Loading…
Tenderkart now works inside Claude and ChatGPT: search and analyse tenders right from your chat
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹71.8 LAccepted-AOC 8 51 PLOT NO 6 LIC COLONY SUJATA NAGAR PENDURTHY MANDAL VISAKHAPATNAM 530042 AP | 530042 | L1 | Accepted-AOC Being L1 | |
| 2 | L2₹78.3 L+₹6.6 L (9.13%)Rejected-Finance DOOR NO 14 6 21 5 OPP MARVAL SCHOOL BC ROAD NEW GAJUWAKA VISAKHAPATNAM 530026 | VISAKHAPATNAM | VISAKHAPATNAM | ANDHRA PRADESH | 530026 | L2 | Rejected-Finance Not Being L1 | |
| 3 | L3₹82.0 L+₹10.2 L (14.2%)Rejected-Finance HARINAGAR BEHIND MAHESHWARY MARKET PO TATISILWAI DIST RANCHI PIN 835103 | RANCHI | JHARKHAND | 835103 | L3 | Rejected-Finance Not Being L1 | |
| 4 | L4₹83.2 L+₹11.4 L (15.9%)Rejected-Finance | L4 | Rejected-Finance Not Being L1 | |
| 5 | L5₹84.1 L+₹12.3 L (17.2%)Rejected-Finance DOOR NO 2 31 23 SECTOR 7 SBI COLONY MVP VISAKHAPATNAM 530 017 | VISAKHAPATANAM | ANDHRA PRADESH | 530017 | L5 | Rejected-Finance Not Being L1 |
Tender Value
₹89.2 L
EMD Value
₹1.6 L
Closing Date
10 Dec 2021, 6:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
GE (I) (DM) VISAKHAPATNAM
GE (I) (DM) VISAKHAPATNAM Naval Dockyard Visakhapatnam 530014
REPLACEMENT OF MS DISTRIBUTION PILLAR BOXES AT IN JETTIES N4 TO N-14A FOR PROVIDING SHORE SUPPLY AT NAVAL DOCKYARD VISAKHAPATNAM UNDER GE (I) (DM) VISAKHAPATNAM
2021_MES_474914_3
SSGE/8620/E8
Open Tender
Electrical and Maintenance Works
Item Rate
90 days
GE (I) (DM) VISAKHAPATNAM
As per tender documents
7 documents required · 7 mandatory
₹1,000
GE (I) (DM) VISAKHAPATNAM
₹1.6 L
Yes
7 Jan 2022
27 Nov 2021
17 Dec 2021
27 Nov 2021
10 Dec 2021
3 Dec 2021
60 days
Amount
Dismantling existing unserviceable / corroded LT Pillar Box and supply, fabricate, install, testing and commissioning in-door type, single door dust & vermin proof LT piller box of 2 M length, 1 M width & 1.6 M height fabricated vertically by using 50x50x5 mm angle iron frame, fixing with nuts & bolts on 75 x 40 mm ISMC as per directions of Engineer-in-Charge and using 3 mm thick CRCA MS sheet all over body front and back cover with hinges and aldrops for locking arrangments, 1 mm thick FRP coating all over the external surfaces and 3 mm thick MS sheet for bus bar cover, piller Box, partitions and bottom cable entry covers duly painted with one coat of redoxide and two coats of synthetic enamel paint including control wiring complete in LT piller box with 2.5 sq mm FRLS copper conductor cable and 5A MCB SPs 2.5 amp for meters, breaker control supply and indication lamps and provision to accommodate the following: (a) 3 ph+1N Copper busbar of equall sizes of capacity 1.5 times of rated current of incoming switchgear. (b) 3 ph+1N Copper busbar of equall sizes of capacity 1.5 times of rated current of outgoing switchgears as down links/connectivity links to switchgear.
(c) Digital ammeter & voltmeter for incoming & Digital ammeter for outgoing. (d) LED indication lamps for RYB for incoming and outgoing indication.(Red,yellow & blue coloured) (e) LT ACB – 1600Amps, 4P, 50KA, complete with over current and earth fault tripping device as incomer -01No (f) LT ACB - 1250 Amps, 3P, 50 KA complete with over current and earth fault tripping device as out going-01 No (g) LT ACB - 800 Amps, 3P, 50KA complete with over current and earth fault tripping device as out going-01No Note : (i) Unit rate quoted include for necessary grouting / chipping of concrete and Anchor fastners and providing necessary PCC (1:2:4) type B1 using 20 mm graded crushed stone agreegate for foundation to fix the LT Piller Box. (ii) Cost of digital ammeter, voltmeter, LED lamps, CTs, LT ACBs, MCCBs and MCBs shall be included in the quoted rate. (iii) Drawing shall be got approved by GE before fabrication of the LT piller Box. (iv) All incoming and outgoing cable connections are to be made as per existing one and rate deemeded to be included in the quoted rate. (v) The pillar box shall be brought to Jetty gallery part by part and to be assembled in site being limited space of work/movement and rate shall deemed to be included in quoted rate. (vi) Copper busbars with pvc sleeves shall be measured and paid seperately under respective item in this schedule as 'Supply only'
Dismantling existing unserviceable / corroded LT Pillar Box and supply, fabricate, install, testing and commissioning out-door type, double door dust & vermin proof LT piller box of 2 M length, 1 M width & 1.6 M height fabricated vertically by using 50x50x5 mm angle iron frame, fixing with nuts & bolts on 75 x 40 mm ISMC as per directions of Engineer-in-Charge and using 3 mm thick CRCA MS sheet all over body front and back cover with hinges and aldrops for locking arrangments, 1 mm thick FRP coating all over the external surfaces and 3 mm thick MS sheet for bus bar cover, piller Box, partitions and bottom cable entry covers duly painted with one coat of redoxide and two coats of synthetic enamel paint including control wiring complete in LT piller box with 1.5 sq mm FRLS copper conductor cable and 5A MCB SPs 2.5 amp for meters, breaker control supply and indication lamps and provision to accommodate the following: (a) 3 ph+1N Copper busbar of equall sizes of capacity 1.5 times of rated current of incoming switchgear. (b) 3 ph+1N Copper busbar of equall sizes of capacity 1.5 times of rated current of outgoing switchgears as down links/connectivity links to switchgear.
(c) Digital ammeter & voltmeter for incoming & Digital ammeter for outgoing. (d) LED indication lamps for RYB for incoming and outgoing indication.(Red,yellow & blue coloured) (e) LT ACB – 1000Amps, 4P, 50KA, complete with over current and earth fault tripping device as incomer -01No (f) LT ACB - 800 Amps, 3P, 50KA complete with over current and earth fault tripping device as out going-02 Nos Note : (i) Unit rate quoted include for necessary grouting / chipping of concrete and Anchor fastners and providing necessary PCC (1:2:4) type B1 using 20 mm graded crushed stone agreegate for foundation to fix the LT Piller Box. (ii) Cost of digital ammeter, voltmeter, LED lamps, CTs, LT ACBs, MCCBs and MCBs shall be included in the quoted rate (iii) Drawing shall be got approved by GE before fabrication of the LT piller Box. (iv) All incoming and outgoing cable connections are to be made as per existing one and rate deemeded to be included in the quoted rate. (v) The pillar box shall be brought to Jetty gallery part by part and to be assembled in site being limited space of work/movement and rate shall deemed to be included in quoted rate. (vi) Copper busbars with pvc sleeves shall be measured and paid seperately under respective item in this schedule as 'Supply only'
Dismantling existing unserviceable /corroded LT Pillar Box and supply, fabricate, install, testing and commissioning out-door type, double door dust & vermin proof LT piller box of 2 M length, 1 M width & 1.6 M height fabricated vertically by using 50x50x5 mm angle iron frame, fixing with nuts & bolts on 75 x 40 mm ISMC as per directions of Engineer-in-Charge and using 3 mm thick CRCA MS sheet all over body front and back cover with hinges and aldrops for locking arrangments, 1 mm thick FRP coating all over the external surfaces and 3 mm thick MS sheet for bus bar cover, piller Box, partitions and bottom cable entry covers duly painted with one coat of redoxide and two coats of synthetic enamel paint including control wiring complete in LT piller box with 1.5 sq mm FRLS copper conductor cable and 5A MCB SPs 2.5 amp for meters, breaker control supply and indication lamps and provision to accommodate the following: (a) 3 ph+1N Copper busbar of equall sizes of capacity 1.5 times of rated current of incoming switchgear. (b) 3 ph+1N Copper busbar of equall sizes of capacity 1.5 times of rated current of outgoing switchgears as down links/connectivity links to switchgear.
(c) Digital ammeter & voltmeter for incoming & Digital ammeter for outgoing. (d) LED indication lamps for RYB for incoming and outgoing indication.(Red,yellow & blue coloured) (e) LT ACB – 1000Amps, 4P, 50KA, complete with over current and earth fault tripping device as incomer -01No (f) LT ACB - 1000 Amps, 3P, 50 KA complete with over current and earth fault tripping device as out going-01 No (g) MCCB - 630 Amps, 3P, 36KA complete with over current and earth fault tripping device as out going-01No Note : (i) Unit rate quoted include for necessary grouting / chipping of concrete and Anchor fastners and providing necessary PCC (1:2:4) type B1 using 20 mm graded crushed stone agreegate for foundation to fix the LT Piller Box. (ii) Cost of digital ammeter, voltmeter, LED lamps, CTs, LT ACBs, MCCBs and MCBs shall be included in the quoted rate. (iii) Drawing shall be got approved by GE before fabrication of the LT piller Box. (iv) All incoming and outgoing cable connections are to be made as per existing one and rate deemeded to be included in the quoted rate. (v) The pillar box shall be brought to Jetty gallery part by part and to be assembled in site being limited space of work/movement and rate shall deemed to be included in quoted rate. (vi) Copper busbars with pvc sleeves shall be measured and paid seperately under respective item in this schedule as 'Supply only'
Dismantling existing unserviceable / corroded LT Pillar Box and supply, fabricate, install, testing and commissioning out-door type, double door dust & vermin proof LT piller box of 3 M length, 1 M width & 1.6 M height fabricated vertically by using 50x50x5 mm angle iron frame, fixing with nuts & bolts on 75 x 40 mm ISMC as per directions of Engineer-in-Charge and using 3 mm thick CRCA MS sheet all over body front and back cover with hinges and aldrops for locking arrangments, 1 mm thick FRP coating all over the external surfaces and 3 mm thick MS sheet for bus bar cover, piller Box, partitions and bottom cable entry covers duly painted with one coat of redoxide and two coats of synthetic enamel paint including control wiring complete in LT piller box with 1.5 sq mm FRLS copper conductor cable and 5A MCB SPs 2.5 amp for meters, breaker control supply and indication lamps and provision to accommodate the following: (a) 3 ph+1N Copper busbar of equall sizes of capacity 1.5 times of rated current of incoming switchgear. (b) 3 ph+1N Copper busbar of equall sizes of capacity 1.5 times of rated current of outgoing switchgears as down links/connectivity links to switchgear.
(c) Digital ammeter & voltmeter for incoming & Digital ammeter for outgoing. (d) LED indication lamps for RYB for incoming and outgoing indication.(Red,yellow & blue coloured) (e) MCCB – 630Amps, 4P, 36KA, complete with over current and earth fault tripping device as incomer -01No (f) MCCB - 630 Amps, 3P, 36 KA complete with over current and earth fault tripping device as out going-01 No (g) MCCB - 400 Amps, 3P, 36KA complete with over current and earth fault tripping device as out going-01No (h) MCCB - 250 Amps, 3P, 36KA complete with over current and earth fault tripping device as out going-02No Note : (i) Unit rate quoted include for necessary grouting / chipping of concrete and Anchor fastners and providing necessary PCC (1:2:4) type B1 using 20 mm graded crushed stone agreegate for foundation to fix the LT Piller Box. (ii) Cost of digital ammeter, voltmeter, LED lamps, CTs, LT ACBs, MCCBs and MCBs shall be included in the quoted rate. (iii) Drawing shall be got approved by GE before fabrication of the LT piller Box. (iv) All incoming and outgoing cable connections are to be made as per existing one and rate deemeded to be included in the quoted rate. (v) The pillar box shall be brought to Jetty gallery part by part and to be assembled in site being limited space of work/movement and rate shall deemed to be included in quoted rate. (vi) Copper busbars with pvc sleeves shall be measured and paid seperately under respective item in this schedule as 'Supply only'
Dismantling existing unserviceable /corroded LT Pillar Box and supply, fabricate, install, testing and commissioning out-door type, double door dust & vermin proof LT piller box of 2 M length, 1 M width & 1.6 M height fabricated vertically by using 50x50x5 mm angle iron frame, fixing with nuts & bolts on 75 x 40 mm ISMC as per directions of Engineer-in-Charge and using 3 mm thick CRCA MS sheet all over body front and back cover with hinges and aldrops for locking arrangments, 1 mm thick FRP coating all over the external surfaces and 3 mm thick MS sheet for bus bar cover, piller Box, partitions and bottom cable entry covers duly painted with one coat of redoxide and two coats of synthetic enamel paint including control wiring complete in LT piller box with 1.5 sq mm FRLS copper conductor cable and 5A MCB SPs 2.5 amp for meters, breaker control supply and indication lamps and provision to accommodate the following: (a) 3 ph+1N Copper busbar of equall sizes of capacity 1.5 times of rated current of incoming switchgear. (b) 3 ph+1N Copper busbar of equall sizes of capacity 1.5 times of rated current of outgoing switchgears as down links/connectivity links to switchgear.
(c) Digital ammeter & voltmeter for incoming & Digital ammeter for outgoing. (d) LED indication lamps for RYB for incoming and outgoing indication.(Red,yellow & blue coloured) (e) LT ACB – 1250Amps, 4P, 50KA, complete with over current and earth fault tripping device as incomer -01No (f) LT ACB - 1000 Amps, 3P, 50 KA complete with over current and earth fault tripping device as out going-01 No (g) LT ACB - 800 Amps, 3P, 50 KA complete with over current and earth fault tripping device as out going-01No Note : (i) Unit rate quoted include for necessary grouting / chipping of concrete and Anchor fastners and providing necessary PCC (1:2:4) type B1 using 20 mm graded crushed stone agreegate for foundation to fix the LT Piller Box. (ii) Cost of digital ammeter, voltmeter, LED lamps, CTs, LT ACBs, MCCBs and MCBs shall be included in the quoted rate (iii) Drawing shall be got approved by GE before fabrication of the LT piller Box. (iv) All incoming and outgoing cable connections are to be made as per existing one and rate deemeded to be included in the quoted rate. (v) The pillar box shall be brought to Jetty gallery part by part and to be assembled in site being limited space of work/movement and rate shall deemed to be included in quoted rate. (vi) Copper busbars with pvc sleeves shall be measured and paid seperately under respective item in this schedule as 'Supply only'
Dismantling existing unserviceable /corroded LT Pillar Box and supply, fabricate, install, testing and commissioning in-door type, single door dust & vermin proof LT piller box of 2 M length, 1 M width & 1.6 M height fabricated vertically by using 50x50x5 mm angle iron frame, fixing with nuts & bolts on 75 x 40 mm ISMC as per directions of Engineer-in-Charge and using 3 mm thick CRCA MS sheet all over body front and back cover with hinges and aldrops for locking arrangments, 1 mm thick FRP coating all over the external surfaces and 3 mm thick MS sheet for bus bar cover, piller Box, partitions and bottom cable entry covers duly painted with one coat of redoxide and two coats of synthetic enamel paint including control wiring complete in LT piller box with 1.5 sq mm FRLS copper conductor cable and 5A MCB SPs 2.5 amp for meters, breaker control supply and indication lamps and provision to accommodate the following: (a) 3 ph+1N Copper busbar of equall sizes of capacity 1.5 times of rated current of incoming switchgear. (b) 3 ph+1N Copper busbar of equall sizes of capacity 1.5 times of rated current of outgoing switchgears as down links/connectivity links to switchgear.
(c) Digital ammeter & voltmeter for incoming & Digital ammeter for outgoing. (d) LED indication lamps for RYB for incoming and outgoing indication.(Red,yellow & blue coloured) (e) LT ACB – 1600Amps, 4P, 50KA, complete with over current and earth fault tripping device as incomer -01No (f) LT ACB - 1600 Amps, 3P, 50 KA complete with over current and earth fault tripping device as out going-01 No (g) LT ACB - 800 Amps, 3P, 50 KA complete with over current and earth fault tripping device as out going-01No Note : (i) Unit rate quoted include for necessary grouting / chipping of concrete and Anchor fastners and providing necessary PCC (1:2:4) type B1 using 20 mm graded crushed stone agreegate for foundation to fix the LT Piller Box. (ii) Cost of digital ammeter, voltmeter, LED lamps, CTs, LT ACBs, MCCBs and MCBs shall be included in the quoted rate. (iii) Drawing shall be got approved by GE before fabrication of the LT piller Box. (iv) All incoming and outgoing cable connections are to be made as per existing one and rate deemeded to be included in the quoted rate. (v) The pillar box shall be brought to Jetty gallery part by part and to be assembled in site being limited space of work/movement and rate shall deemed to be included in quoted rate. (vi) Copper busbars with pvc sleeves shall be measured and paid seperately under respective item in this schedule as 'Supply only'
Dismantling existing unserviceable /corroded LT Pillar Box and supply, fabricate, install, testing and commissioning in-door type, single door dust & vermin proof LT piller box of 2 M length, 1 M width & 1.6 M height fabricated vertically by using 50x50x5 mm angle iron frame, fixing with nuts & bolts on 75 x 40 mm ISMC as per directions of Engineer-in-Charge and using 3 mm thick CRCA MS sheet all over body front and back cover with hinges and aldrops for locking arrangments, 1 mm thick FRP coating all over the external surfaces and 3 mm thick MS sheet for bus bar cover, piller Box, partitions and bottom cable entry covers duly painted with one coat of redoxide and two coats of synthetic enamel paint including control wiring complete in LT piller box with 1.5 sq mm FRLS copper conductor cable and 5A MCB SPs 2.5 amp for meters, breaker control supply and indication lamps and provision to accommodate the following: (a) 3 ph+1N Copper busbar of equall sizes of capacity 1.5 times of rated current of incoming switchgear. (b) 3 ph+1N Copper busbar of equall sizes of capacity 1.5 times of rated current of outgoing switchgears as down links/connectivity links to switchgear.
(c) Digital ammeter & voltmeter for incoming & Digital ammeter for outgoing. (d) LED indication lamps for RYB for incoming and outgoing indication.(Red,yellow & blue coloured) (e) LT ACB – 1600Amps, 4P, 50KA, complete with over current and earth fault tripping device as incomer -01No (f) LT ACB - 1600 Amps, 3P, 50 KA complete with over current and earth fault tripping device as out going-01 No (g) MCCB - 630 Amps, 3P, 36 KA complete with over current and earth fault tripping device as out going-01No Note : (i) Unit rate quoted include for necessary grouting / chipping of concrete and Anchor fastners and providing necessary PCC (1:2:4) type B1 using 20 mm graded crushed stone agreegate for foundation to fix the LT Piller Box. (ii) Cost of digital ammeter, voltmeter, LED lamps, CTs, LT ACBs, MCCBs and MCBs shall be included in the quoted rate. (iii) Drawing shall be got approved by GE before fabrication of the LT piller Box. (iv) All incoming and outgoing cable connections are to be made as per existing one and rate deemeded to be included in the quoted rate. (v) The pillar box shall be brought to Jetty gallery part by part and to be assembled in site being limited space of work/movement and rate shall deemed to be included in quoted rate. (vi) Copper busbars with pvc sleeves shall be measured and paid seperately under respective item in this schedule as 'Supply only'
Dismantling existing unserviceable /corroded LT Pillar Box and supply, fabricate, install, testing and commissioning in-door type, single door dust & vermin proof LT piller box of 2 M length, 1 M width & 1.6 M height fabricated vertically by using 50x50x5 mm angle iron frame, fixing with nuts & bolts on 75 x 40 mm ISMC as per directions of Engineer-in-Charge and using 3 mm thick CRCA MS sheet all over body front and back cover with hinges and aldrops for locking arrangments, 1 mm thick FRP coating all over the external surfaces and 3 mm thick MS sheet for bus bar cover, piller Box, partitions and bottom cable entry covers duly painted with one coat of redoxide and two coats of synthetic enamel paint including control wiring complete in LT piller box with 1.5 sq mm FRLS copper conductor cable and 5A MCB SPs 2.5 amp for meters, breaker control supply and indication lamps and provision to accommodate the following: (a) 3 ph+1N Copper busbar of equall sizes of capacity 1.5 times of rated current of incoming switchgear. (b) 3 ph+1N Copper busbar of equall sizes of capacity 1.5 times of rated current of outgoing switchgears as down links/connectivity links to switchgear.
(c) Digital ammeter & voltmeter for incoming & Digital ammeter for outgoing. (d) LED indication lamps for RYB for incoming and outgoing indication.(Red,yellow & blue coloured) (e) LT ACB – 1250Amps, 4P, 50KA, complete with over current and earth fault tripping device as incomer -01No (f) LT ACB - 1250 Amps, 3P, 50 KA complete with over current and earth fault tripping device as out going-01 No (g) LT ACB - 800 Amps, 3P, 50 KA complete with over current and earth fault tripping device as out going-01No Note : (i) Unit rate quoted include for necessary grouting / chipping of concrete and Anchor fastners and providing necessary PCC (1:2:4) type B1 using 20 mm graded crushed stone agreegate for foundation to fix the LT Piller Box. (ii) Cost of digital ammeter, voltmeter, LED lamps, CTs, LT ACBs, MCCBs and MCBs shall be included in the quoted rate (iii) Drawing shall be got approved by GE before fabrication of the LT piller Box. (iv) All incoming and outgoing cable connections are to be made as per existing one and rate deemeded to be included in the quoted rate. (v) The pillar box shall be brought to Jetty gallery part by part and to be assembled in site being limited space of work/movement and rate shall deemed to be included in quoted rate. (vi) Copper busbars with pvc sleeves shall be measured and paid seperately under respective item in this schedule as 'Supply only'
Dismantling existing unserviceable /corroded LT Pillar Box and supply, fabricate, install, testing and commissioning in-door type, single door dust & vermin proof LT piller box of 2 M length, 1 M width & 1.6 M height fabricated vertically by using 50x50x5 mm angle iron frame, fixing with nuts & bolts on 75 x 40 mm ISMC as per directions of Engineer-in-Charge and using 3 mm thick CRCA MS sheet all over body front and back cover with hinges and aldrops for locking arrangments, 1 mm thick FRP coating all over the external surfaces and 3 mm thick MS sheet for bus bar cover, piller Box, partitions and bottom cable entry covers duly painted with one coat of redoxide and two coats of synthetic enamel paint including control wiring complete in LT piller box with 1.5 sq mm FRLS copper conductor cable and 5A MCB SPs 2.5 amp for meters, breaker control supply and indication lamps and provision to accommodate the following: (a) 3 ph+1N Copper busbar of equall sizes of capacity 1.5 times of rated current of incoming switchgear. (b) 3 ph+1N Copper busbar of equall sizes of capacity 1.5 times of rated current of outgoing switchgears as down links/connectivity links to switchgear.
(c) Digital ammeter & voltmeter for incoming & Digital ammeter for outgoing. (d) LED indication lamps for RYB for incoming and outgoing indication.(Red,yellow & blue coloured) (e) LT ACB – 1250Amps, 4P, 50KA, complete with over current and earth fault tripping device as incomer -01No (f) LT ACB - 1250 Amps, 3P, 50 KA complete with over current and earth fault tripping device as out going-01 No (g) MCCB - 630 Amps, 3P, 50 KA complete with over current and earth fault tripping device as out going-01No Note : (i) Unit rate quoted include for necessary grouting / chipping of concrete and Anchor fastners and providing necessary PCC (1:2:4) type B1 using 20 mm graded crushed stone agreegate for foundation to fix the LT Piller Box. (ii) Cost of digital ammeter, voltmeter, LED lamps, CTs, LT ACBs, MCCBs and MCBs shall be included in the quoted rate. (iii) Drawing shall be got approved by GE before fabrication of the LT piller Box. (iv) All incoming and outgoing cable connections are to be made as per existing one and rate deemeded to be included in the quoted rate. (v) The pillar box shall be brought to Jetty gallery part by part and to be assembled in site being limited space of work/movement and rate shall deemed to be included in quoted rate. (vi) Copper busbars with pvc sleeves shall be measured and paid seperately under respective item in this schedule as 'Supply only'
Dismantling existing unserviceable /corroded LT Pillar Box and supply, fabricate, install, testing and commissioning in-door type, single door dust & vermin proof LT piller box of 2 M length, 1 M width & 1.6 M height fabricated vertically by using 50x50x5 mm angle iron frame, fixing with nuts & bolts on 75 x 40 mm ISMC as per directions of Engineer-in-Charge and using 3 mm thick CRCA MS sheet all over body front and back cover with hinges and aldrops for locking arrangments, 1 mm thick FRP coating all over the external surfaces and 3 mm thick MS sheet for bus bar cover, piller Box, partitions and bottom cable entry covers duly painted with one coat of redoxide and two coats of synthetic enamel paint including control wiring complete in LT piller box with 1.5 sq mm FRLS copper conductor cable and 5A MCB SPs 2.5 amp for meters, breaker control supply and indication lamps and provision to accommodate the following: (a) 3 ph+1N Copper busbar of equall sizes of capacity 1.5 times of rated current of incoming switchgear. (b) 3 ph+1N Copper busbar of equall sizes of capacity 1.5 times of rated current of outgoing switchgears as down links/connectivity links to switchgear.
(c) Digital ammeter & voltmeter for incoming & Digital ammeter for outgoing. (d) LED indication lamps for RYB for incoming and outgoing indication.(Red,yellow & blue coloured) (e) LT ACB – 2000Amps, 4P, 50KA, complete with over current and earth fault tripping device as incomer -01No (f) LT ACB - 2000 Amps, 3P, 50 KA complete with over current and earth fault tripping device as out going-01 No (g) LT ACB - 800 Amps, 3P, 50 KA complete with over current and earth fault tripping device as out going-01No Note : (i) Unit rate quoted include for necessary grouting / chipping of concrete and Anchor fastners and providing necessary PCC (1:2:4) type B1 using 20 mm graded crushed stone agreegate for foundation to fix the LT Piller Box. (ii) Cost of digital ammeter, voltmeter, LED lamps, CTs, LT ACBs, MCCBs and MCBs shall be included in the quoted rate (iii) Drawing shall be got approved by GE before fabrication of the LT piller Box. (iv) All incoming and outgoing cable connections are to be made as per existing one and rate deemeded to be included in the quoted rate. (v) The pillar box shall be brought to Jetty gallery part by part and to be assembled in site being limited space of work/movement and rate shall deemed to be included in quoted rate. (vi) Copper busbars with pvc sleeves shall be measured and paid seperately under respective item in this schedule as 'Supply only'
Dismantling existing unserviceable /corroded LT Pillar Box and supply, fabricate, install, testing and commissioning out-door type, double door dust & vermin proof LT piller box of 2 M length, 1 M width & 1.6 M height fabricated vertically by using 50x50x5 mm angle iron frame, fixing with nuts & bolts on 75 x 40 mm ISMC as per directions of Engineer-in-Charge and using 3 mm thick CRCA MS sheet all over body front and back cover with hinges and aldrops for locking arrangments, 1 mm thick FRP coating all over the external surfaces and 3 mm thick MS sheet for bus bar cover, piller Box, partitions and bottom cable entry covers duly painted with one coat of redoxide and two coats of synthetic enamel paint including control wiring complete in LT piller box with 1.5 sq mm FRLS copper conductor cable and 5A MCB SPs 2.5 amp for meters, breaker control supply and indication lamps and provision to accommodate the following: (a) 3 ph+1N Copper busbar of equall sizes of capacity 1.5 times of rated current of incoming switchgear. (b) 3 ph+1N Copper busbar of equall sizes of capacity 1.5 times of rated current of outgoing switchgears as down links/connectivity links to switchgear.
(c) Digital ammeter & voltmeter for incoming & Digital ammeter for outgoing. (d) LED indication lamps for RYB for incoming and outgoing indication.(Red,yellow & blue coloured) (e) LT ACB – 1250 Amps, 4P, 50KA, complete with over current and earth fault tripping device as incomer -01No (f) LT ACB - 1250 Amps, 3P, 50 KA complete with over current and earth fault tripping device as out going-01 No (g)MCCB - 400 Amps, 3P, 36 KA complete with over current and earth fault tripping device as out going-01No Note : (i) Unit rate quoted include for necessary grouting / chipping of concrete and Anchor fastners and providing necessary PCC (1:2:4) type B1 using 20 mm graded crushed stone agreegate for foundation to fix the LT Piller Box. (ii) Cost of digital ammeter, voltmeter, LED lamps, CTs, LT ACBs, MCCBs and MCBs shall be included in the quoted rate. (iii) Drawing shall be got approved by GE before fabrication of the LT piller Box. (iv) All incoming and outgoing cable connections are to be made as per existing one and rate deemeded to be included in the quoted rate. (v) The pillar box shall be brought to Jetty gallery part by part and to be assembled in site being limited space of work/movement and rate shall deemed to be included in quoted rate. (vi) Copper busbars with pvc sleeves shall be measured and paid seperately under respective item in this schedule as 'Supply only'
Supply only copper bus bar links with PVC sleeves of raing 630 A to 2000 A complete all as specified and directed.
REAL ENGINEERING WORKS
UNIVERSAL ENTERPRISES
M/s Sai Venkata Durga Constructions
M/s SS Engineering Enterprises
Vijaypower Generators Limited
eldi techs
SD TECH
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .