| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹6.0 LAccepted-AOC GLYPTIC RAIPUR P O BHITA BURDWAN 713102 | BURDWAN | PURBA BARDHAMAN | WEST BENGAL | 713102 | L1 | Accepted-AOC L1 | |
| 2 | L2₹6.9 L+₹89,700 (15.0%)Rejected-Finance | L2 | Rejected-Finance L2 | |
| 3 | L3₹10.7 L+₹4.7 L (78.5%)Rejected-Finance 19B PANKAJINI CHATTERJEE ROAD CHARU MARKET KOLKATA WEST BENGAL 700033 UDYAM WB 10 0047115 | KOLKATA | WEST BENGAL | 700033 | L3 | Rejected-Finance L3 | |
| 4 | Rejected-Technical 7A BENTINCK STREET KOLKATA 700 001 | KOLKATA | KOLKATA | WEST BENGAL | 700001 | - | Rejected-Technical insufficient Electrical Contractor license | |
| 5 | Rejected-Technical | - | Rejected-Technical Insufficient documents |
Tender Value
Refer Docs
EMD Value
₹15,000
Closing Date
13 Sept 2021, 4:00 pmClosed
Executive Engineer, PWD MsdED
GOVERNMENT OF WEST BENGALOFFICE OF THE EXECUTIVE ENGINEER, PWD MURSHIDABAD ELECTRICAL DIVISION, PWD184, C. R. DAS ROAD,BERHAMPORE, MURSHIDABAD, W.B-742101
Vertical Extensionof the left part of the mainbuilding of Lalbahg Sub-Divisional Hospital under Berhampore Division No. II during the year 2018-19.---SITC of Fire Detection System.
2021_WBPWD_342653_1
WBPWD/EE/MsdED/27/e-Q of 2021-22
Open Tender
ELECTRICAL WORKS ORG
Item Rate
15 days
GOVERNMENT OF WEST BENGAL
Please refer Tender documents.
5 documents required · 5 mandatory
₹15,000
26 Nov 2021
6 Sept 2021
15 Sept 2021
6 Sept 2021
13 Sept 2021
6 Sept 2021
Amount
Supply, Installation,Testing & Commisioning of Microprocessor based Intelligent, addressable expandable and fully networkable fire alarm control panel ( VDS / UL /ERTL/ LPCB / FM approved ) suitable for the devices as stated in the previous items of this BOQ along with 20% spare capacity with each loop loading not exceeding 80% of the full capacity of detectors and devices taken together, conplying to IS 2189:2008 or its latest amendments, and with minimum 320 character alpha - numeric liquid crystal display.The panel shall be soft addressable type and shall be able to give pin point location of all fire/ fault conditions. Further, the panel must be able to automatically switch off respective control switches whenever any alarm is triggered.The Panel should be able to store sufficient numbers of log events in its Memory as per recommended standards.
The panel shall have in built rectifier, provision for external & internal printer ( if required ), Loop cards, L C D unit to indicate Fire/Fault Signal with address and analog output, complete in all respects, in built Surge protection facility, integral SMF lead acid batteries with sealed cells of 24 V capable of running for 24 hours normal working and then be capable of operating the system for 30 minutes during Emergency condition, with integral battery charger complete in all respect as required.
The FACP shall be capable of being networked ( future expansion ) with other similar FACP located at different part of the premises through single RS 485 bus.The FACP shall have provision for interfacing with the public address system, remote computer and BMS interface.The system must be preloaded with licenced software. (Approved Make: Esser/Cerberus Pro/ Bosch/ Johnson Controls/ Notifer / Edward /Secutron/ Securiton/ Apollo / Morley / Eaton/GST )
Supply, Installation,Testing & Commisioning of Analog Addressable Intelligent multisensor detector ( VDS / UL /ERTL/ LPCB / FM approved ) with inbuilt optical smoke sensors as well as additional heat detector sensor with decentralise intelligence, soft addressable Photothermal type with inbuilt fault isolator as per NFPA style 7 wiring complete with base having IP as per recommended standard.(Note : Detectors without built-in fault isolator is also acceptable but in such case the contractor shall provide one independent fault isolator module for every group of addressable devices ( Numbers of addressable devices in a group will be as per latest recommended standards ) without any additional cost). (Approved Make: Esser/Cerberus Pro/ Bosch/ Johnson Controls/ Notifer / Edward /Secutron/ Securiton/ Apollo / Morley / Eaton/GST )
Supply, Installation,Testing & Commisioning of Addressable Manual Call Point ( VDS / UL /ERTL/ LPCB / FM approved )soft addressable type with in built fault isolator as per NFPA style 7 wiring complete as required. (Approved Make: Esser/Cerberus Pro/ Bosch/ Johnson Controls/ Notifer / Edward /Secutron/ Securiton/ Apollo / Morley / Eaton/GST )
Supply, Installation, Testing & Commissioning of Addressable Loop Powered Hooter ( sound output of minimum 90 db ) cum strobe (strength of light 10 cd)complete with inbuilt isolator & IP65 base complete ( VDS / UL /ERTL/ LPCB / FM approved) approved. (Approved Make: Esser/Cerberus Pro/ Bosch/ Johnson Controls/ Notifer / Edward /Secutron/ Securiton/ Apollo / Morley / Eaton/GST ) Note : Hooter must be Addressable by itself or by using control module. If Loop Power Hooter is not used, separate wiring from control Panel upto the the hooter will be in contractor scope without any extra cost.
Supply, Installation, Testing & Commissioning of Addressable transponder/ Monitor Modules ( VDS / UL /ERTL/ LPCB / FM approved ) for monitoring flow switches/Fire exit doors / AHU / Lift etc complete as required. (Approved Make: Esser/Cerberus Pro/ Bosch/ Johnson Controls/ Notifer / Edward /Secutron/ Securiton/ Apollo / Morley / Eaton/GST)
Supply, Installation, Testing & Commissioning of Addressable Relay Modules (VDS / UL /ERTL/ LPCB / FM approved) for switching / integration of Lift / AHU etc complete as required. (Approved Make: Esser/Cerberus Pro/ Bosch/ Johnson Controls/ Notifer / Edward /Secutron/ Securiton/ Apollo / Morley / Eaton/GST )
Supplying, installation, testing and commissioning of LED type Response Indicator ( VDS / UL /ERTL/ LPCB / FM approved) having 2 Nos. red coloured LED lamps including connections etc. (Approved Make: Esser/Cerberus Pro/ Bosch/ Johnson Controls/ Notifer / Edward /Secutron/ Securiton/ Apollo / Morley /Eaton/GST/System Sensor/Agni Suraksha )
Supply & Laying of 2 Core 1.5 sq.mm FRLS armoured copper Cable (For Loop) (Make. Finolex/RR Kable/Polycab ) with all GI fittings & accessories ,termination with appropriate cable gland.
Supply, Installation, Testing and Commissioning of public address system with 320 W amplifier, microphone, chord set as per specification.(Make-:Ahuja/Bosch/Philips)
Supply, Installation, Testing and Commissioning of speaker 10 Watt with all accessories(Make-Sonodyne/Bosch/Honeywell)
SITC of 2KVA UPS back up for PA system with 60 minute backup. (Make-APC/EMERSON /NUMERIC)
NOTE : 1. The Fire Alarm system shall comply with latest requirements of -- 2. National Fire Protection Association (NFPA) Standards. 1. IS 2189 3. NFPA 70 National Electric Code 4. NFPA 72 National Fire Alarm & Signaling Code 5. Local Statutory Regulations 6. Manufacturer Recommendation 7. Detectors/Devices without built-in fault isolator is also acceptable but in such case the contractor shall provide one independent fault isolator module for every group of addressable devices ( Numbers of addressable devices in a group will be as per latest recommended standards ) without any additional cost) .
TESTS:1.The system shall be tested and commissioned by a qualified competent,trained engineer or technician authorized by the manufacturer of the fire alarm equipment to technically supervise and participate during all of the adjustments and tests for the system. 2. Before energizing the cables and wires, check for correct connections and test for short circuits, ground faults, continuity, and insulation and other tests as per above standards must be done.
Terms and condition The Agency must procure the materials from the Manufacturer / OEM or from their authorised sales channel so that the standard warranty / support of the Manufacturer / OEM becomes applicable to the products to be delivered and installed by them.
Documents that authenticates such procurement from the Manufacturer / OEM or from their authorized sales channel and standard warranty / support should be sent from the e-mail of the Manufacturer / OEM / authorized sales channel to the e-mail of Engineer-in-Charge and hard copy of it to be submitted during execution, of work/submission of bill.
If any refurbished material is supplied and installed, penal action will be taken as per existing rules
MAM ENTERPRISE
BALAJI FIRE PROTECTION SYSTEMS
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.PDF
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .