Loading…
Loading…
Tender Value
₹2.1 Cr
EMD Value
₹2.1 L
Closing Date
18 Aug 2026, 5:00 pmClosed
Chief Officer,Sachin Notified Area
Upgradation Of Water Supply Network With Pumping Machinery Including Electro-Mechanical with Three-Year Free Comprehensive Maintenance Guarantee For Zone-I II and III At Notified Area GIDC-Sachin 2026-27.
326284
04 of 2026-27(Serial No. 2)
Open
Electrical - Motors and other equipment
Works
Surat
16 documents required · 16 mandatory
₹4,248
Chief Officer, Sachin Notified Area
₹2.1 L
3 Aug 2026
3 Aug 2026
3 Aug 2026
18 Aug 2026
3 Aug 2026
NAME OF WORK: -Upgradation Of Water Supply Network With Pumping Machinery Including Electro-Mechanical
With Three-Year Free Comprehensive Maintenance Guarantee For Zone-I, II And III At Notified
Area, GIDC-Sachin 2026-27.
DESCRIPTION QTY UNIT RATE AMOUNT
1 Supply, installation, testing & commissioning of Vertical 180 KW 14,878.00
Turbine pump motor set of specified duty parameters &
guaranteed efficiency of following MOC with specified
capacity vertical solid shaft TEFC squirrel cage induction
motor (with minimum IE-3 efficiency class), working on
three phase AC supply with 50 Hz ± 3%, 415 V ± 10%, rated
speed 1000 RPM along with column and bowl assembly,
discharge head, base channel / RSJ etc. complete as per
relevant IS. M.O.C.: Impeller & Sealing Rings: CF8M, Bowl
& Suction Bell: Cast Steel WCB , Shaft with coupling: SS
410, Column Pipe: MS ERW, Mechanical seal (above
kw),Base Plate: MS, Line Bearing: Thordon, Suction
Vertical Turbinel pump
77.09 lps, 33 M Head, (2W + 2S)
2 Do but 73 lps, 34 M Head, (2W + 2S) 180 KW 14,878.00
3 Do but 59 lps, 33 M Head, (2W + 2S) 152 KW 14,878.00
4 Providing submerged centrifugal pump sets (water 11.2 KW 11,634.00
immersed, dry air filled, class "F" insulated TEWC motor
integrally mounted on volute casing pump sets for water
duty, 3-phase, 50 ± 3% Hz, 415 ± 10% V along with suitable
foundation / installation device with cable length from
pumps to panels & of following Material of Construction:
Impeller: CF8M, Casing: C.I. FG 260, Wearing Ring: SS, TC
mechanical seal, CS/SS bearing, SS shaft with sleeve, SS
strainer & MS motor body.1-upto 30.0KW
13.90 lps, 15 M Head, (1W + 1S)
5 Do But Installation, testing & commissioning for pump sets. 2 Job 20,948.00
6 Expansion Below:- Supply, intallation, testing & 2 No. 4,896.00
commissioning of flange ends expansion bellow as per
EJMA standards of overall length of minimum 300 mm,
designed for 15 mm axial compression and 5 mm axial
extension with tie rods etc. of following MOC & pressure
ratings. MOC: Bellows: SA 240 Gr. 304; Internal sleeve: SA
240 Gr. 304; Weldends: IS 2062 Gr. B; Flanges: IS 2062 Gr.
B (Drilling as per IS 1538 / IS 6392) & Limit rods & nuts:
9 Reflux valves 2 Nos. 8,933.00
Supply, lowering, laying, and jointing of ISI mark CI D/F
reflux valve as per IS: 53112 (latest edition) of follwing class
and diameter including alll taxes, insurance, transportation,
frieght charges, octroi, inspection charges, loading,
unloading, conveyance to departmental strores, stacking,
cost of all labour, jointing material, nut blots and giving
satisfactory hydraulictesting, etc. complete.
Reflux valves PN 1.6 IS 5312 with ISI mark
11 Sluice valve:- Supply, lowering, laying, and jointing of ISI 4 Nos. 4,034.00
mark CI D/F Sluice Valves as per IS:14846 (Latest Edition)
of following class and diameter including all taxes,
insurance, transportation, freight charges, octroi, inspection
charges, loading, unloading, conveyance to departmental
stores, stacking cost of all labour, jointing material, nut blots
and giving satisfactory hydraulictesting, etc. complete (Rate
for all class of valves) sluice valve /BF valve. PN-1.6 With
gear operated (Ait-1 type long body) (for SCADA actuator-
compatible gearbox valves) PN- 1.6 80 mm
15 Air valves:- Providing and supplying C.I Temper proof Air 4 Nos. 16,427.00
valves with SS 304 float gun metal- nozzle of approved make
& quality of following class and diameter including all taxes,
insurance, trasportation, freight charges, octroi, inspection
charges, loading, unloading, conveyance to departmental
store, stacking etc. complete. With Isolating sluice valve PN
16 MS Specials flange ended 1,385.00 Kg. 98
1) Up to 300mm dia.
17 2) Above 300mm dia. 1,944.00 Kg. 98
18 MS Pipe:- Supply, lowering, laying, and jointing of Electric 37 RMT 2,119
Resistance Welded (Up to 400mm)/Submerged Arc
Welded(Above 400mm) M.S.Pipe having beveled ends plate
or coil conforming to IS-3589-2001 or its latest revision/
ammendment for following thickness outside diameter at
GWSSB store or site anywhere in Gujarat State including all
taxes, insurance, transportation, freight charges, octroi,
inspection charges, loading, unloading conveyance to
Departmental stores, stacking etc. all complete. (Rate for MS
Pipe based on the ex. works price of HR Coil as Rs.58500
per MT - withouth GST (Above 3.15 mm to 10 mm) & Rs.
59000.00 per MT without GST (Above 10 mm) as onJan-23.(
WPI Index of H. R Coil of Dec-22 is 144) and Lowering,
laying, jointing & welding in position to correct line & level
M.S. Pipe with outerside 3 LPE coating & inside solvent free
liquid epoxy lining on pedestal or chairs upon prepared
formation or prepared bedding in trenches the rates include
conveyance from store to site of work loading, unloading,
heat shrink sleev jointing hydrotesting etc. complete.- I/S
Solvent free Liquid Epoxy Lining (406 micron) + O/S 3 LPE
Coated M. S. Pipe. :- Pipe dia in OD 168.3mm 4.5 mm
19 Pipe dia in OD 273 5.0mm thickness 39 RMT 3,640.00
20 Pipe dia in OD 355.6 5.6mm thickness 69 RMT 5,106.00
21 Welding:- Welding in all positions with required number 121.9446 Rmt 681.00
runs, for M.S.Pipes internally and/or externally including
gauging wherever necessary, fixing appurtenances and other
accessories in connection with pipe laying work as per
specification.As Above for Butt joint: Plate thickness. 1)
welding for Pipe thickness 4mm to 7mm
22 Gas Cutting of MS Pipe / Plates:- Gas cutting(Either square 121.9446 Rmt 56.00
cut or V cut) pipes, plates etc. including all costs for the
following thickness. 2) Above 5mm up to 10mm
23 Full Bore Electromagnetic Flow Meter- Regular Power 1 No. 91,269.01
operated: Design, Supply, Installation, Testing,
Commissioning of Full Bore Electromagnetic flow meter
with factory calibrated,Regular Power Operated, flanged
connection, Flow sensor, Indicator, transmitter and totaliser
with all accessories viz.surge arrestor, associated cables,
cabinets, hardwares, etc complete as per following
specifications: Flow Transmitter/ Converter ( Remote Field
Mounted): Microprocessor based, Modular design, 2 line
LCD for indication of actual flow rate, forward, reverse, sum
totaliser display, ±0.5% accuracy at 0.3 to 4 m/sec velocity,
4 to 20 mA with HART/Modbus output, one scalable pulse,
one status output, IP 67 protection, Die cast aluminium/
polycarbonate/ SS316 with Anticorrosive Paint/ PU finish
with glass window enclosure, Inbuilt EEPROM and Data
Logger, 20 meters cable length for sensor to transmitter
communication etc alongwith wall mounted/ stand mounted
cabinet.: Full Bore Electromagnetic Flow Meter (Regular
Power Operated)- PN 16 For PN 16 rating, 10% rise in rate
to be considere on rate of PN 10 rating Item (Item No. 2A)
(7) 150mm Nominal Bore
24 (11) 350mm Nominal Bore 3 No. 2,04,490.00
25 Pressure Gauges with Accessories:- Design, Supply, 14 Nos. 2,629.00
Installation, Testing, Commissioning of Diaphragm sealed
Pressure Gauge, ±1% accuracy, Direct bottom 1/2" NPT (M)
process connection, IP 67, Glycerine filled, SS304 Case with
Bayonet Type Bezel, SS316 L Diaphragm, SS316 Bottom
Housing Material, SS 316 Movement material, Aluminium
dial with black graduation on white background, Micro Zero
adjustable pointer, neoprene gasket, Blow out disc, shatter
proof glass, SS tag plate etc as per IS 3624. (a) 100 mm Dial
Size, 0 to 10 Kg/cm2
26 Pressure Transmitter:- Design, Supply, Installation, Testing 18 Nos. 29,147.00
and Commissioning of Sealed Diaphragm Type Pressure
Transmitter. Piezo-resistive sensor technolgy based pressure
transmitter with Micro-processor based integral LED/ LCD
display, with accuracy of ± 0.3% of span, external zero and
span adjustment, self diagnostics, temperature sensor for
compensation. 15 to 36 V DC power supply, output signal of
4-20 mA DC with HART. Minimum IP 65 degree of
protection. Aluminium housing with epoxy coating,
Accessories like snubbers for pump discharge applications,
three way manifold, mounting brackets, name plate etc.
Material for accessories shall be SS. Protection Box/Canopy
shall be provided for outside installed transmitters. Pressure
Transmitter shall be suitable for following Range. :- 0 to
27 Ultrasonic Level Transmitter:- Ultrasonic Type Level 9 No. 59,436.00
Transmitter with Remote Display : Design, Supply,
Installation, Testing and Commissioning of NOn Contact
Ultrasonic Type Level Transmitter with Remote Display.
Sensor: The sensor should be non contact type, field
mounting type, housing shall have minimum IP65
protection, PP/ PVC Sensor MOC, with sensor to transmitter
cable. Remote Indicator cum Transmitter: Microprocessor
based indicator with LED / LCD digital display, panel/ wall
mounting type, power supply shall be 110-240 Vac or 15 to
36 Vdc, 50 Hz ± 10 %. Accesories: Mounting bracket, nut,
bolts etc as per system requirement and Hook up diagram of
the Instruments. Level Transmitter shall be suitable for
following Range.;- 0 to 10 Meter
28 LV PCC & MCC Panel:- Design, Supply, Installation, 1 Nos. 12,80,270.00
Testing and Commissioning of Power cum Motor Control
Centre of 400A, 415, TPN, Power Cum Motor Control
Centre (PCC & MCC) cubical having depth not less than
1000 mm throghout the required length & detachable,
fabricated from 2 mm CRCA sheet steel, free standing, floor
mounted, compartmentalized, extensible, dust and vermin
proof enclosure, duly painted provided with required rating
switch gears and shall be complete with (a) required size of
TPN Electrolyte 400 A Copper bus bar having cross section
not less than 1.6 Amp per 1.0 Sq. MM, (b) 400 Amp
capacity of 4 pole- EDO microproccessor based MOULDED
CASE CIRCUIT BREAKERS with RS 485 / RS
computer interface . All release of all MCCB, VFD should
have in built power meter/ analyser having, 3 phase, V, KW,
I, KVA, KVAh, KVArh, PF, Frequency, harmonic analysis up
to 30th harmonic and last ten faults history.with RS 485 / RS
232 computer interface facility and all other required
protection etc., complete. The PCC & MCC panel shall be
supplied as per detailed specifications with remote control
Panel including ON/OFF Push Button & indicator with
emergancy stop & reference single line diagram (SLD)
complete or the instruction of Engineer In charge. (45KW X
29 Do but (45KW X 4 nos VFD With 7.5KW x 2 nos S/D) 1 Nos. 13,07,041.00
30 Do but (37KW X 4 nos VFD) 1 Nos. 12,55,824.00
31 LV APFC PANEL:- Supply, installaton, testing & 3 No. 1,38,383.00
commissioning LV APFC panel consisting of required
capacitor banks for continuous duty to improve P.F. 0.85 to
0.99 in required steps enclosed in dust & vermin proof
compartment, indoor type, fabricated from CRCA sheet steel
with minimum thickness of 3 mm for base frame / channel /
gland plates, 2.0 mm for load bearing members / doors &
mm for internal partitions, minimum degree of protection -
IP 42, busbar chamber, required size of Al bus bar / terminals,
minimum 10 stage APFC relay, metering, indicating lamps,
push buttons complete as per IS: 16636-2017 with latest
ammendment & detailed technical specification and data
sheet as under.Up to 50 KVAR capacity: APFC panel
consisting following items. a) 125 A, 50 kA for 1sec. TP, TM
based MCCB with spreader terminals & rotary handle b) 0-
125 A range analogue ammeter of 96 x 96 mm size with
selector switch c) 3 nos. 125 / 5A, 10 VA CL-1.0 cast resin
type current transformer d) Suitable rating MCCB / MCB
&Contactors for each capacitor bank e) Suitable rating APP
type capacitor banks (vacuum impregnated with non-PCB /
non toxic oil, internally delta connected with built in internal
fuses complete with discharge resistances & terminal cover)
of approoved make in required steps with well suited detuned
reactor is placed in series with each capacitor step. (e.g.
KVAR capacity will be provided in steps of 2 nos x 5 KVAR,
2 nos x 7.5KVAR & 2 nos x12.5 KVAR). f) Enclosure
dimensions: 1600 (H) x 1150 (W) x 600 (D) As per above
32 PVC insulated flat / round submersible copper cables: PVC 70 Rmt. 81
insulated round submersible cable as per detailed technical
specifications conforming to IS 694, IEC 60227 / 60228. a)1
34 Supply installation testing commissioning Shielded Shielded 300 Mtr. 203.01
Control Cables for VRV System with necessary ISI mark
Medium class rigid PVC pipes with necessary accessories
with termination in machine and control equipment’s. (C) 4C
X 1.5 Sq mm Shielded Armoured
35 Supply, laying, testing & commissioning 1.1 kV grade, 400 Mtr. 504
XLPE insulated, stranded Aluminium conductor, galvanised
steel flat strip / round wire armoured, extruded PVC type ST2
sheathed, heavy duty cable (to be laid on wall surface with
necessary clamps / in existing cable trench / cable trays /
conduit / pipe sleeves at road crossing or floor as per site
requirement) conforming to IS:7098 (Part-1) & IEC:60502
(Part-1) of following sizes: g) 3.5 core x 150 Sqmm
36 h) 3.5 core x 185 Sqmm 200 Mtr 622
37 Cable Terminals (Lugs):- Providing & fitting crimping type 32 Ea. 21
Cable Terminals (Lugs) conforming to IS of following types
and sizes Aluminium Tubular Terminals (Long Barrel) (in
Sq. mm.). l) 150 sqmm
39 Copper Tubular Terminals (Long Barrel) (in Sq. mm.) a) 2.5 16 Ea. 4
41 Providing & fitting heavy duty brass cable glands (nickel- 4 Ea. 73
plated) with washers & rubber ring conforming to IS,
suitable for 3, 3½ & 4 core cables of following type & sizes:
Double Compression Brass Cable Glands. a) 3 sqmm
45 Providing and fixing printed instruction chart both in English 16 Ea. 130.29
and Gujarati and duly framed with front glasses, for
treatment of person suffering from Electric shock with
minimum 50" diagonally size.
46 Supplying rubber matting of following thickness as per 15 Sq.Mtr 1027.17
IS:15652/IEC 61111. (b)4mm
47 Providing pair of rubber hand gloves suitable for working on 6 No. 214.12
11 KV/22 KV supply.
48 Providing and erecting metallic vitrified danger notice board 12 No. 69.69
as per language suggested by engineer incharge for
MEDIUM VOLTAGE installation to be erected as per IS-
49 Providing and erecting metallic vitrified danger notice board 12 No. 81.81
as per language suggested by engineer incharge for HIGH
VOLTAGE installation to be erected as per IS.-2551.
50 Supplying & erecting ABC powder type 'Ceasefire' type Fire 12 No. 5090.4
extinguisher as per IS 13849 or 6 Kg capacity with necessary
clamp for erection on wall
51 Supplying & erecting carbon dioxide (CO2) fire extinguisher 6 No. 8671.86
user of following capacity with necessary clamps made from
50 x 6 mm M.S. Flat with nut & bolts grouted in wall
complete. [B] For 5.5 / 6.5 KG Capacity
52 Making trench in soft soil of suitable width of 90 cm deep 1,590.00 Mtr. 55.55
for laying cable or locating the fault all over the run and back
filling the same and making the surface as normal ground.
53 Covering of cable with second class bricks or cement tiles 600 Mtr. 140.39
laid cover the cable crosswise & also on both sides with
covering of 7. 5 Cm. layer of sand above & below cable (16
bricks per meter)
54 Providing & laying approved make Double walled 690 Mtr. 62.62
corrugated pipes (DWC) of polyethylene(conforming to IS
14930 II )with necessary connecting accessories of same
material at required depth in existing trench for laying of
cable. below ground / road surface for enclosing cable.
(A)50 mm outer dia.
55 (C))90 mm outer dia 600 Mtr. 95.95
56 Providing and erecting ISI mark Medium class RIGID PVC 630 Mtr. 33.33
PIPES of following size complete to be erected on/in wall or
ceiling erected with necessary PVC fittings & Junction
boxes fixed with adhesive solution & Clamps with following
dia of pipes, in approved manner as directed. (b) 25 mm
57 Supply & laying GI perforated type cable trays with returned 240 Rmt. 228
edge / flange, fabricated from 2.0 mm thk sheet steel in the
standard length of 2.5 mtrs, duly hot dipped galvanized after
fabrication as per IS 2629-1989 / IS 4759-1984 including
accessories such as coupler plates/ fish plates, bends, tees,
reducers, elbows, covers and electro-galvanized hardware
etc, erected on existing support as per specification and
instruction of Engineer-in-charge. a) 100(W) x 35(H) x
58 Supply, installation, testing & commissioning single girder 3 Set 4,76,250.00
type fully electrically operated EOT crane with electrically
operated hoist, class II duty, geared travelling trolley with
seven meter lift complete with long travel rail track (40 mm
sq. bar), moving or cross girder, all three motions electrically
operated by suitable rating motor IP 54, control panel &
down pendant control block, brake, safety device, cables
form motor to starter panel & other required accessories &
tested as per IS Specifications. capacity 2 Ton, Span 6m -
9m, Long travel 12mtr, Lift 6m -10m.
59 SITC of Vertical Air Termination Solid aluminium with 3 Ea. 9,416.23
Base- 10 mm dia and 1000 mm long. Air Termination Base
tested for conditioning, Ageing Test & Lightning impulse
current withstand test: 100 kA of 10/350µs waveform in an
accredited Third party laboratory as per 6.3 & 6.4 of IEC
62561-1 2017 protocol with MAST 34mm dia 3000 mm
long- Cold Galvanized
60 SITC of 8 mm dia solid Aluminium Conductor for roof top 150 Mtr. 299.97
mesh grid and tested as per IEC 62561- 2 conducted in the
Govt. accredited thirty party laboratory to meet the
requirement of IS/IEC 62305 with Required Accessories -
Aluminium Holding clamp at every 1 mtr distance,
Aluminium/SS cross splicer at every crossing of Alu.
conductor, Expansion piece with connectors at every 20 mtr
distance, Aluminium straight Splicer to connect conductors.
All Accessories should be tested as per IEC 62561-1
Cl. 6.3 for conditioning & Ageing Test & 6.4 for Lightning
impulse current withstand test: 100 kA of 10/350µs
waveform(Ageing & Electrical test ) conducted in a
sequence manner & tested in the Govt. accredited Third party
laboratory to meet the requirements of IS/IEC
61 Providing and erecting required size HOT deep Galvanised 150 Kg. 77.77
iron strip for earthing of H.T. , OCB/ ACB/ Transformer LT
panel board, Motors etc. using proper clamp.
62 Supplying & erecting earth pit of minimum bore dia.150mm 23 Nos. 5,760.03
size approved make Earthing Electrode consisting Pipe-in-
Pipe Technology as per IS 3043-1987 made of corrosion free
hot dipped G.I.Pipes having Outer pipe dia of 50mm having
80-200 Micron galvanising, Inner pipe dia of 25 mm having
200-250 Micron galvanising, connection terminal dia of
12mm with constant ohmic value surrounded by highly
conductive compound with high charge dissipation suitable
for following type of applications with chamber and heavy
duty cover.(approved make OEM has to submit test
certificate) & having back filling compound of (B) Inner
chemical (CCM Compound)- Resistivity:- 0.2 / meter testing
as per IEC 62561-2017, Voltage drop:- < 1 volt at no load &
dry form, Sulphar content:- <2%(C) Back fill Compound :-
Earthing compound should be capable to retain moisture for
long time Necessary test report must be submitted. (b)For
Electrical installation up to 11 KV in normal soil. Length of
Pipe : 2.00 mtrs.
Back filling Compound :1 no. Bag of 25 Kg.
63 (c) For Electrical Installation covering Transformer Neutrals, 9 Ea. 8,636.51
Lightning arrester Earthing, A.C.Plant & Sensitive Computer
System(like Automation, SCADA) i.e independent Earthing
in normal soil. Length of Pipe : 3.00 mtrs. Back filling
Compound :2 nos Bags of 25 Kg.
64 Supplying & erecting single phase approved make industrial 6 Ea. 3,339.06
exhaust fan suitable for medium duty ring mounted low noise
operation suitable for medium duty having following dia size
and maximum speed in RPM. [D] 450 mm dia 900 RPM cat
65 Point wiring for Light / Fan/ Bell/ Primary Point with 2-1.5 45 Pt. 372.24
sq. mm & earth wire of 1.5 sq. mm (green) both are of ISI
marked 1.1 kv grade FRLS PVC insulated multi strand
copper wires upto max length of 10 mt, in below type of pipe
erected with 6A Tissino Type ISI marked flush type switch /
bell push and accessories erected on Metal / PVC/Wooden
Box covered with 3 mm thick PC(Polycarbonate)
/Acrylic/Laminated sheet. with necessary Lamp
holder/ceiling rose / H.D.Connector as directed.
(a) with medium class Rigid PVC pipe and accessories
erected flushed on wall/ceiling complete
66 Point wiring for independent PLUG with following size 12 Pt. 518.58
mains earth wire of 1.5 sq.mm (green) both are of ISI marked
1.1 KV grade FRLS PVC insulated multi strand copper wires
upto 10 mt length, in following below of pipe erected
complete with ISI marked 3 / 5 Pin socket and tissino type
switch erected with earth continuity connection erected on
Metal / PVC/Wooden box covered with 3 mm thick
PC(Polycarbonate) / Acrylic/Laminated sheet. [B] 6/16A
Plug and 16 amp switch with 2-2.5 sq. mm Cu. Mains from
mcb d b boards.
(a) with medium class Rigid PVC pipe and accessories
erected flushed on wall/ceiling complete
67 Point wiring for FAN with 2-1.5 sq.mm & earth wire of 1.5 6 Pt. 670.24
sq.mm (Green) both are of .ISI marked 1.1 KV Grade FRLS
PVC insulated multi strand copper wires up to 10 mtr length,
in below type of pipe erected with 6A Modular type switch
and hum free EME step type electronic fan regulator
mounted and accessories with earth continuity of following
type erected on PVC / Metallic/Wooden box, single
mounting base frame covered with textured/metallic/white
front plate modules erected on / in wall / ceiling as per pipe
erected. with necessary ceiling rose / H.D. Connector as
(a) with medium class Rigid PVC pipe and accessories
erected flushed on wall/ceiling complete cat. III
68 Providing and erecting approved make split air-conditioning 6 Ea. 45,209.62
unit consisting of copper condensing unit with fan motor,
hermetically sealed rotary compressor with accessories etc.
duly connected separately erected evaporating unit and
blower motor with its accessories by means of extra supplied
proper insulated copper tubing, drain PVC pipes suitable for
( cost includes powder coated Stand, Eco Friendly green gas
charging, 15A plug top & Remote Control) with necessary
core cutting. (2)For ISEER Range (KWH/KWH)(4.0 to
4.49). (b) for 1.5 ton capacity
69 Supplying and erecting approved make Octagonal pole made 30 Ea. 8,192.11
from HR sheet steel. The pole should be made as per IS. and
shall be coated with hot dip galvanizing as per IS
2629/2633/4759, suitable suspend local wind speed with
integral Junction box consist of terminal plate of min 6mm
Hylam sheet, standard profile 35mmX7.5mm Din-Rail for
MCB Mounting, stud type terminal and arrangement for
cable termination to be erected With Suitable foundation
(Included) as per details given by manufacturer considering
site requirement.
(D) 6 Mtr. Long 70 mm Top X 135 mm bottom dia, 3 mm
thickness with 200mmX200mmX12mm base plate, 4-M20
Bolts and 600mm long J-Bolt.Approx Pole weight 59 kg
70 Providing and erecting street light pole bracket comprising 45 Ea. 614.08
main B Class GI pipe of 4.2 cm/require outside dia. complete
with suitable B Class G.I sleeve tubing of approx.
45cms.length and suitable for 76.5 mm / 80mm. / require size
pole top having sufficient fasteners for fixing the brackets
and having spread of 1 mtr. length with suitable rise as per
site condition & suitable welded stiffener reducer and nipple
with check nut complete painted with one coat of Red oxide
/ PU base primer and two coats of Aluminium / PU paint.
paint with following nos of arms.
[A] Single Arm Bracket 1 Mtr
71 Providing and erecting Pipe type earthing having 150 40 Ea. 368.65
cms.long and 2.5 cms. dia. galvanised iron pipe with
coupling and buch buried in specially prepared earth pit
complete with necessary 8 SWG earth wire.
72 Providing and erecting Pipe type earthing with 40 mm dia 3 Ea. 823.15
2.5 mtr long 'B' grade G.I. pipe with necessary coupling buch
buried in specially prepared earth pit & G.I. earth wire of
SWG erected & connected as directed (For panel)
73 For using salt and charcoal / coke as required for pipe type 33 Ea. 171.7
74 Supplying, erecting, testing, commissioning approved make 3 Ea. 1,41,616.14
M.S. Polygonal High Mast Pole having following general
Specification. (a) Polygonal Section fabricated from M.S.
Plate confirms BSEN 10025 & Hot deep galvanized
minimum 65/86 micron (as per IS 2629 /1985) Lantern
carriage with ring and rubber lines for erection of luminaries
of suitable site. (b) Maximum telescopic section not more
than four (c) Double drum gear pipe motorized winch with
6mm dia S.S. Rod (For 16 mtr and above size) (d) Approved
make L.E.D. aviation light = 1 No. Lightening arrestor =
No. with necessary wiring of 2.5 sq.mm 5 core ISI copper
cable Unarmoured. (e) Bottom most section suitable for
mounting reversible motor and switchgears having door not
more than 1400mm x 300mm with waterproof gasket &
hinges & locking arrangement. (f) Pole structure comprises
suitable size of reversible motor, cable and necessary
switchgears with control panel. (g) bottom section shall have
suitable size of thickness supports ribs foundation bolts nuts
etc. (h) Item not comprises the cost of lanterns. (i) Necessary
Cement Concrete foundation as per IS including testing &
commissioning of the entire structure for following size of
High Mast poles [1] High Mast 12 Mtr. TOP A/F 105 mm,
BOTTOM A/F 360mm, No. of Sec. No. - 1, Bottom
Thickness - 3 mm, Size of Base Plate - Dia 520 mm x 20 mm
thick, Foundation Bolt Size M24 x 850 mm, Qty - 6 Nos.,
Suitable for mounting Fitting of Light - 6 Nos.
75 Supply, laying, testing & commissioning 1.1 kV grade, 540 Mtr. 78
XLPE insulated, stranded Aluminium conductor, galvanised
steel flat strip / round wire armoured, extruded PVC type ST2
sheathed, heavy duty cable (to be laid on wall surface with
necessary clamps / in existing cable trench / cable trays /
conduit / pipe sleeves at road crossing or floor as per site
requirement) conforming to IS: 7098 (Part-1) & IEC:
(Part-1) of following sizes: 4 Core x 6.0 Sqmm
76 4 Core x 10 Sqmm 300 Mtr. 97
77 Providing & erecting Approved make Ceiling Fan with 6 Ea. 2,311.89
double ball bearing ISI mark with Condenser 230 volt
A.C.50 Hz 1200 mm sweep complete having 3 blades
aluminium body and blade sets having ornamental design
shanks , canopy erected with earthing. [ Make shall be
approved by Engineer in Charge]
78 Supplying and erecting 19 / 20 mm. nominal bore Medium 6 Ea. 108.07
Class M.S. Pipe down rod erected duly painted for fan
complete with proper insulation without leakage and
79 Supplying & erecting Fan Hook of 10 mm M.S. Round bar 6 Ea. 43.43
grouted in RCC slab with Making the site as original.
80 Supplying & erecting fan hook box of 10 mm M.S. round 6 Ea. 108.07
bar bounded to the RCC bars up to 50mm length each side
and pierced through a 16 Gauge M.S. box / Heavy Duty PVC
box complete erected concealed in Ceiling with necessary
81 Providing Fan clamp of 30 x 5 mm flat of required length & 6 Ea. 98.98
10 mm M.S. Bolt & Nuts erected with necessary hook of
mm M.S. Round Bar.
82 Providing 2.5mm.thick laminated acrylic sheet to cover the 6 Ea. 18.18
fan hook or Fan box.
83 Supplying and erecting LED indoor fittings with LEDs of 15 Ea. 373.7
wattage 0.2 Watt to 0.5 Watt assembled on single MCPCB,
with housing used as a heat sink shall be made of thick sheet
Steel conforming to IS: 513/CRCA/ aluminium die cast
powder coated and high U.V. & corrosion resistance with
diffuser with company mark/name 160V to 270V, Power
Factor more than 0.9, THD < 15%, CCT 3000 K to 6500K,
Luminaire efficacy> 85 lumens/watt ,LED LED driver
efficiency > 85 % ( fitting required LM-79 & LM-80
Certificates)(NOTE: Below description have shown ranges
of Wattage capacity of LED fittings.The Engineer incharge
may select any wattage capacity between the ranges shown.)
(A) Tube Light with integral driver
(iv) 22-24 Watts, Surge - 2KV,IP-20, conventional 4 feet
84 Supplying and erecting LED street light / Flood light fittings 42 Ea. 4,997.48
with High power White LEDs wattage of 3 Watt and above
assembled on single MCPCB, efficiency more than 130 lm/w
and corrosion free High pressure die cast aluminum housing
with smooth finish powder coated and heat sink extruded
aluminium with diffuser and Polycarbonate optics/ lenses,
with toughened glass with company mark/name engraved or
embossed 160 to 270 V,Power Factor more than 0.95, THD
< 10 %, CCT 3000 K to 5700K,Uniformity ratio >0.45,
Luminaire efficacy> 100 lumens/watt . LED driver
efficiency > 85 %.( fittings required LM-79 & LM-80
certificates)(NOTE: Below description have shown ranges of
Wattage capacity of LED fittings.The Engineer incharge may
select any wattage capacity between the ranges shown.) (A)
Street Light (IP-65), Surge protection -4KV integral and
,Light must have 440VAC line supply with over-voltage
protection. (ii) above 48 to 60 Watts cat-III
85 (B) Flood Light (IP-65), Surge protection -4KV integral and 18 Ea. 10,818.11
,Light must have 440VAC line supply with over-voltage
protection. (vii)above 200 to 250 watts
86 Supplying and erecting Flexible PVC insulated multi strand 750 Mtr. 46.46
multi core 1.1 kv grade ISI marked copper wires of following
size to be erected as directed. (e) 1.50 Sq.mm 3 core round
87 (k) 4.00Sq.mm 4 core round PVC sheathed 450 Mtr. 176.75
88 providing and erecting Miniature circuit breaker single pole 45 Ea. 112.11
6A to 25A suitable to operate on 240 V A.C. system and
having breaking capacity 10 KA to be erected in existing
box. confirming to IS 8828/1996 with ISI Mark
89 Providing and erecting Approved make RCCBs conforming 6 Ea. 2,637.11
to IS: 12640 and having sensitivity of 30 mA and Short
Circuit withstand capacity of 10 KA and suitable for
operation on 3 phase and neutral 415V,50Hz. having
characteristic of quick action & tripping with all advance
feature & do not incorporate any electronic component for
following Max. rating erected as directed. (ii) 40Amps. FP
90 Providing & erecting 415 V MCB Four Pole for Motor & 6 Ea. 668.62
Inductive Load (C Curve) having 10KA breaking capacity
& confirms to IS :8828 in existing box having following
capacity (b)40 Amp. Cat III
91 Providing & erecting 240 V MCB double pole switch for 6 Ea. 330.27
motor & inductive load (C Curve) having 10 KA breaking
capacity & confirms to IS : 8828 in existing box having
following capacity
(B) 40 Amp. CAT III
92 Providing and erecting Sheet Steel powder coated MCB 6 Ea. 1,492.78
distribution board - flush / surface mounted fitted with
busbar, neutral link, earth bar and DIN rail, Conforms to IS
8623-1 & 3, IEC 61439-1 & 3 without MCB to house
appropriate nos. of MCBs.(The DBs should be used of same
company of MCB to be used) suitable for (b) sheet steel
double door (IP-43). (iv) 12 Way
93 Supplying & erecting approved make IP 55 grade Company 3 Ea. 12,399.77
fabricated Timer Panel of following capacity for switch On-
Off street lights on time scheduling basis made from 16G
CRCA sheet duly epoxy power painted inside and outside
with hinged doors and locking arrangement consisting of
suitable size of 4 Pole MCB and 4 pole contactor (cat-
III)with analog time switch, auto manual switch of same
make and suitable input and output Bakelite terminals and
with door earthing approved by Engineer in charge. (A)
94 Providing & erecting 240 V MCB double pole switch for 6 Ea. 299.97
motor & inductive load (C Curve) having 10 KA breaking
capacity & confirms to IS : 8828 in existing box having
following capacity
(A) 6 to 32 Amp. Cat lll
95 Supplying & erecting approved make LAN cable of 1,200.00 Mtr. 94
following size in existing pipe as per direction. [E] CAT -
96 Supply, Installation Testing & Commissioning 10 Mtr. 5 Ea. 1,310.00
HDMI Interface Cable as per the detailed Specifications
supports transmission of 4K Signals as per the detailed
97 Supply, installation, testing & commissioning of LED TV 43 3 Ea. 38,727.00
inchas per the specification given in Detailed Technical
98 Supply, Installation, Testing & Commissioning of 6 MP 15 Nos. 12,477.67
VARIFOCAL BULLET CAMERA as per the specification
given in Detailed Technical Specification.
99 Supply, Installation, Testing & Commissioning of 4MP 9 Nos. 8,000.00
DOME CAMERA with Camera Safe Box as per the
specification given in Detailed Technical Specification.
100 Supply, Installation, Testing & Commissioning of 14" 15 Nos. 2093.67
CAMERA HOUSING as per the specification given in
Detailed Technical Specification.
101 Supply, Installation, Testing & Commissioning of CAMERA 15 Nos. 608.76
STAND as per the specification given in Detailed Technical
102 Supply, Installation, Testing & Commissioning of 6U Wall 3 Nos. 4,543.00
Mount RACK as per the specification given in Detailed
Technical Specification.
103 Supply, Installation, Testing & Commissioning of UPS FOR 3 Nos. 6,678.75
BACKUP 1100VA as per the specification given in Detailed
Technical Specification. Make will be as per attached make
104 Supply, Installation, Testing & Commissioning of 16 3 Nos. 19,027.50
CHANNEL NVR 2 SATA as per the specification given in
Detailed Technical Specification.
105 Supply, Installation, Testing & Commissioning of POE 3 Nos. 3,800.00
SWITCH 04 PORT as per the specification given in Detailed
Technical Specification.
106 Supply, Installation, Testing & Commissioning of POE 3 Nos. 9,900.00
SWITCH 16 PORT as per the specification given in Detailed
Technical Specification.
107 Supply, Installation, Testing & Commissioning of 3 Nos. 16,900.00
SURVELLIANCE HDD 4TB as per the specification given
in Detailed Technical Specification.
108 Supply, Installation, Testing & Commissioning of POWER 3 Nos. 2,123.79
BOARD 6A, 4 PLUG AND SWITCH as per the
specification given in Detailed Technical Specification.
109 SITC Of SC-SC Fibre Patch cord 3 mtr with joint box as per 9 Nos. 1,880.62
technical specifications.
110 SITC of Fiber Media Converter (10/100/1000 base T) as per 6 Nos. 6,136.76
technical specifications.
Total Amount in Rs.
Total Amount in Rs.
I / We agree to carry out the above work at ____________ % above the estimated rate ((In Words)
_________________________________________________) percentage above the Estimated Tender Rate.
I / We agree to carry out the above work at ____________ % below the estimated rate ((In Words)
_________________________________________________) percentage below the Estimated Tender Rate.
Estimated Amount Estimated Amount
Put to Tender Rs. 2,12,30,449.55 Put to Tender Rs.
Add % Above Rs. _____________ Deduct % Below Rs. ______________
Net Amount Rs.____________ Net Amount Rs. ______________
Net in Figure Rs. _____________ Net in Figure Rs. ______________
I / We have read the Condition mentioned in this tender and agree to abide by the same.
Note:- Estimated Cost put to tender is excluding GST and Including all other Taxes. GST will be paid additional
as per applicable rate prevailing from time to time and all other statutory liabilities are part of estimated
cost and will be bound by bidder. Prospective bidder may please by read carefully, app prevailing policy
/Government Resolution (GT) of Govt. of Gujarat (GoG)/competent authority, regarding GST and submit
the price bid offer accordingly.
Signature of Contractor with Seal Sachin Notified Area,
G.I.D.C.-SACHIN
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
RAW_HTML
Tender Documents.pdf
Schedule-B.pdf
B1 Agreement.pdf
Cori-326284.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .