executive engineer kadodara division
Tender for work of Erection & Maintenance work of HT/LT line & TC and HT XLPE UG CABLE Work on ARC Basis for work under various scheme under KAMREJ RURAL S/dn under KADODARA Division ( Vav SS Area).
274061
KAD/O&M/EXP/N-Procure/2026/02/No.0106 date. 06-02-2026 SR. NO.02
Open
Electrical
Works
Surat
3 documents required · 3 mandatory
₹1,180
DAKSHIN GUJARAT VIJ COMPANY LTD.
₹40,000
7 Feb 2026
7 Feb 2026
7 Feb 2026
16 Feb 2026
7 Feb 2026
SCHEDULE B FOR Laying & commissioning of UG Cable with Erection &
Maintenance of HT ,LT & TC as per REC Norms under any sub division under Kadodara division
PART A LT /HT & O/H ERECTION
Sr. No. Item Code Item Unit FY 2024-25
HT TAPPING FROM THE EXISTING POLE INCLUDING FIXING OF CROSS ARMS, CLAMPS ANTI-CLIMBING
DEVICES, DANGER BOARD, INSULATORS ETC. COMPLETE AND PAINTING OF FABRICATED MATERIALS AND
NUMBERING COMPLETE WITH COST OF PAINTS AS PER STANDARD SPECIFICATION BUT EXCLUDING
ERECTION OF GUY SET AND EARTHING.
ERECTION OF PSC POLES OF 8 *200 KG INCLUDING EXCAVATION OF PIT AND REFILLING OF EARTH, FIXING
OFCROSS ARMS, TOP FITTING CLAMPS ANTI-CLIMBING DEVICES, INSULATORS ETC. COMPLETE AND
PAINTING OF FABRICATED MATERIALS USED ON THE POLES AND NUMBERING WITH COST OF PAINT AS
PER STANDARD SPECIFICATION BUT EXCLUDING ERECTION OF GUY SET AND EARTHING.
ERECTION OF STEEL POLES OF 9 TO 11 METERS INCLUDING EXCAVATION OF PIT AND REFILLING OF
EARTH, FIXING OFCROSS ARMS, TOP FITTING CLAMPS ANTI-CLIMBING DEVICES, DANGER BOARD,
3 9926000003 INSULATORS ETC. COMPLETE AND PAINTING OF STEEL POLE, FABRICATED MATERIALS USED ON THE No.
POLEAND NUMBERING WITH COST OF PAINT AS PER STANDARD SPECIFICATION BUT EXCLUDING
ERECTION OF GUY SET AND EARTHING.
ERECTION OF STEEL POLE OF 13 METERS FOR RAILWAY CROSSING ON BG/MG/NG LINE FOR 0.400/11/22KV
OVERHEAD LINES I.E INCLUDING EXCAVATION OF PIT & REFILLING OF EARTH, FIXING CROSS ARMS, TOP
4 9926000004 FITTING CLAMPS,ANTI-CLIMBING DEVICES DANGER BOARD, INSULATORS ETC. COMPLETE AND PAINTING No.
OF STEEL POLES, FABRICATED MATERIALS USED ON THE POLES AND NUMBERING WITH COSTOF PAINT
AS PER STANDARD SPECIFICATION BUT EXCLUDING ERECTION OF GUY SETS AND EARTHING.
ERECTION OF DOUBLE POLE STRUCTURE OF 8 METERS 200 KG PSC POLES INCLUDING EXCAVATION OF
PITS & REFILLING OF EARTHING, FIXING OF CHANNELS, SUPPORTING ANGLES,CLAMPS, ANTI-CLIMBING
5 9926000005 DEVICES DANGER BOARDS,INSULATORS ETC.COMPLETE AND PAINTING OF FABRICATED MATERIALS USED No.
ON THE POLES AND NUMBERING WITH COST OF PAINT AS PER STANDARD SPECIFICATION BUT
EXCLUDING ERECTION OF GUY SETS AND EARTHING.(WITHOUT AB SWITCH)
ERECTION OF DOUBLE POLE STRUCTURE OF 9 TO 11 METERS.STEEL POLE INCLUDING EXCAVATION OF
PITS & REFILLING OFEARTH, FIXING OF CHANNELS, SUPPORTING ANGLES, CLAMPS,ANTI-CLIMBING
6 9926000006 DEVICES DANGER BOARDS, INSULATORS ETC.COMPLETE & PAINTING OF POLES,FABRICATED No.
MATERIALSUSED ON THE POLES AND NUMBERING WITH COST OF PAINTSAS PER STANDARD
SPECIFICATION BUT EXCLUDING ERECTION OF GUY SET AND EARTHING.(WITHOUT AB SWITCH)
ERECTION OF DOUBLE POLE STRUCTURE WITH MOUNTING OF AB SWITCH, HG FUSES OF 8 MTRS 200 KG
PSC POLES INCLUDING EXCAVATION OF PITS AND REFILLING OF EARTH,FIXING OF CHANNELS
SUPPORTING ANGLES, CLAMPS, ANTI-CLIMBING DEVICES, DANGER BOARDS, INSULATORS,DOFUSES ETC.
COMPLETE AND PAINTING OF FABRICATED MATERIALS USED ON THE POLES AND NUMBERING WITH
COSTOF PAINT AS PER STANDARD SPECIFICATION BUT EXCLUDINGOF ERECTION OF GUY SET AND
EARTHING.(WITH AB SWITCH)
ERECTION OF DOUBLE POLE STRUCTURE WITH MOUNTING OF AB SWITCH,HG FUSES, 9 TO 11 METERS
STEEL POLES INCLUDING EXCAVATION OF PITS AND REFILLING OF EARTH, FIXING OFCHANNEL,
SUPPORTING ANGLES, CLAMPS, ANTI-CLIMBING DEVICES , DANGER BOARDS, INSULATORS, ETC.
COMPLETE AND PAINTING OF POLES FABRICATED MATERIALS USED ON THE POLES AND NUMBERING
WITH COST OF PAINT AS PER STANDARD SPECIFICATION BUT EXCLUDING ERECTION OF GUY SET AND
EARTHING.(WITH AB SWITCH)
ERECTION OF DOUBLE POLE STRUCTURES WITH MOUNTING OFAB SWITCH, HG FUSES, TRANSFORMERS,
LIGHTENING ARRESTORS, DISTRIBUTION BOX. OF 8 METER,200KG PSC POLE METERS POLES INCLUDING
EXCAVATION OF PITS AND REFILLING OF EARTH, CARTING OF TRANSFORMERS FROMSTORES TO SITE,
9 9926000009 FIXING OF CHANNELS, SUPPORTING ANGLES,BRACINGS CROSS ARMS CLAMPS, ANTICLIMBING DEVICES No.
DANGER BOARDS, CONDUCTOR AND CABLE WIRING ETC.COMPLETE AND PAINTING OF FABRICATED
MATERIALS USEDON THE POLES AND NUMBERING WITH COST OF PAINT AS PER STANDARD
SPECIFICATION BUT EXCLUDING ERECTION OF GUY SETS AND EARTHING.
ERECTION OF DOUBLE POLE STRUCTURE WITH MOUNTING OF AB SWITCH,HG FUSES TRANSFORMERS,
LIGHTENING ARRESTORS, DISTRIBUTION BOX 9 TO 11 METERS STEEL POLES INCLUDING EXCAVATION OF
PITS & REFILLING OF EARTH CARTING OF TRANSFORMERS FROM STORE TO SITE, FIXINGOF CHANNELS
10 9926000010 SUPPORTING ANGLES, BRACING, CROSS ARMS,CLAMPS, ANTICLIMBING DEVICES, DANGER No.
BOARDS,CONDUCTOR AND CABLE WIRING ETC. COMPLETE AND PAINTING OF POLES FABRICATED
MATERIALS USED ON THE POLES AND NUMBERING AS PER STANDARD SPECIFICATION BUT EXCLUDING
ERECTIONS OF GUY SETS AND EARTHING.
ERECTION OF GUY SET INCLUDING EXCAVATION OF PITS & REFILLING OF EARTH AS PER STANDARD
11 9926000011 SPECIFICATION WITH STAY CLAMPS, STAY WIRE, ANCHOR ROD, TURN BUCKLE, EYEBOLT, GUY No.
INSULATOR, CEMENT CONCRETE BLOCK ETC. BUT EXCLUDING CONCRETING.
CONCRETING OF POLES, GUYS, ETC. INCLUDING COST OF CEMENT SAND METAL (1:2:4) AND WATER ETC.
AS PER STANDARD SPECIFICATION.(cement Should be 53 grade) used for Concreting.
ERECTION OF COIL TYPE EARTHING INCLUDING COST OF COAL,SALT ETC. BUT WITHOUT COST OF GI
WIRE AS PER STANDARD SPECIFICATION(20kg solt+20kg coal)
ERECTION OF GI PIPE/CI PLATE TYPE EARTHING INCLUDINGCOST OF COAL SALT ETC. BUT WITHOUT COST
OF PIPE/GIPLATE GI WIRE AS PER STANDARD SPECIFICATION.(20kg solt+20kg coal)
ERECTION OF STREET LIGHT FIXTURE COMPLETE WITH CLAMPS, BRASS NIPPLE, BRASS HOLDER TECK
15 9926000015 WOOD BUSH,REFLECTORS FUSE, WIRING ETC. AS PER STANDARD SPECIFICATION BUT EXCLUDING COST No.
STRINGING OF(30mm2)ACSR/34MM@,55MM2 AAA CONDUCTOR for ALL TYPE OF CONDUCTOR (EXCEPT ONE COND
DOG CONDUCTOR) FOR 11/22KV & LT LINES INCLUDING FIXING OF INSULATORS, BINDING JUMPERING ETC. PER KM
17 9926000017 STRINGING OF GI WIRE 8 SWG INCLUDING BINDING JUMPERING ETC. DO
PROVIDING SINGLE PHASE SERVICE CONNECTION WITH PVC 2.5/4MM2 TWIN CORE CABLE FROM TERMINAL
18 9926000018 POLE TO METERING POINT INCLUDING FIXING OF METER WITH METER EARTHING COMPLETE WORK AS No.
PER STANDARD SPECIFICATION BUT EXCLUDING COST OF MATERIALS.
PROVIDING THREE PHASE 4 WIRE SERVICE CONNECTION WITH PVC 4MM2/10MM2 FOUR CORE CABLE
19 9926000019 FROM TERMINAL POLE TO METERING POINT INCLUDING FIXING OF METER WITH METER EARTHING No.
COMPLETE WORK AS PER STANDARD SPECIFICATION BUT EXCLUDING COST OF MATERIALS.
ADDITIONAL COST FOR EXCAVATION OF PIT IN HARD ROCK AREA FOR ERECTION OF POLE/ GUY ETC. AS
PER STANDARD SPECIFICATION OVER & ABOVE NORMAL COST COVERED AGAINST EXCAVATION OF PIT
UNDER NORMAL SOIL FOR ERECTION OF POLE,GUY, DOUBLE POLE STRUCTURE EARTHING WITH THE
APPROVAL OF SUPDT.ENGINEER.
21 9926000021 PROVIDING GUARDING TO HT LINE ON ROAD/ RAIL CROSSING. MTR
22 9926000022 PROVIDING GUARDING OF LT LINES ON ROAD/RAIL CROSSING. MTR
23 9926000023 LT LINE TAPPING- SINGLE PHASE No.
24 9926000024 LT LINE TAPPING- THREE PHASE No.
Stringing/LAYING OF OVER HEAD LT CABLE FOR ROAD CROSSING,HT LINE CROSSING AND TELEPHONE LINE
CROSSING ETC.(PER SPAN)
ERECTION OF SINGLE POLE STRUCTURES WITH , HG FUSES,TRANSFORMERS, LIGHTENING ARRESTOR,
DISTRIBUTION BOX. ON 8 METERS 200 KGAND PSC POLE INCLUDING EXCAVATION OF PITS AND REFILLING
OF EARTH, CARTING OF TRANSFORMERS FROM STORES TO SITE, FIXING OF CHANNELS, SUPPORTING
26 9926000026 ANGLES,BRACINGS CROSS ARMS CLAMPS, ANTICLIMBING DEVICES DANGER BOARDS, CONDUCTOR AND No.
CABLE WIRING ETC.COMPLETE AND PAINTING OF FABRICATED MATERIALS USED ON THE POLE AND
NUMBERING WITH COST OF PAINT AS PER STANDARD SPECIFICATION BUT EXCLUDING ERECTION OFGUY
SETS AND EARTHING.
ERECTION OF SINGLE POLE STRUCTURES WITH MOUNTING OFAB SWITCH , HG FUSES,TRANSFORMERS,
LIGHTENINGARRESTOR, DISTRIBUTION BOX. ON 9 to 11 METERS RSJ POLE INCLUDING EXCAVATION OF
PITS AND REFILLING OF EARTH, CARTING OF TRANSFORMERS FROM STORES TO SITE, FIXING OF
27 9926000027 CHANNELS, SUPPORTING ANGLES,BRACINGS CROSS ARMS CLAMPS, ANTICLIMBING DEVICES DANGER No.
BOARDS, CONDUCTOR AND CABLE WIRING ETC.COMPLETE AND PAINTING OF FABRICATED MATERIALS
USED ON THE POLE AND NUMBERING WITH COST OF PAINT AS PER STANDARD SPECIFICATION BUT
EXCLUDING ERECTION OFGUY SETS AND EARTHING.
ERECTION OF PSC POLES OF 10 *270 KG INCLUDING EXCAVATION OF PIT AND REFILLING OF EARTH,
FIXING OF CROSS ARMS, TOP FITTING CLAMPS ANTI-CLIMBING DEVICES, INSULATORS ETC. COMPLETE
AND PAINTING OF FABRICATED MATERIALS USED ON THE POLES AND NUMBERING WITH COST OF PAINT
AS PER STANDARD SPECIFICATION BUT EXCLUDING ERECTION OF GUY SET AND EARTHING.
ERECTION OF DOUBLE POLE STRUCTURE OF 10 METERS 270 KG PSC POLES INCLUDING EXCAVATION OF
PITS & REFILLING OF EARTHING, FIXING OF CHANNELS, SUPPORTING ANGLES,CLAMPS, ANTI-CLIMBING
29 9926000029 DEVICES DANGER BOARDS,INSULATORS ETC.COMPLETE AND PAINTING OF FABRICATED MATERIALS USED No.
ON THE POLES AND NUMBERING WITH COST OF PAINT AS PER STANDARD SPECIFICATION BUT
EXCLUDING ERECTION OF GUY SETS AND EARTHING.(WITHOUT AB SWITCH)
STRINGING OF 100MM2 ACSR/100MM2 AAAC CONDUCTOR FOR 11/22KV & LT LINES INCLUDING FIXING ONE COND
OFINSULATORS, BINDING JUMPERING ETC. PER KM
STRINGING OF DOG CONDUCTOR FOR 11/22KV & HT LINES INCLUDING FIXING OF INSULATORS, BINDING ONE COND
JUMPERING ETC. PER KM
ERECTION OF DOUBLE POLE STRUCTURES WITH MOUNTING OF AB SWITCH, HG FUSES, TRANSFORMERS,
LIGHTENING ARRESTORS, DISTRIBUTION BOX. OF 10 METERS 270 KGAND PSC POLES INCLUDING
EXCAVATION OF PITS AND REFILLING OF EARTH, CARTING OF TRANSFORMERS FROMSTORES TO SITE,
32 9926000032 FIXING OF CHANNELS, SUPPORTING ANGLES,BRACINGS CROSS ARMS CLAMPS, ANTI-CLIMBING No.
DEVICES,DANGER BOARDS, CONDUCTOR AND CABLE WIRING ETC.COMPLETE AND PAINTING OF
FABRICATED MATERIALS USED ON THE POLES AND NUMBERING WITH COST OF PAINT AS PER STANDARD
SPECIFICATION BUT EXCLUDING ERECTION OF GUY SETS AND EARTHING.
DISMENTALLING OF 8 MTR PSC POLE WITH CREDITING OF FABRICATION AT STORE & STACKING OF POLE
SAFELY ON ROAD SIDE OR CREDITING TO DEPARTMENTAL STORE
DISMENTALLING OF 10 MTR PSC POLE WITH CREDITING OF FABRICATION AT STORE & STACKING OF POLE
SAFELY ON ROAD SIDE OR CREDITING TO DEPARTMENTAL STORE
DISMENTALLING OF TRANSFORMER CENTRE (8 MTR PSC POLE) (WITH TRANSFORMER) WITH CREDITING
35 9926000035 OF FABRICATION & TRANSFORMER AT STORE & STACKING OF POLE SAFELY ON ROAD SIDE OR CREDITING No.
TO DEPARTMENTAL STORE
DISMENTALLING OF TRANSFORMER CENTRE (8 MTR PSC POLE) (WITHOUT TRANSFORMER) WITH
36 9926000036 CREDITING OF FABRICATION AT STORE & STACKING OF POLE SAFELY ON ROAD SIDE OR CREDITING TO No.
DEPARTMENTAL STORE
STRINGING OF LT ABC OF 1*35 SQ MM + 1*25 SQ MM INCLUDING FITTING OF ALL ACESSARIES I.E. SPECIAL
DESIGN SUSPENSION / TENSION CLAMP, FIXING OF CROSS ARM, LT SHACKLE INSULATOR ETC. FOR FIXING
37 9926000037 OF MESSENGER WIRE AND TO PROVIDE SERVICE CONNECTION ON AERIAL BUNCH CABLE BY INSULATED KM
PIERCEING CONNECTORS THROUGH SERVICE CONNECTION BOX COMPLETE AS REQUIRED & DIRECTED
BY ENGINEER IN CHARGE.
STRINGING OF LT ABC OF 3*50 SQ MM +1*25 SQ MM+1*35 SQ MM INCLUDING FITTING OF ALL ACESSARIES
I.E. SPECIAL DESIGN SUSPENSION / TENSION CLAMP, FIXING OF CROSS ARM, LT SHACKLE INSULATOR
38 9926000038 ETC. FOR FIXING OF MESSENGER WIRE AND TO PROVIDE SERVICE CONNECTION ON AERIAL BUNCH KM
CABLE BY INSULATED PIERCEING CONNECTORS THROUGH SERVICE CONNECTION BOX COMPLETE AS
REQUIRED & DIRECTED BY ENGINEER IN CHARGE.
STRINGING OF 11KV ABC OF 3*95 SQ MM +80 SQ MM INCLUDING FITTING OF ALL ACESSARIES I.E. SPECIAL
39 9926000039 DESIGN SUSPENSION / TENSION CLAMP, FIXING OF CROSS ARM, BINDING TO PIN INSULATOR,PREPARING KM
SHACKLE POINT,JUMPERS ETC. AS REQUIRED & DIRECTED BY ENGINEER IN CHARGE
STRINGING OF 22 KV ABC OF 3*70 SQ MM +95 SQ MM INCLUDING FITTING OF ALL ACESSARIES I.E. SPECIAL
40 9926000040 DESIGN SUSPENSION / TENSION CLAMP, FIXING OF CROSS ARM, BINDING TO PIN INSULATOR,PREPARING KM
SHACKLE POINT,JUMPERS ETC. AS REQUIRED AND DIRECTED BY ENGINEER IN CHARGE
STRINGING OF LT ABC OF 2*50 SQ MM +1*25 SQ MM+ 35 SQ MM INCLUDING FITTING OF ALL ACESSARIES
I.E. SPECIAL DESIGN SUSPENSION / TENSION CLAMP, FIXING OF CROSS ARM, LT SHACKLE INSULATOR
41 9926000041 ETC. FOR FIXING OF MESSENGER WIRE AND TO PROVIDE SERVICE CONNECTION ON AERIAL BUNCH KM
CABLE BY INSULATED PIERCEING CONNECTORS THROUGH SERVICE CONNECTION BOX COMPLETE AS
REQUIRED & DIRECTED BY ENGINEER IN CHARGE.
42 9926000042 DISMENTALING OF RSJ (9/11 METER) POLE AND CREDITING THE OLD MATERIAL TO STORE No.
DISMENTALING OF TRANSFORMER CENTER ON 10MTR,270KG PSC POLE(WITHOUT TRANSFORMER) WITH
43 9926000043 CREDITING OF FABRICATION AT STORE AND STACKING OF POLE SAFELY ON ROAD SIDE OR CREDITING TO No.
DEPARTMENTAL STORE
DISMENTALING OF TRANSFORMER CENTER ON 10MTR,270KG PSC POLE(WITH TRANSFORMER) WITH
44 9926000044 CREDITING OF FABRICATION AT STORE AND STACKING OF POLE SAFELY ON ROAD SIDE OR CREDITING TO No.
DEPARTMENTAL STORE
DISMENTLING OF 11KV ABC OF 3*95 SQ MM +80 SQ MM AND CREDITING FITTING OF ALL ACESSARIES AND
FABRICATION TO DEPARTMENTAL STORE
DISMENTLING OF 22 KV ABC OF 3*70 SQ MM +95 SQ MM AND CREDITING FITTING OF ALL ACESSARIES
AND FABRICATION TO DEPARTMENTAL STORE
DISMENTALING OF LT ABC OF 1*35 SQ MM + 1*25 SQ MM AND CREDITING FITTING OF ALL ACESSARIES TO
DEPARTMENTAL STORE.
DISMENTALING OF LT ABC OF 3*50 SQ MM +1*25 SQ MM+1*35 SQ MM AND CREDITING FITTING OF ALL
ACESSARIES TO DEPARTMENTAL STORE.
DISMENTALING OF LT ABC OF 2*50 SQ MM +1*25 SQ MM+ 35 SQ MM AND CREDITING FITTING OF ALL
ACESSARIES TO DEPARTMENTAL STORE.
RESTRINGING OF ALL TYPE OF CONDUCTOR (EXCEPT DOG CONDUCTOR) FOR 11/22KV & LT LINES ONE COND
INCLUDING FIXING OF INSULATORS, BINDING JUMPERING ETC. PER KM
51 9926000051 RESTRINGING OF DOG CONDUCTOR FOR 11/22KV HT LINES INCLUDING , BINDING JUMPERING ETC.
52 9926000052 LABOUR CHARGE FOR THE INSTALLATION OF NEW DTR METER. (METER WILL BE PROVIDED BY DGVCL) No.
LABOUR CHARGE FOR THE REPLACEMENT OF DTR METER AND OLD METER SHOULD BE CREDITED TO SDN
STORE. (METER WILL BE PROVIDED BY DGVCL)
LABOUR CHARGE FOR PROVIDING CT COIL FOR DTR METER CONNECTION. (CT COIL WILL BE PROVIDED
LABOUR CHARGE FOR REPLACEMENT OF CT COIL FOR DTR METER CONNECTION AND OLD CT SHOULD BE
CREDITED TO SDN STORE. (CT COIL WILL BE PROVIDED BY DGVCL)
56 9926000056 LABOUR CHARGE FOR FIXING OF MMB FOR DTR METER (MMB WILL BE PROVIDED BY DGVCL) No.
57 9926000057 LABOUR CHARGE FOR REPLACEMENT OF DTR METER BOX. (METER WILL BE PROVIDED BY DGVCL) No.
PROVIDING / REPLACEMENT OF 1.5 SQ MM 10 CORE COPPER CABLE 3.5 METER (CABLE TO BE PROVIDED
LABOUR CHARGE FOR PROVIDING/RECONNECTION OF TERMINAL CONNECTION WITH PROPER SIZE OF
59 9926000059 TERMINATI
LUGS. (LUGS COST IS BORNE BY AGENCY)
LABOUR CHARGE FOR THE SPOT READING OF DTR METER WITH DETAIL SURVEY OF DEFECT IF ANY. A
DULY SIGN COPY BY SURVEYOR PERSON OF AGENCY IN PRO-FORMA REPORT SHOULD BE SUBMITTED TO
SDN OFFICE.(* ONLY IF ALL PARAMETER OF VOLTAGE, CURRENT & LOAD AS SHOWN IN PER-FORMA IS
FILLED) AS PER THE INSTRUCTION OF ENGINEER IN-CHARGE.
LABOUR CHARGE FOR THE SPOT READING OF DTR METER WITH DETAIL SURVEY OF DEFECT IF ANY. A
DULY SIGN COPY BY SURVEYOR PERSON OF AGENCY IN PRO-FORMA REPORT SHOULD BE SUBMITTED TO
SDN OFFICE. (DULY FILL PER-FORMA IN FAULT CONDITION IN WHICH READING PARAMETER IS NOT SHOWN
INSTALLATION OF DTR METER INCLUDING METER BOX, PROVIDING & FIXING OF 1.5SQ MM SINGLE STRAND
62 9926000062 10 CORE ARMOURED COPPER CABLE (3.5METER), TERMINATION IN METER & COIL ETC.(METER, METER No.
BOX, C.T./P.T. COIL WILL BE PROVIDED BY DGVCL)
INSTALLATION OF DTR METER INCLUDING METER BOX, TERMINATION IN METER & COIL ETC. (WITHOUT
10CORE COPPER CABLE) (METER, METER BOX, C.T./P.T. COIL WILL BE PROVIDED BY DGVCL)
Binding of messanger Conductorat with a distance not more than 0.75 mtr with 6 turns minimum on XLPE Cable with
single strand binding wire (including cost of binding wire)
Supply and Installation of 11/22 kV Distribution Transformers HT Terminal protector (UV Resistance) with using
95/120/150 sq.mm long barrel aluminum lug. (1Set = 3 Nos i.e. on R, Y, B)
Supply & Installation of HT EPR Tap on 11/22 kV Distribution Transformer with replacement of bare conductor by HT
66 9926000087 ABC conductor (DO bottom side to transformer) after removal of semi conductor by HT ABC (6 inch both side). HT ABC PER SET
to be supplied by DGVCL. (1Set = 3 Nos i.e. on R, Y, B)
Supply, Installation, Testing and Commissioning of Maintenance Free, Ready Capsule, Pipe-In-Cage (Pic) Type, Earth
67 9926000088 Electrodes for HT Feeder Pole Having 2000 mm Electrode Length as per the Tender Specifications and Drawing. (All NO
Materials Will Be Supplied By Agency)
Supply, Installation, Testing and Commissioning of Maintenance Free, Ready Capsule, Pipe-In-Cage (Pic) Type, Earth
68 9926000089 Electrodes for HT Feeder Pole Having 3000 mm Electrode Length as per the Tender Specifications And Drawing. (All NO
Materials Will Be Supplied By Agency)
Supply and Installation of 25 X 3 mm GI Strip having hot dip- galvanized-zinc coating of 80-100 microns without any
joints or welding. Both the end of the GI strip should be connected with GI nut bolts and required fabrication work for
giving separate earthing connections to
(1) Neutral of the transformer
(2) MS structures of the transformer center (Approximately 25 meter GI strip per transformer centre
- as per requirement and instruction of Engineer in- charge) (All Materials will be supplied by Agency)
Supply and Installation of uPVC standard make Pipe of 1.25" diameter for covering GI strip with UV protected Cable
70 9926000092 Ties of 550 X 7.6 mm size to bind with pole face(Approximately 25 meter uPVC pipe for GI strip covering per Meter
transformer centre -as per requirement and instruction of Engineer in-charge.
Supply & fixing of upto 33 kV Conductor sleeve for Busbar to Drop out Fuse and Drop out fuse to Transformer H.T.
including Busbar (12 mm sleeve) as per technical specification. (All Materials will be supplied by Agency)
Supply & fixing of upto 33 kV Conductor sleeve for Busbar to Drop out Fuse and Drop out fuse to Transformer H.T.
without Busbar (12 mm sleeve) as per technical specification. (All Materials will be supplied by Agency)
Supply & fixing of upto 33 kV Conductor sleeve for Busbar to Drop out Fuse and Drop out fuse to Transformer H.T.
including Busbar(15 mm sleeve) as per technical specification. (All Materials will be supplied by Agency)
Supply & fixing of upto 33 kV Conductor sleeve for Busbar to Drop out Fuse and Drop out fuse to Transformer H.T.
without Busbar(15 mm sleeve) as per technical specification. (All Materials will be supplied by Agency)
Supply & fixing of Disc type Red Color FRP(Non-flammable) material with Weather resistant, Non-conductive bird guard
75 9926000095 OD=300 MM, ID=33 MM, Width =1.25 MM, one side cut from ID to OD. (All Materials will be supplied by Agency) NO
Providing and fixing of LT Terminal protectors i.e. Re-useable boot (LT Side 1.1 kV) including LT (1.1 kV) insulating
taps. All live part at LT side shall be covered with fixing of LT insulating taps.
77 Nylon Net around Transformer Center
77.1 9926000097 Nylon Net (12 * 15 ft) Per Net
77.2 9926000098 Nylon Dori Per TC
77.3 9926000099 Labour charge for fitting Nylon Net (All fabricated material for fitting nylon net shall be provided by DGVCL) Per TC
1. DGVCL will provide key material like M.S. materials,ABC/Bare conductors,PSC/RSJ Poles,Insulators,Fabricated
materials etc. to the contractor.
2.All fabricated items shall be fabricated as per DGVCL approved drawing and by welding rods confirming to the
relevent ISI specification and as directed by Engineer in charge.
3.Necessary electricity connection for fabrictated items shall be provided by DGVCL on payment of required charge for
connection & electricity bill of the same shall be paid by the agency.
4.All the rates are inclusive of PF and Exclusive of GST applicable time to time.
5.All steel material are to be painted as below:
(a) Scrubbing of rusted surface properly before applying the paints on to the RSJ poles & steel fabricated materials of
RSJ/PSC poles is must required.
(b) Two coats of approved ISI mark red oxide (primer) is to be properly painted for the RSJ poles & steel fabricated
materials of RSJ/PSC poles.
(c) Two coats of approved ISI mark silver paint (i.e. triple mangoes or equivalent quality silver paint) is to be properly
painted on to the RSJ poles & steel fabricated materials of RSJ/PSC poles.
78 9924000001 Cutting of Tree branches surounding HT/LT line Per Tree
79 9924000002 Replacement of old jumpers & providing new double jumpers with 8" binding [D Type] & capsuling with PVC pipe etc No.
80 9924000005 Support pole for Stay PSC/STP/RSJ No.
81 9924000006 Pin binding of conductor 11/22kv Pin insulator No.
82 9924000007 Pin binding of conductor 11/22kv Pin insulator per pole in costle area with cleaning . No.
83 9924000008 Pin binding of conductor LT shakel insulator No.
84 9924000009 Replacement of one/both disc.insulator at strain pole No.
85 9924000010 Replacement of LT shackle insulator at cut point No.
86 9924000011 Refixing of V cross Arm No.
87 9924000012 Replacement of V cross Arm (With Transportation & Painting) No.
88 9924000013 Refixing of Top fitting in proper position No.
89 9924000014 Replacement of Top fitting No.
90 9924000015 Replacement of LT cross Arm No.
91 9924000016 Providing DO fuse on DP with carting & jumpuring(ONE DO FUSE) No.
Numburing of pole with paint by preparing back ground of one colour and have lettering(height 3" * width 0.5") using
93 9924000018 Fixing of MMB(1PH.) at consumer end No.
94 9924000019 Fixing of MMB(3PH.) at consumer end No.
95 9924000020 Replacement of (1ph.) meter for Urban area No.
96 9924000021 Replacement of (1ph.) meter for Rural area No.
97 9924000022 painting consumer no. on MMB (Urban) (with letter size height 40mm* width 8mm) No.
98 9924000023 painting consumer no. on MMB (Rural) (with letter size height 40mm* width 8mm) No.
99 9924000024 Replacement of deteriorated Single phase Service line No.
100 9924000025 Fixing of new dist. Box with complete wiring including clamps,nut bolts etc. No.
101 9924000026 Reparing of guarding involving reshaping of bearer wire cross lacing binding etc. R Mtr.
102 9924000027 Painting of steel fabricated material of RSJ DO DP structure with paint No.
103 9924000028 Painting of steel fabricated material of RSJ pole mounted transformer double pole structure with paint No.
104 9924000029 Painting of steel fabricated material of RSJ single pole with paint No.
105 9924000030 painting of steel fabricated material of PSC Single pole (HT line) with paint No.
106 9924000031 painting of steel fabricated material of PSC DO DP double pole with paint No.
107 9924000032 painting of steel fabricated material of PSC double pole at pole mounted transformer with paint No.
108 9924000033 Providing line seperater single phase No.
109 9924000034 Providing line seperater three phase No.
110 9924000035 Replacement / Providing of stay insulator along with adjustment of tension in stay wire No.
111 9924000036 Replacement of deteriorated /providing LT dist. Box with new up to 100KVA capacity & crediting it to store. No.
112 9924000037 Replacement of deteriorated /providing LT dist. Box with new above 100KVA capacity & crediting it to store. No.
113 9924000038 Adjustment of tension in stay wire No.
114 9924000039 Refitting of LA No.
115 9924000040 Converting pin point to Shackle point including dismentaling & restringing etc. location
116 9924000041 replacement of 11KV Pin insulator with providing new double pin binding No.
117 9924000042 replacement of 22KV Pin insulator by new 11kv pin insulator with spares & providing new double pin binding No.
118 9924000043 Providing 11kv double disc insulators with binding & restringing No.
119 9924000045 Replacement of existing 11kv conductor (all size) with new double pin binding Cond/KM
120 9924000046 Plumbing of PSC Pole with straightening at pin point No.
121 9924000047 Plumbing of PSC Pole with straightening at tension point No.
122 9924000048 Plumbing of tilted DP structure (PSC/RSJ/STP) with refilling of stone Murrum etc. No.
123 9924000049 Providing new 11kv AB /GO switch with fabrication and insulated colour code jumper, binding, lugs etc Set
124 9924000051 Replacement of old 11kv AB /GO switch with providing new insulated jumper, binding, lugs etc Set
125 9924000052 Providing cage type loop guard in verticle LT line with using PVC reel insulators etc per pole
126 9924000053 Labour charges for replacement /providing of MMB & service with all accessories for three phase connection No.
127 9924000054 Labour charges for replacement /providing of MMB & service with all accessories for single phase connection No.
Dismentalling of existing Dist.X'mer center(RSJ /STP POLE) 25/63/100/200 KVA with all fabrication & creditig the old
material to store
Disconnection from LT pole 1 phase
Reconnection from LT pole 1 phase
( payment after receipt of R/C charges)
131 9924000058 Disconnection from LT pole 3 phase No.
Reconnection from LT pole 3 phase
( payment after receipt of R/C charges)
133 9924000060 Dismentaling & removing of service line from pole & crediting to S/dn (1 ph.) No.
134 9924000061 Dismentaling & removing of service line from pole & crediting to S/dn (3 ph.) No.
135 9924000062 Reconnection of service line complete with PVC cable (1 Ph) No.
136 9924000063 Reconnection of service line complete with PVC cable (3 Ph) No.
Providing spiral type earthing by G.I. NO 8(weight 2kg -5mtr in length) with salt and coal 10kg each, including pvc rigid
137 9924000064 pipe 20mm dia( 1.5mtr length) to pass exposed part of G.I. wire at consumer end with all materials, earth resistance No.
should be less than 2 ohms
Providing and fixing of signle core 1.5 sq mm single strand copper insulated cable with cable nail clip for spiral type
earthing at consumer end. The end of G.I. no 8 is to be connected by connector with copper cable of which other end
138 9924000070 per meter
shall be connected to the earth terminal of meter box. This item shall be used in location where there is more distance
between earth terminal and earthing terminal of meter. (All materials supplied by contractor)
PART B: UG WORK
Sr. No. Item Code Description Unit FY 2024-25
Labour charge for excavation of cable trench of 400mm width x 1200mm depth, in any type of soil for laying of cable of
1 9925000001 size up to 240 mm2 (For additional cable 200 mm additional width shall be considered i.e. half trench length is to be Meter
Labour charge for excavation of cable trench of 600mm width x 1200mm depth, in any type of soil for laying of cable of
2 9925000002 size up to 240 mm2 (For additional cable 200 mm additional width shall be considered i.e. half trench length is to be Meter
Labour charge for excavation of cable trench of 400mm width x 1500mm depth, in any type of soil for laying of cable of
3 9925000003 size up to 240 mm2 (For additional cable 200 mm additional width shall be considered i.e. half trench length is to be Meter
Labour charge for laying of 11kV / 22 kV XLPE Cable of size up to 240 mm2 & preparation of sand layer 100mm thick,
in the cable trench & covering the cable with 150 mm dia (Inner), thickness 25 mm, 1.0 meter long RCC half round
muffs and providing and fixing of 4inch width yellow colour polyethylene tape with printing "CAUTION ELECTRIC
CABLE BELOW" at 0.75 m depth from ground surface after laying cable in trench. This will provide indication that
electric cable is passing underground so as to protect cable from mechnical injuries, refilling the same, as per
Instruction of Engineer in Charge (EIC).
Labour charge for horizontal drilling using Auger machine without damage to surface road at max 2.0 mtrs depth &
putting of 6.11 kg/cm2 , class-4,Green color, 110mm O.D. , 8.5mm thickness H.D.P.E. pipe confirms to IS 4984-
1987(3rd revision) and BIS certification and laying of 11KV/22KV XLPE cable of size up to 240 mm2 in HDPE pipe, as
per Site Condition (excluding cost of pipe). The detail map obtained from HDD machine and excell sheet(hard and soft
copy) indicating the respective depth and distance from adjacent landmark for each segment for HDD is must required
to be submitted. HDD to be carried out at depth 1.5 mtrs to 2.0 mtrs as per site conditions and as per instruction of EIC.
Labour charge for horizontal drilling manually without damage to surface road at max 2.0 mtrs depth & putting of
kg/cm2 , class-4,Green color, 110mm O.D. , 8.5mm thickness H.D.P.E. pipe confirms to IS 4984-1987(3rd revision)
and BIS certification and laying of 11KV/22KV XLPE cable of size up to 240 mm2 size, as per Site Condition (excluding
cost of pipe). The detail map and excell sheet(hard and soft copy) indicating the respective depth and distance from
adjacent landmark for each segment of cable to be submitted. Drilling to be carried out at depth Minimum 1.2 mtrs to
2.0 mtrs as per site conditions as per instruction of EIC.
Supply of 6.11kg/cm2 , class-4,Green color, 110mm O.D. , 8.5 mm thickness H.D.P.E. pipe confirms to IS 4984 and
BIS certification for laying of underground 11KV / 22KV XLPE cable up to 240 mm2 size.
Labour work for RCC concreting on disputed location and repairing of damage portion of road crossing for the work
carried out for roads crossing as well as concreting & muffing of ploes including all materials (1:2:4)
Providing & fixing concrete stone route marker of 300 mm width x 150 mm thick x 650 mm height embedded in earth
at least 300 mm below & 350 mm above ground level respectively at distance approx 50 meters along the length of
cable. The RCC concreting (1:2:4)(all necessary maeterials will be in bidder's scope) of route marker is to be carried out
9 9925000009 300 mm width x 150 mm thick x 300 mm below ground level as per instruction of EIC. The route marker should be No.
with name of company with approved yellow colour-DGVCL. The distance from marker to cable and cable depth with
feeder name etc., marked with arrow sign is to be painted on it.The route marker is to be fixed at location near to any
fixed permanent location (not necessary to fix exact on top of cable) as per instruction of EIC.
Erection of D.P. (double pole) structure using 9 / 11 Mtr. RSJ pole with cable connection arrangement along with
10 9925000010 fitting of necessary fabrication for 11KV cable including excavation of pit & refilling of earth as per instruction of EIC. No.
(Exclusive of concreting & muffing of poles)
Erection of Single pole structure using 9 / 11 Mtr RSJ pole with cable connection arrangement along with fitting
11 9925000011 ofnecessary fabrication for 11KV/22 KV cable including excavation of pit & refilling of earth as per instruction of EIC. No.
(Exclusive of concreting & muffing of poles)
Erection of D.P. (double pole) structure using 8.0 Mtr. PSC pole with cable connection arrangement along with fitting
12 9925000012 of necessary fabrication for 11KV cable including excavation of pit & refilling of earth as per instruction of EIC. (Exclusive No.
of concreting & muffing of poles)
Erection of Single pole structure using 8.0 Mtr PSC pole with cable connection arrangement along with fitting
13 9925000013 ofnecessary fabrication for 11KV/22 KV cable including excavation of pit & refilling of earth as per instruction of EIC. No.
(Exclusive of concreting & muffing of poles)
Labour charge for erecting of 11kV / 22 kV XLPE cable of size up to 240 mm2 on DP Structure with fixing of
14 9925000014 Nos polymer cleats on top and middle part.Polymer cleats, nut bolts etc. fixing material to be provided by Per Job
Providing & fixing of 6.11kg/cm2 , class-4,Green color, 110mm O.D. , 8.5mm thickness H.D.P.E. pipe confirms to
IS 4984 and BIS certification on the erected DP structure for the mechanical protection of cable by inserting the
15 9925000015 cable inside HDPE pipe. The HDPE pipe shall be erected in such a way that 300mm shall be below the ground level and Per Job
the rest 2700 mm shall be supported on the DP Structure with 01 No Polymer cleat.All materials including polymer
cleat and Nut bolt to be provided by contractor.
Providing and fixing of pipe type earthing from 80 mm dia class-B GI pipe with pit to be filled with salt & coke and
16 9925000016 construction of chamber as per DGVCL Drg. No. dg /100 for DP and cable. The earthing pit should be joined with cable No.
by G.I. strip of size 1” width & 2 mm thick. All material GI pipe, Coke, Salt etc will be supplied by bidder.
Supply & fixing of heat shrink type end terminations (outdoor) for upto 11kV 3C x 185 mm2 size XLPE cable as
per DGVCL technical specification
Supply & fixing of heat & shrinkable end terminations (outdoor) for upto 22 kV 3C x 185 mm size XLPE cable as per
DGVCL technical specification)
Supply & fixing of heat shrink type end terminations (indoor) for upto 11kV 3C x 185 mm2 size XLPE cable as per
DGVCL technical specification)
Supply & fixing of heat & shrinkable end terminations (indoor) for upto 22 kV 3C x 185 mm size XLPE cable as per
DGVCL technical specification
Supply & fixing of heat shrinkable straight through joint for upto 11kV 3C x 185 mm2 size XLPE cableas per DGVCL
technical specification.
Supply & fixing of heat shrinkable straight through joint type for upto 22kV 3C x 185 mm size XLPE cable as per
DGVCL technical specification
Labour charge for excavation of 2100mm long x 1200mm wide x 1200 mm deep joint pits for installation of 11kV /
23 9925000023 22kV Straight through joints as per instruction of engineer-in-charge & covering the cable with 150 mm dia (Outer), No.
thickness 25 mm, 1.0 meter long RCC half round muffs & refilling same as per instruction of EIC .
Providing and fixing of insulating bus bar, made from 11KV/22KV XLPE cable after removal of semi conducting layer
and applying of PVC heat shrinkable anti-tracking core insulating tubing (1.1KV), on both end terminal using Aluminium
24 9925000024 long barrel heavy duty up to 240 sq mm lugs, Aluminium bus connector. Taping with PG- clamp for bus conductor as No.
per drawing and as per instruction of EIC. The Alluminium lugs and PG clamp shall be covered with 11KV/22KV HT
insulating tapes.(11KV/22KV XLPE cable will be in scope of DGVCL while all other materials will be in bidder's scope)
Testing of cable at various points and commissioning the feeder as per instruction of engineer-in-charge.Test result
shall be submitted by contractor with bill.
Preparation and submission of 6 (six) copies, of complete layout drawings with GIS mapping as per actual cable
routing showing road crossing, HDPE pipe sleeving, jointing locations, markers etc.
Providing and fixing of Sign Board at junction point Made out of 2 mm aluminium sheet size 750x300 mm (2.5 x 1ft)
rectangle, as per design, pre treated with phosphate process and acid etching coated with one coat of epoxy primer and
two coats of best quality paints, refloctrorised with Hi-Intensity retro – reflective sheeting as per the latest and frame
27 9925000027 fabricated from suitable size iron angle. The Sign Board is to be fixed on the base prepared from channel and bracing No.
angles which is grouted by means of cement concreting of 1:2:4 for size of 300 mm dia x 800 mm height (500 mm to be
grouted in ground). The details to be displayed on sign board will be given by In-charge Engineer.
(a) Hi intensity Micro prismatic Grade
Providing and fixing of Sign Board (Danger Board) on Distribution Transformer Centers
Made out of 2mm aluminium sheet size 300x300mm (1x1ft) as per design, pre treated with phosphate process and acid
etching coated with one coat of epoxy primer and two coats of best quality paints, refloctrorised with Hi-Intensity retro-
reflective sheeting as per the latest and frame fabricated from suitable size iron angle. The Sign Board (Danger Board is
to be fixed at the location as per instruction of In-charge Engineer.
(a) Hi intensity Micro prismatic Grade
Providing & fixing of aluminium tag of size 250 mm (L) x 75 mm (W) from 3 mm aluminium sheet along with 1.0 mm dia
aluminium binding wire for fixing of aluminium tag near end termination joint at DP structure for identifyng the cable. The
details of feeder i.e. 11 / 22 KV with feeder name shound be punched on the tag by letter punch of size 16 mm as per
instruction of In-charge Engineer.
Supply & fixing of heat shrink type end terminations (outdoor) for 11kV 3C x 240 mm2 size XLPE cable as per
DGVCL technical specification
Supply & fixing of heat & shrinkable end terminations (outdoor) for 22 kV 3C x 240 mm2 size XLPE cable as per
DGVCL technical specification)
Supply & fixing of heat shrink type end terminations (indoor) for 11kV 3C x 240 mm2 size XLPE cable as per DGVCL
technical specification)
Supply & fixing of heat & shrinkable end terminations (indoor) for 22 kV 3C x 240 mm2 size XLPE cable as per
DGVCL technical specification
Supply & fixing of heat shrinkable straight through joint for 11kV 3C x 240 mm2 size XLPE cableas per DGVCL
technical specification.
Supply & fixing of heat shrinkable straight through joint type for 22kV 3C x 240 mm2 size XLPE cable as per DGVCL
technical specification
Installation, Testing and commissioning of 11 KV,630 A SCADA Compatible, RRL type- 3 Way RMU including Two
numbers of earthings as per Drawing (material is in bidder's scope) and as per DGVCL Technical specification.
Installation, Testing and commissioning of 11 KV,630 A SCADA Compatible, RRLL type- 4 Way RMU including Two
numbers of earthings as per Drawing (material is in bidder's scope) and as per DGVCL Technical specification.
Installation, Testing and commissioning of 22KV,630 A SCADA Compatible, RRL type-3 Way, RMU including Two
numbers of earthings as per Drawing (material is in bidder's scope) and as per DGVCL Technical specification.
Installation, Testing and commissioning of 22KV,630 A SCADA Compatible, RRLL type-4 Way, RMU including Two
numbers of earthings as per Drawing (material is in bidder's scope) and as per DGVCL Technical specification.
Construction of plinth for 11KV, RRL type- 3 Way (i.e Two numbers of Isolator & One number of Breaker) Ring Main
40 9925000042 Unit as per DGVCL's technical specification mentioned in drawing no: Drg. 11kv-01. All required material will be No.
supplied by contractor.
Construction of plinth for 11KV, RRLL type- 4 Way (i.e Two numbers of Isolator & Two number of Breaker)Ring
41 9925000043 Main Unit as per DGVCL's technical specification mentioned in drawing no:Drg. 11kv-02.All required material will be No.
supplied by contractor.
Construction of plinth for 22KV, RRL type- 3 Way (i.e Two numbers of Isolator & One number of Breaker) Ring Main
42 9925000044 Unit as per DGVCL's technical specification mentioned in drawing no: Drg. 22kv-01. All required material will be No.
supplied by contractor.
Construction of plinth for 22KV, RRLL type- 4 Way (i.e Two numbers of Isolator & Two number of Breaker)Ring
43 9925000045 Main Unit as per DGVCL's technical specification mentioned in drawing no:Drg. 22kv-02.All required material will be No.
supplied by contractor.
Modifications e.g.Providing and fixing of Terminal protectors i.e. Re-use able boot (HT Side 11/22KV, LT Side 1.1KV)
including 11/22 KV insulating taps and L.T.(1.1 KV) insulating taps ,Busbar, Tapping from Bus Bar (11/22 KV XLPE
cable) through P.G. Clamp for H.T. Jumper to D.O. Fuse to bushings of Transformer Center, providing & Fixing of
jumper and providing & fixing of Heat Shrinkable Anti Tracking Core Insulating Tubing (Insulation Level 11/22 KV) in
44 9925000046 H.T. jumper , Clamping arrangement of cable support frame on both side of existing Over Head type Distribution No.
Transformer to utilize in Under Ground cable network as per drawing & as per instruction of Engineer incharge. All live
parts i.e. PG-Clamp, connections of D.O.fuses, HT bushings etc . shall be covered with fixinng of 11/22 KV HT
insulating tapes. ( 11/22 KV XLPE cable will be in scope of DGVCL while all other materials will be in bidder's scope ) .
45 9925000047 Laying of any size of 11/ 22 KV XLPE /PILC Cable in redaymade trench or in open space
46 9925000060 Labour charges for Lying of O/H XLPE cable pole to pole KM
47 9925000064 Supply of 150 mm dia (Inner), thickness 25 mm, 1.0 meter long RCC half round pipe No.
1.DGVCL will provide key material like M.S. materials,ABC/Bare conductors,PSC/RSJ Poles,Insulators,Fabricated
materials etc. to the contractor.
2.All fabricated items shall be fabricated as per DGVCL approved drawing and by welding rods confirming to the
relevent ISI specification and as directed by Engineer in charge.
3.Necessary electricity connection for fabrication items shall be provided by DGVCL on payment of required charge for
connection & electricity bill of the same shall be paid by the agency.
4.All the rates are inclusive of PF & Exclusive of GST applicable time to time.
5.All steel material are to be painted as below:
(a) Scrubbing of rusted surface properly before applying the paints on to the RSJ poles & steel fabricated materials of
RSJ/PSC poles is must required.
(b) Two coats of approved ISI mark red oxide (primer) is to be properly painted for the RSJ poles & steel fabricated
materials of RSJ/PSC poles.
(c) Two coats of approved ISI mark silver paint (i.e. triple mangoes or equivalent quality silver paint) is to be properly
painted on to the RSJ poles & steel fabricated materials of RSJ/PSC poles.
PART-B (UG WORK )
Total Amount Rs.Twenty Seven Lacs ( PART A+ PART B)
Total Amount Rs.Twenty Seven Lacs ( PART A+ PART B)
Kadoddara Division DGVCL
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
RAW_HTML
Notice.pdf
Integrity Part - Copy (6).pdf
Technical Specification.pdf
DRAFT TENDER CONDITION.pdf
Schedule-B.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .