Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹12.9 LAccepted-AOC H NO 199 W NO 6 NEAR OLD SDM OFFICE DISTT HAMIRPUR HP 177001 | HAMIRPUR | HAMIRPUR | HP | 177001 | L1 | Accepted-AOC work awarded being L1 | |
| 2 | L2₹14.3 L+₹1.4 L (10.6%)Rejected-Finance 2ND FLOOR SALIG RAM BUILDING OPPOSITE SHIMLA PUBLIC SC KHALINI SHIMLA HIMACHAL PRADESH 171002 | SHIMLA | HIMACHAL PRADESH | 171002 | L2 | Rejected-Finance Rejected being L2 firm | |
| 3 | Rejected-Technical | - | Rejected-Technical bid responsive but disqualified |
Tender Value
₹12.4 L
EMD Value
₹25,000
Closing Date
17 Jun 2020, 6:00 pmClosed
Executive Engineer, Electrical Division, HP.PWD Ma
Executive Engineer, Electrical Division, HP.PWD Mandi
Construction of Sanskriti Sadan at Motipur District Mandi HP SH Supply, installation Testing and commissioning of UPS System in Auditorium therein
2020_PWD_37850_1
PW/MED/TA/NIT/ e-notice/20-21-309-14 dt 22.05.20
Open Tender
Electrical Works
Item Rate
180 days
Motipur Distt Mandi
Please refer to bid document
11 documents required · 11 mandatory
₹500
Executive Engineer, Electrical Division, HP.PWD Ma
₹25,000
13 Oct 2021
8 Jun 2020
18 Jun 2020
8 Jun 2020
17 Jun 2020
8 Jun 2020
Amount
Supply Erection of 30 KVA/30 KW Online UPS : Three Phase Input & Three Phase Output-Autosensing, True Online UPS with Full Digital Signal Processing (DSP )Technologies with Touch Screen LCD /LED Panel & Pure Sine Wave O/P . UPS unit shall operate in double conversion mode, it shall be a VFI-type UPS (as per stanard IEC 62040-3) with Inbuilt /external Galvanic ISOLATION Transformer of same OEM make only. UPS should be with 3 level IGBT Based Rectifier & 3 Level IGBT Based Inverter Technology. UPS should have minimum 60 minutes backup on SMF Batteries Bank with Minimum VAH = 46800 VAH . along with following features/specifications The job includes the cost of carriage, erection, installation, commissioning and testing charges including rack, connecting and other petty material required to complete the job. Approved Make: APC- Schneider / Vertiv-Emerson / Legrand-Numeric / Mitsubishi Only.
The UPS should have following specification.
INPUT FEATURE :
Input Voltage window 320 VAC - 459 VAC 3 Phase
Input Frequency window 45-65 Hz .
Nominal Frequency 50 Hz
Total Harmonic Current Distortion (THDI ) should be less than 5 % at full rated load
Input power factor (PF) greater than or equal to 0.99
OUTPUT FEATURE :
Output Power Factor should be unity.
Output Power Capacity in watts (KW) 30KVA / 30KW
Output Voltage - 380 / 400 /415 Volts rms, adjustable via the user interface.
Total Harmonic Distortion : < 2% for linear load & < 5% for 100% non-linear load
Output Frequency : a. Rated Frequency:- 50 or 60 HZ. B Variations - +_ 0.01% ( Adjustable from frunt pannel )
Battery Bank :
UPS unit shall be equipped with its independent battery bank of the following:
a) VRLA type, mounted on a rack with a design life of 3 yrs as per OEM
b) The battery shall be sized to ensure continuity in the supply to the inverter for 60 minutes for a power rating of 30KVA at 0.8PF & 1.7 ECV.
Battery Type DC Voltage Bus with Flexibility of at least 2 no. of Batteries , Min. 60 Mins Backup , 12V Batteries will be provided by firm Minimum required VAH per UPS =46800.
Sealed Maintenance Free - Lead Acid Battery with suspended Electrolyte (Leak Proof)
Battery Make : Quanta / Exide/Panasonic make only
DC Battery Breaker : For safe maintenance on the battery of UPS unit, the system shall include a circuit breaker to isolate the battery from the corresponding rectifier /charger and inverter. When the battery is isolated from the system, the UPS shall continue to supply the load without interrup-tion or disturbance, except in the event of a normal AC source outage.
Battery Rack & Links - Racks Suitable for Mounting the All Batteries each Sheet Metal Type along with interconnection cables and 5/7 meter wire from UPS to battery bank.
Communications & Management :-
Interfact ports : optional SNMP , USB/ RS 232.
Touch Screen (LCD /LED) Display and Multicolour LED Bar highly visible even from a distance
Alarms : Audible Alarm required for Mains failure, Low Battery, Inverter Trip, Over Temperature, Over Load
Internal Backfeed Protection as standard
Noise level at 1meter (dBA) should be < 60dBA
Emergency Power Off (EPO) Should be available as standard
Regulatory Approvals :- EN/IEC 62040-2, EN/IEC 62040-3 Compliance & CE
EFFICIENCY :- Min. 96% ( AC to AC i.e Online Mode) and 98% ( Eco Mode ) without Isolation TX.
Overload Capacity: A) 10 minutes at a load representing 125% of the rated load 40 Deg. C continous. B) 1 Minutes at a load representing 150% of the rated load at 40 Deg. C continous
Parallel option upto 6-8 Units should be available .
UPS Should be built in Manual and automatic Bypass.
Warranty Terms :- 3 Years on UPS & 2 years on Batteries with onsite service Support.
Approved Make : APC- Schneider / Vertiv -Emerson/ Legrand-Numeric /Mitsubishi /GE Only .
SERVICE & Support : OEM should have service centers /network in the Mandi town for better services and need to furnish service centre address along with atleast two enginerrs contact details .
Providing and laying of one No. aluminium conductor, PVC insulated and PVC sheathed, armoured/XLPE power cable, working voltage 1100 volts grade direct in ground; to be laid 1 meter below the ground level including excavation sand cushioning, protective covering and refilling the trench etc. of the required size complete in all respect as per entire satisfaction of Engineer- in- Charge. i) Armoured cable 95 sq. mm (3.5 core) Cable Make : CCI/ Universal/ Finolex / Polycab / Rallison / Grandlay / KEI.
Providing, laying and fixing of one No. aluminium conductor, PVC insulated and PVC sheathed, armoured/XLPE power cable, working voltage 1100 volts grade on surface etc. of the required size complete in all respect as per entire satisfaction of Engineer- in- Charge. i) Armoured cable 95 sq. mm (3.5 core) Cable Make : CCI/ Universal/ Finolex / Polycab / Rallison / Grandlay / KEI.
Earthing with copper earth plate 600 mmx600 mmx 3 mm thick, including accessories and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. ( but without charcoal or coke and salt ) complete as required complete in all respect as per entire satisfaction of Engineer- in- Charge.Copper (Pure).
Extra for using salt and charcoal for G.I. or copper plate earth electrode complete as required complete in all respect as per entire satisfaction of Engineer- in- Charge.
Wiring for circuit/sub-main with following size PVC insulated heat resistant flame retardant (HRFR) and low smoke single core (flexible) copper conductor cable in surface/recessed steel conduit along with 1 No.HRFRLS/PVC insulated single core copper conductor cable of same size for earthing as required complete in all respect as per entire satisfaction of Engineer- in- Charge. i) 2x10 Sq. mm. Cable Make : Finolex / Plaza / RR / Unitech / Bonton / KEI.
Supplying and fixing of following sizes of PVC conduit along with the accessories in surface / recess including cutting the wall and making good the same in case of recessed conduit as required complete in all respect as per entire satisfaction of Engineer- in- Charge. i) 25 mm. dia Make : AKG/ BEC/NIC/ Diplast.
Providing and fixing following rating and breaking capacity MCCB in the existing cubical panel board including drilling holes in the cubicle panel, making connections, etc. as required complete in all respect as per entire satisfaction of Engineer- in- Charge. i) 125 Amp. -16 KA Make : Schncider/ Legrand/ L&T / Siemens.
Providing & fixing Superior Aesthetics, Enclosure for 3P & 4P MCCB's Generous space for cable termination, Mouting holes for easy wall mounting, Louvers for better heat dissipation, Effortless Installation, IK08 and IP30 Protection as required complete in all respect.
Satluj Document Company
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .