Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹38.0 LAdmitted-Finance | ₹38.0 L | L1 | Admitted-Finance |
| 2 | L2₹38.0 LAdmitted-Finance Q 158 SHIVALIK NAGAR HARIDWAR PIN 249 403 | HARIDWAR | UTTARAKHAND | 249403 | ₹38.0 L | L2 | Admitted-Finance |
| 3 | Rejected-Technical 221 VIJAY PARK EXTENSION LANE NO 11 DEHRADUN | DEHRADUN | UTTARAKHAND | 248001 | - | - | Rejected-Technical BID IS NON RESPONSIVE |
| Sl No | Description | Qty | Unit | Garg Construction L1 | Purohit Hydro Power Management L2 |
|---|---|---|---|---|---|
| 1.00MV CABLES | |||||
| 2.00Laying of PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing RCC/ HUME/ METAL/DWC pipe as required. | |||||
| 3.00 | Upto 35 sq. mm | 500 | Mtr | 39 ₹19,500 | 38 ₹19,000 |
| 4.00Supply, connection, testing and commissioning of heavy duty, medium voltage, XLPE (IS 7098 - PART-II) insulated, Stranded AL / Cu conductor Armoured / Flexible cables as per specification & IS. The cable shall have outer sheeth of XLPE and inner sheath of PVC with stranded AL conductor wherever specified. The cable shall be laid underground in excavated trench / prepared trench / hume pipes when laid outside the building. Cable shall be laid throught preapred trench / cable tray / duct / hume pipe / channel / floor trunks etc when laid inside the building as instructed by PMC/Site Incharge. The scope shall include: 1) Supply of Cables.(With Non Returnable Drums) 2) Delivery of the cables at site. 3) Unloading at site store. 4) Shifting of cable from site store to place of installation. 5) Connection of cable with proper tagging as specified ni specifications. 6) Supply & fixing of cable clamps, brackets, supports, route markers etc. where ever required to fix the cables safely. 7) Earthing the glands and armouring with earthing clamp and jumper and also connecting to common earth bar. 8) Testing of insulation and continuity of cable and submission of reports to the client's representative. 9) To prepare submission drawing and to take approval of consultant at each stage. 10) To prepare & submit as-built drawing and handing over document to end user. 11) Rate shall be inclusive of route markers at 15mtr intervals 12) Each run of cable to be tested with 1KV meggar 13) Proper cables tags of Aluminium shall be made and feeder shall be written. | |||||
| 5.00 | 3C x 16 Sq.mm. CU XLPE armored cable | 225 | Mtr | 1,566 ₹3.5 L | 1,565 ₹3.5 L |
| 6.00 | 3C x 10 Sq.mm. CU XLPE armored cable | 75 | Mtr | 1,050 ₹78,750 | 151 ₹11,325 |
| 7.00 | 3C x 6 Sq.mm. CU XLPE armored cable | 120 | Mtr | 650 ₹78,000 | 650 ₹78,000 |
| 8.00 | 3C x 4 Sq.mm. CU XLPE armored cable | 60 | Mtr | 470 ₹28,200 | 470 ₹28,200 |
| 9.00 | 3C x 2.5 Sq.mm. CU XLPE armored cable | 20 | Mtr | 335 ₹6,700 | 335 ₹6,700 |
| 10.00CABLE TERMINATION | |||||
Updated dates
Tender Value
₹38.0 L
EMD Value
₹76,000
Closing Date
12 Dec 2025, 3:00 pmClosed
PM BRIDCUL
BRIDCUL Opp Govt ITI Niranjanpur Saharanpur Road Dehradun
Electrical and Allied works for Rainshelter (A1 A2 and B1 to B5) at Mahasu Devta Hanol
2025_BRID3_89112_2
1231/BRIDCUL/233/25 Dated 10.11.2025
Open Tender
Electrical Works
365 days
Uttarkashi
Please refer Tender documents.
3 documents required · 3 mandatory
₹5,900
Project Manager, Project Unit Dehradun, BRIDCUL
₹76,000
BRIDCUL Dehradun
12 Feb 2026
24 Nov 2025
12 Dec 2025
24 Nov 2025
12 Dec 2025
2 Dec 2025
1 Dec 2025
MV CABLES
Laying of PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing RCC/ HUME/ METAL/DWC pipe as required.
Upto 35 sq. mm
Supply, connection, testing and commissioning of heavy duty, medium voltage, XLPE (IS 7098 - PART-II) insulated, Stranded AL / Cu conductor Armoured / Flexible cables as per specification & IS. The cable shall have outer sheeth of XLPE and inner sheath of PVC with stranded AL conductor wherever specified. The cable shall be laid underground in excavated trench / prepared trench / hume pipes when laid outside the building. Cable shall be laid throught preapred trench / cable tray / duct / hume pipe / channel / floor trunks etc when laid inside the building as instructed by PMC/Site Incharge. The scope shall include: 1) Supply of Cables.(With Non Returnable Drums) 2) Delivery of the cables at site. 3) Unloading at site store. 4) Shifting of cable from site store to place of installation. 5) Connection of cable with proper tagging as specified ni specifications. 6) Supply & fixing of cable clamps, brackets, supports, route markers etc. where ever required to fix the cables safely. 7) Earthing the glands and armouring with earthing clamp and jumper and also connecting to common earth bar. 8) Testing of insulation and continuity of cable and submission of reports to the client's representative. 9) To prepare submission drawing and to take approval of consultant at each stage. 10) To prepare & submit as-built drawing and handing over document to end user. 11) Rate shall be inclusive of route markers at 15mtr intervals 12) Each run of cable to be tested with 1KV meggar 13) Proper cables tags of Aluminium shall be made and feeder shall be written.
3C x 16 Sq.mm. CU XLPE armored cable
3C x 10 Sq.mm. CU XLPE armored cable
3C x 6 Sq.mm. CU XLPE armored cable
3C x 4 Sq.mm. CU XLPE armored cable
3C x 2.5 Sq.mm. CU XLPE armored cable
CABLE TERMINATION
Supplying and making end termination with brass compression gland and Copper lugs for following size of PVC insulated and PVC sheathed / XLPE copper conductor cable of 1.1 KV grade as required.
3C x 16 Sq.mm. CU XLPE armored cable
3C x 10 Sq.mm. CU XLPE armored cable
3C x 6 Sq.mm. CU XLPE armored cable
3C x 4 Sq.mm. CU XLPE armored cable
3C x 2.5 Sq.mm. CU XLPE armored cable
DISTRIBUTION BOARDS
Supplying and fixing DP sheet steel enclosure on surface/ recess along with 25/32 A 240 V "B" curve DP MCB complete with connections, testing and commissioning etc. as required.
POINT WIRING
Point wiring in PVC conduit, with modular type switch: Wiring for light point/ fan ponit/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface/ recessed medium class PVC conduit, with modular switch, modular plate, suitable Gl box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc.as required- Group C
Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 3 pin 5/6 amps modular socket outlet and 5/6 amps modular switch, onnection, painting etc. as required. (For light plugs to be used in non residential buildings).
Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 3 pin 5/6 & 15/16A amps modular socket outlet and 15/16 amps modular switch, onnection, painting etc. as required. (For light plugs to be used in non residential buildings).
Wiring for circuit/ submain wiring along with earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required.
2X1.5 sq. mm + 1 X 1.5 sq. mm earth wire
2 X 2.5 sq. mm + 1X2.5 sq. mm earth wire
2 X 4 sq. mm + 1 X 4 sq. mm earth wire
CONDUIT & OTHER
Supply, installation, testing and commissioning of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required.
LIGHT FIXTURES
Supply of Weather Proof Recessed false ceiling light Recessed Celiing Light - 10W,800lm,IP65,3000/4000K, Dimension 100X80mm, Height 80mm Diameter is 100mm, Weight is 0.5kg, Fixing Suitable for ceiling-mounted recessed installation. Fixture is made of Die Cast Aluminium, Powder Coated, LED is COB, Inbuilt driver, Input AC 240V, 50/60Hz * Colour of light fixture shall be BLACK as per Architectural requirements. * Contractor to submit samples for Approval before ordering the fixture.
DWC PIPES
Supplying and laying of following size DWC HDPE pipe ISI marked along with all accessories like socket, bend, couplers etc. conforming to IS 14930, Part II complete with fitting and cutting, jointing etc.direct in ground (75 cm below ground level) including excavation and refilling the trench but excluding sand cushioning and protective covering etc. , complete as required.
63 mm dia (OD-63 mm & ID-51 mm nominal)
120 mm dia (OD-120 mm & ID-103 mm nominal)
CCTV SYSTEM
Supply, installation, testing and commissioning of Cat6 cable.
Supply, Installation,testing and commissioning of 8Port POE Network Switch to provide Power and Data Communication for mentioned Camera. With 1 G SFP Module.
Supply, Installation, Testing & Commissiong of 5 MP IR Dome Camera 1/3″ Megapixel progressive scan Exmor CMOS, Infrared, Dome camera with D/N ICR, IR, varifocal lens, 2.8mm-12mm, F1.6, with Audio, H.264, IP66 rated 720p @ 25fps, H.264: 4–8192 kbps, BLC/HLC/DWDR, IR distance up to 30m, RJ-45 connection, Inbuilt microSD card slot, BLC/HLC/DWDR, 3D DNR, ROI, ONVIF, PoE Complete as per specification, IP66, IK10, Including necessary accessories for mounting * Colour of Camera shall be Black as per Architectural requirements. * Contractor to submit samples for Approval before ordering the fixture.
Supply, Installation, Testing and Commissioning of 6 single mode fiber optic cables (9/125 µm) with all necessary accessories to comply the installation.
Supply, Installation, Testing and Commissioning of 1 mtr. Cat 6 Patch cord.
Supply, Installation, Testing and Commissioning of 24 Port fully loaded patch panel
Supply, Installation, Testing and Commissioning of 24 LC Port Loaded LIU SM with all necessary accessories to comply the installation.
Supply, Installation, Testing and Commissioning of 12 LC Port Loaded LIU SM with all necessary accessories to comply the installation.
Supply, Installation, Testing and Commissioning of 06 LC Port Loaded LIU SM DinRail Type with all necessary accessories to comply the installation.
Supply, Installation, Testing and Commissioning of LC-LC SM Patch Cord 3 Mtr with all necessary accessories to comply the installation.
Supply, Installation, Testing and Commissioning of SC-LC SM Patch Cord 3 Mtr with all necessary accessories to comply the installation.
Supply, Installation, Testing and Commissioning of I/O User end and all necessary accessories to comply the installation.
Supply, Installation, Testing and Commissioning of Weather Proof Back Box for CCTV(120X120X75) with all necessary accessories to comply the installation.
PUBLIC ADDRESS
Supply, Installation, Testing and Laying of 2 Core X 1.5 Sq.mm FRLS PVC insulated Shielded Copper armoured cable with all required accessories.
Supply, Installation, Testing and Laying of 2 Core X 1.5 Sq.mm FRLS PVC insulated Shielded Copper unarmoured cable with all required accessories.
Ceiling mounted Weatherproof Speaker: Supply, Installation, Testing and Commissioning of 7.5W tapping Ceiling Speaker * Colour of Ceiling Speaker shall be Black as per Architectural requirements. * Contractor to submit samples for Approval before ordering the fixture.
stage.html
html • 0.03 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.16 MB
SBD_ELECTRAINSHELTER.pdf
Tender Documents • 1.78 MB
BOQ_105711.xls
BOQ • 0.31 MB
Download all tender documents and submit your bid