI 14S of CG or equivalent Model of Make C&S/Seimens/ Schneider]
Repairs to battery charger with automatic float/boost change over suitable for charging of 110 Volts Battery Bank comprising of 55 Nos of 2 Volts,120 AH VRLA Type Batteries by removing from existing position,dismanteling of parts,periodic maintenance servicing of battery charger, rewinding of transformer with super enamelled copper wires of existing size including provision of all insulating materials and varnishing as per OEM's specifications,adjustment of short circuit & overload protections, FCBC system,contactors,relays etc.,replacement of Ammeter,Voltmeter, Indicators etc. including replacement of all internal wirings and control wirings as per OEM's specifications,re-fixing in original position,testing and commissioning, complete all as specified and directed. Note:-The work shall be carried out through Authorised Original Equipment Manufacturer's (Amara Raja) Service Centre Engineers or through OEM Certified Agencies as approved by the Engineer in Charge.
Supply Only,Release / Closing Coil,30V DC,suitable for 33 KV,1250 Amps rating outdoor VCB panels as per OEM's specifications,complete all as specified. (Code No.52747/2 (Old)/A 6111(New) of OEM Areva ‘Alstom’)
Supply Only,aluminium VCB pad clamp and connector with 06 (Six) Nos. of bolt with nut arrangement,suitable for 33 KV,1250 Amps rating outdoor VCB panels as per OEM's specifications,complete all as specified. (OEM:-Areva ‘Alstom’)
Materials and Labour for protection of aluminium VCB pad clamp and connector for 11KV/33 KV,400/630/800/1250 Amps rating indoor/outdoor VCB panels with with anti corrosive gel as per OEM's specifications, complete all as specified and directed. (OEMs:-Crompton Greaves/ Areva ‘Alstom’/Schneider/Seimens/ITE/ Andrew Yule)
Disconnecting all incoming and outgoing electrical connections,opening top lid cover of 33 KV CT PT combine unit with 3 Nos.CT & 1 No. PT coils,outdoor oil cooled type,3 Phase 4 Wire,50Hz,Power (kw) 100VA, Insulation Level (kv) 70/170KVP and disconnecting all internal connection for repairs and periodical maintenance, such as cleaning of core and winding by means of washing by draining down with clean dehydrated oil to remove dust /sludge on core and coil including cleaning of oil tank to removed sludge deposits,rewinding of burnt out transformer coil with super enameled /paper coated copper wire/strip of existing gauge/size and provision of all associated insulating materials such as separator etc, varnishing replacement of gasket set,replacement of silica gel, as per OEM's specifications,reassemblying of parts,re installation,testing and commissioning,complete all as specified and directed. Note: - Transformer Oil for replacement/ topping up will be measured and paid separately.
Supply and Fix,lightning arresters metal oxide type,consisting of a stack of zinc oxide discs encapsulated in heat shrinkable sleeve,arranged in hermatically sealed porcelain housing,complete with all fittings, transmission class,discharge capacity 65 kilo amp,suitable for 33000 Volts,complete all as specified and directed.
Supply and Fix in repairs,33 KV Outdoor Current Transformer,single phase outdoor dead tank type,ratio 200-100/5-5A, Core1: Class 5P10, 15VA, Core2: Class 0.5,15VA,rated short circuit thermal current 20 KA for 3 seconds, conforming to IS:2705,complete all as specified and directed.
Supply and Fix in repairs,33 KV, Out Door, Single Phase, Oil Cooled Potential Transformer(PT), 33 kV / √3 : 110 √3, Class 0.5, 200 VA burden, conforming to IS:3156,complete all as specified and directed.
Disconnecting all EHV and HV connection from existing 5 MVA,33 KV/11 KV Power Transformer,opening top lid cover of transformer and disconnecting all internal connection of EHV/HV side for periodical maintenance,such as cleaning of core and winding by means of washing by draining down with clean dehydrated oil to removed dust /sludge on core and coil including cleaning of oil tank to removed sludge deposits, replacement of gasket set,burnt spindle,damaged EHV/HV porcelain bushing,surge arrestor,re-fixing of top lid cover including refilling/topping up dehydrated new transformer oil,reconnection of EHV and HV connection, testing on load as per OEMs specifications and commissioning,complete all as specified and directed. NOTES: - (i) The work shall be carried out through Authorised & Qualified agencies as approved by the Engineer in Charge. (ii) Cost of transformer oil for cleaning by draining down shall be deemed to be included in the Quoted Rates. (iii) Topping up of transformer oil and dehydration & filteration of transformer oil will be measured and paid seperately under respective items of this BOQ here in after. (iv) Gasket set, EHV/HV side porcelain bushing,spindle for EHV/HV side and silica gel breather etc. for replacement will be measured and paid under relevant items of this BOQ. (v) Testing(s) shall be done through State Electrical Licencing Board's valid electrical licence holder for the appropriate class/category of the work as approved by the Engineer in Charge.
Supply Only, Breather assembly, filled with silica gel suitable for 5 MVA, 33 KV/11 KV Power Transformer,as per OEM's specifications,complete all as specified.
Supply Only,6mm-8mm thick gasket for top lid cover,EHV and HV bushing assembly of 5 MVA 33 KV/11 KV Power Transformer,as per OEM's specifications,complete all as specified.
Supply Only, porcelain bushing of HV side of transformer, conforming to IS:3347(Part-I) & IS:7412 suitable for 5 MVA 33 KV/11 KV Power Transformer,all as per OEM's specifications,complete all as specified.
Supply Only, porcelain bushing of EHV side of transformer,conforming to IS:3347(Part-I) & IS:7412 suitable for 5 MVA,33 KV/11 KV Power Transformer,all as per OEM's specifications,complete all as specified.
Disconnecting incoming, outgoing and earthing lead connections of transformers,100 KVA to 630 KVA,outdoor/indoor type from 11 KV /433 Volt supply system,carrying out routine yearly maintenance works as per Table-1 of IS:10028 (Part-III) including reconnection of all incoming outgoing and earthing lead connections,testing and commissioning, complete all as specified and directed. Notes:- (i) The work shall be carried out through Authorised & Qualified agencies as approved by the Engineer in Charge. (ii) Testing(s) shall be done through State Electrical Licencing Board's valid electrical licence holder for the appropriate class/category of the work as approved by the Engineer in Charge. (iii) Spare Parts for replacement, topping up of transformer oil and dehydration & filteration of transformer oil will be measured and paid seperately under respective items of this BOQ here in after.
Disconnecting incoming,outgoing and earthing lead connections of transformers,100 KVA to 160 KVA,outdoor/indoor type from 11 KV /433 Volt supply system,taking down carefully from pole/platform etc and transportation to workshop for repairs,carrying out routine yearly maintenance works as per Table-1 of IS:10028 (Part-III) including rewinding defective LT/HT Coil of transformer with super enameled /paper coated copper wire/strip of existing gauge/size and provision of all associated insulating materials such as separator etc, varnishing all as per OEM's specifications including dismantling of top cover, conservator, all internal connections and taking out core carefully and re-insulation after rewinding work and all arrangements for draining out transformer oil and refilling including reconnection of all internal connections,transportation of transformer from workshop to site and re installation in original position and including reconnection of all incoming outgoing and earthing lead connections,testing and commissioning,complete all as specified and directed. Notes:- (i) The work shall be carried out through Authorised & Qualified agencies as approved by the Engineer in Charge. (ii) Super enameled /paper coated copper wire/strip for rewinding of defective HV/LV coils will be measured and paid seperately under respective items of this BOQ. (iii) Testing(s) shall be done through State Electrical Licencing Board's valid electrical licence holder for the appropriate class/category of the work as approved by the Engineer in Charge. (iv) Spare Parts for replacement, topping up of transformer oil and dehydration & filteration of transformer oil will be measured and paid seperately under respective items of this BOQ here in after.
Disconnecting incoming,outgoing and earthing lead connections of transformers,200 KVA to 400 KVA,outdoor/indoor type from 11 KV /433 Volt supply system,taking down carefully from pole/platform etc and transportation to workshop for repairs,carrying out routine yearly maintenance works as per Table-1 of IS:10028 (Part-III) including rewinding defective LT/HT Coil of transformer with super enameled /paper coated copper wire/strip of existing gauge/size and provision of all associated insulating materials such as separator etc, varnishing all as per OEM's specifications including dismantling of top cover, conservator, all internal connections and taking out core carefully and re-insulation after rewinding work and all arrangements for draining out transformer oil and refilling including reconnection of all internal connections,transportation of transformer from workshop to site and re installation in original position and including reconnection of all incoming outgoing and earthing lead connections,testing and commissioning,complete all as specified and directed. Notes:- (i) The work shall be carried out through Authorised & Qualified agencies as approved by the Engineer in Charge. (ii) Super enameled /paper coated copper wire/strip for rewinding of defective HV/LV coils will be measured and paid seperately under respective items of this BOQ. (iii) Testing(s) shall be done through State Electrical Licencing Board's valid electrical licence holder for the appropriate class/category of the work as approved by the Engineer in Charge. (iv) Spare Parts for replacement, topping up of transformer oil and dehydration & filteration of transformer oil will be measured and paid seperately under respective items of this BOQ here in after.
Disconnecting incoming,outgoing and earthing lead connections of transformers,500 KVA to 630 KVA,outdoor/indoor type from 11 KV /433 Volt supply system,taking down carefully from pole/platform etc and transportation to workshop for repairs,carrying out routine yearly maintenance works as per Table-1 of IS:10028 (Part-III) including rewinding defective LT/HT Coil of transformer with super enameled /paper coated copper wire/strip of existing gauge/size and provision of all associated insulating materials such as separator etc, varnishing all as per OEM's specifications including dismantling of top cover, conservator, all internal connections and taking out core carefully and re-insulation after rewinding work and all arrangements for draining out transformer oil and refilling including reconnection of all internal connections,transportation of transformer from workshop to site and re installation in original position and including reconnection of all incoming outgoing and earthing lead connections,testing and commissioning,complete all as specified and directed. Notes:- (i) The work shall be carried out through Authorised & Qualified agencies as approved by the Engineer in Charge. (ii) Super enameled /paper coated copper wire/strip for rewinding of defective HV/LV coils will be measured and paid seperately under respective items of this BOQ. (iii) Testing(s) shall be done through State Electrical Licencing Board's valid electrical licence holder for the appropriate class/category of the work as approved by the Engineer in Charge. (iv) Spare Parts for replacement, topping up of transformer oil and dehydration & filteration of transformer oil will be measured and paid seperately under respective items of this BOQ here in after.
Supply Only, silica gel suitable for breather assembly of 100 KVA to 630 KVA transformers,as per OEM's specifications, complete all as specified.
Supply Only,silica gel breather assembly in PVC container with fully transparent body, filled with silica gel not less than 0.50 Kg. per container for 100 KVA to 630 KVA transformers,as per OEM's specifications, complete all as specified.
Supply Only,6mm-8mm thick gasket for top lid cover,HT and LT bushing assembly of 100 KVA to 160 KVA transformers,as per OEM's specifications,complete all as specified.
Supply Only,6mm-8mm thick gasket for top lid cover,HT and LT bushing assembly of 200 KVA to 400 KVA transformers,as per OEM's specifications,complete all as specified.
Supply Only,6mm-8mm thick gasket for top lid cover,HT and LT bushing assembly of 500 KVA to 630 KVA,11/0.433 KV transformers,all as per OEM's specifications,complete all as specified.
Supply Only,16 mm dia.,brass spindle with 05 Nos. Nuts, check nuts and washers, ISI Marked (IS: 3347) suitable for bushing assembly of 100 KVA to 630 KVA ,11/0.433 KV transformers,all as per OEM's specifications, complete all as specified.
Supply Only,20 mm dia.,brass spindle with 05 Nos. Nuts, check nuts and washers, ISI Marked (IS: 3347) suitable for bushing assembly of 100 KVA to 630 KVA ,11/0.433 KV transformers,all as per OEM's specifications, complete all as specified.
Supply Only,super enameled copper wire of existing gauge for HV Coil of transformer,all as per OEM's specifications, complete all as specified.
Supply Only,super enameled /paper coated copper strip of existing size for LV Coil of transformer,all as per OEM's specifications, complete all as specified.
Dehydration, filtration, de-sludge of transformer oil in situ for 33/11KV transformers / 11/0.433 KV transformers of any rating,by means of centrifugal filtration plant to achieve dielectric strength not less than 40 KV (rms) with gap of 2.5 mm, complete all as specified and directed. (NOTE: Transformer oil used for topping up will be measured and paid separately)
Supply, filling in, dehydration and filtration of new transformer oil, having dielectric strength not less than 40 KV (rms) with gap of 2.5 mm, conforming to IS: 335-1993, for topping up /replacement of transformer oil complete all as specified and directed. (Make: Shell/Gulf/Power Oil/Servo)
Materials and Labour for applying one coat of synthetic enamel paint on old painted exposed steel surfaces of transformer 100 KVA to 160 KVA, 11/0.433 KV transformers in situ by spray painting, after preparation of surface, including writing letters or figures (Block, Roman, Italic or Indian) n. exc. 30 cm high, stops commas, short lines, dashes, hyphens, brackets etc.for marking SM/MES No, Capacity etc. for the transformers, complete all as specified and directed.
Materials and Labour for applying one coat of synthetic enamel paint on old painted exposed steel surfaces of transformer 200 KVA to 400 KVA, 11/0.433 KV transformers in situ by spray painting, after preparation of surface, including writing letters or figures (Block, Roman, Italic or Indian) n. exc. 30 cm high, stops commas, short lines, dashes, hyphens, brackets etc.for marking SM/MES No, Capacity etc. for the transformers, complete all as specified and directed.
Materials and Labour for applying one coat of synthetic enamel paint on old painted exposed steel surfaces of transformer 500 KVA to 630 KVA, 11/0.433 KV transformers in situ by spray painting, after preparation of surface, including writing letters or figures (Block, Roman, Italic or Indian) n. exc. 30 cm high, stops commas, short lines, dashes, hyphens, brackets etc.for marking SM/MES No, Capacity etc. for the transformers, complete all as specified and directed.
Supply and Fix in repair, LED lights fitting 1x 10W, 220V,AC polycarbonate batten type with driver,holder including LED tube light connecting up with three core flexible copper conductor cable of suitable size from ceiling rose,complete as specified and directed. [Cat No.CCS-102-10-65-SL-DP-NWH of Make Crompton or equivalent Model of Make 'Wipro'/'Philips'/ 'GE']
Supply and Fix in repair, LED lights fitting 1x 20W, 220V,AC,polycarbonate batten type with driver,holder including LED tube light connecting up with three core flexible copper conductor cable of suitable size from ceiling rose, complete as specified and directed. [Cat No.CCS-102-20-65-SL-DP-NWH of Make Crompton or equivalent Model of Make 'Wipro'/'Philips'/ 'GE']
Supply and Fix in repair, LED light fitting 1X10W bulkhead luminaires including LED light driver holder connecting up with three core flexible copper conductor cable of suitable size,complete as specified and directed. [Cat No.LBHP-10-CDL of Make Crompton or equivalent Model of Make 'Wipro'/'Philips'/ 'GE']
Supply and Fix in repair,12 W round recess mounted LED edge lit slim down light with die-cast aluminium housing,powder coated finished,lumen efficacy 100 Lumens/Watt suitable for roof ceiling including connecting up with three core flexible copper conductor cable of suitable size,complete as specified and directed. [Cat No.LSCRM-12W-CDL of Make Crompton or equivalent Model of Make 'Wipro'/'Philips'/ 'GE']
Supply and Fix in repair,18 W square surface mounted LED panel with PDC aluminium housing and high translucent frosted plastic diffuser, lumen efficacy 100 Lumens/Watt suitable for roof ceiling including connecting up with three core flexible copper conductor cable of suitable size,complete as specified and directed. [Cat No.LCDSPLN-18-CDL of Make 'Crompton Greaves' or equivalent Model of Make 'Philips'/ 'Wipro'/'GE']
Supply and Fix in repairs,decorative wall light fixture made up of polycarbonate, with and including 15 W retrofit LED Lamp (Spiral B-22 base) complete all as specified and directed. [Model CITY 2, Cat No.LHDL03160099 for light fitting and Cat No. LHLDDEEEML8R015 for Lamp of Make 'Havells' or equivalent Model of Make 'Philips'/ 'Wipro'/'GE'/'Crompton']
Supply and Fix in repair,1 x 8 Watts LED T8 tube with extruded aluminium body,polycarbonate diffuser and in built driver,lumen efficacy 100 Lumens/ Watt,complete all as specified and directed. [Cat No.LTT8-8 of Make 'Crompton' or equivalent Model of Make 'Philips'/ 'Wipro'/'GE']
Supply and Fix in repair,1 x 20 Watts LED T8 tube with extruded aluminium body,polycarbonate diffuser and in built driver,lumen efficacy 100 Lumens/ Watt,complete all as specified and directed. [Cat No.LTT8-20 of Make 'Crompton' or equivalent Model of Make 'Philips'/ 'Wipro'/'GE']
Supply and Fix in repair,18 Watts LED PL-L,high efficacy,suitable for installation in existing 2G11 lamp holders,complete all as specified and directed. [Cat No. PHOTONULTRA PLL419TL18WLED865SPC of Make 'Havells' or equivalent Model of Make 'Wipro'/'Philips'/ 'GE'/'Crompton']
MAHANTA ENTERPRISES
kabitaconstruction
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .