| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹32.8 LAccepted-AOC | L1 | Accepted-AOC L1 | |
| 2 | L2₹34.5 L+₹1.6 L (4.74%)Rejected-Finance | L2 | Rejected-Finance L2 | |
| 3 | L3₹35.0 L+₹2.0 L (6.14%)Rejected-Finance | L3 | Rejected-Finance L3 | |
| 4 | L4₹35.3 L+₹2.3 L (6.96%)Rejected-Finance | L4 | Rejected-Finance L4 | |
| 5 | Rejected-Technical | - | Rejected-Technical Due to not fulfilling Cat b(i) |
Tender Value
₹30.5 L
EMD Value
₹61,000
Closing Date
2 Nov 2021, 6:00 pmClosed
Lt Col Bhamre Kiran S
Military Engineer Service Garrison Engineer (AF) No.1 Air Force Station No.1 Jamnagar 361 003
CERTAIN E/M MINOR AND SPECIAL REPAIR WORKS AT VARIOUS LOCATIONS UNDER GE(AF) JAMNAGAR NO.1
2021_MES_474172_2
8121/E8
Open Tender
Miscellaneous Works
Item Rate
180 days
Jamnagar
Please refer Tender documents
6 documents required · 6 mandatory
₹500
GE (AF) Jamnagar No. 1
₹61,000
Yes
27 Nov 2021
19 Oct 2021
3 Nov 2021
19 Oct 2021
2 Nov 2021
26 Oct 2021
Amount
Materials & labour in repairs for XLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, cross-sectional area 240 sq. mm 3.5 core. Complete all as specified and directed.
Supply and lay in repairs High density polyethylene pipes (HDPE) of size 100 mm bore of PN10 with fittings include for jointing and jointing materials fixed complete to walls, ceilings or in floors etc. Complete all as specified and directed.
Excavating in trenches, n exc 1.5 m wide and n exc 1.5 m in depth; for foundation, etc. or for shafts, wells, cesspits, manholes, pier holes, etc. n exc 10 sq m on plan and n exc 1.5 m in depth and getting out in soft/loose soil and getting out all as directed.
Returning, filling in, including spreading, levelling, watering and well ramming in layers not exc 25 cm in soft/loose soil all as directed.
Removing excavated soil n exc. 50m and depositing where directed at a level n exc. 1.5 m above the starting point all as directed.
M&L for providing dry river sand as in sand cushioning to under ground PVC cable including punning down of sand in layer all as specified and directed. (Note: Work shall be executed as per clause 19.75 of standard schedule of rates part-1 (2009) for measurement purpose thickness of sand after punning down will be considered.)
Supply & laying ISI marked & conforming to IS - 5820 - 1970 unreinforced precast concrete cable cover Class LV , Type I , flat size 250 mm X 150 mm X 40 mm in trenches as protection to LT UG cable all as specified and directed.
S&F in repairs Copper strip 20 x 3.15mm with saddles and fixing screws etc. complete fixed to wall / ceiling in any position or any other situation for loop earthing etc. and including epoxy insulators with necessary fixture complete all as specified and directed.
S&F Copper strip 20 x 3.15mm with saddles and fixing screws etc. complete fixed to wall / ceiling in any position or any other situation for loop earthing etc. and including epoxy insulators with necessary fixture complete all as specified and directed.
S&F in repairs Aluminium strip 25 x 3.15mm with saddles and fixing screws etc. complete fixed to wall / ceiling in any position or any other situation for loop earthing etc.and including epoxy insulators with necessary fixture complete all as specified and directed.
Material and labour in replacement for provision of earthing complete with galvanized iron earth plate electrode 600 mm x 600 mm x 6 mm thick buried directly in ground (earth pit not less than 2.25 m deep below normal ground level) with top edge of the plate not less than 1.5 m deep below normal ground connected to galvanised mild steel strip 32 x 6 mm by means of bolts, nuts, check nuts and washer of galvanized steel, watering pipe of 20 mm bore galvanised iron medium grade and 40 mm bore galvanised iron light grade for earth strip protection including.....
.....all excavation, earth work in any type of soil, PCC pit in PCC 1:2:4 type B-1 and RCC 1:2:4, type B1 for precast chamber cover 50 mm thick, reinforced with welded steel wire fabric or XPM Jali (weight not less than 4.00 Kg / sqm), with charcoal, salt, funnel complete all as shown in the electrical plate No 3 of SSR part –I and testing on completion. Note : (i)Earth result after installation completely should be less than 5 Ohm . (ii)Quoted rates shall be deemed to include for earth strip with protection pipe of 7.5 M length.
M&L in replacement for provn of chemical earthing with copper earth plate 90x60cmx5mm & copper earth strip 50x6mm complete all as specified.
M&L for provn of chemical earthing with copper earth plate 90x60cmx5mm & copper earth strip 50x6mm complete all as specified.
Material & Labour for point wiring for one light / Fan point controlled by one way switch complete with 1.5 Sqmm multi-stranded copper conductor PVC insulated, unsheathed, fire retardant low smoke cable 1100 volts grade ISI marked drawn and including PVC casing capping 20 mm dia , including all accessories like bend, tees, junction boxes etc. including 1.5 Sqmm multi-stranded copper conductor PVC insulated, unsheathed, fire retardant low smoke cable as a earth wire connected to common earth dolly, etc including pressed steel terminal box of suitable size for modular switch complete all as specified and directed. Note:- Cutting chasing wherever required for concealed wiring will be measured & paid separately.
All as per item No 14 above but point wiring for one 5 Amps socket outlet on independent board controlled by one-way switch.
All as per item No 14 above but point wiring for one 5 Amps socket outlet on same board controlled by one-way switch.
All as per item No 14 above but wiring with 2.5 Sqmm multi-stranded copper conductor PVC insulated, unsheathed fire retardant low smoke, cable and 2.5 Sqmm multi-stranded copper conductor PVC insulated, unsheathed fire retardant low smoke, cable as earth wire connected to common earth dolly for 15 Amps multipurpose socket outlet on independent board, controlled with one way switch.
M&L Modular switch 1 way 6A, 1 module including connecting complete.
M & L for Socket, 6A - 2/3 pin combined 2 module,including connecting complete.
M&L Modular switch 1 way 16A,1 module, including connecting complete.
M & LSocket 6A/16A - 2/3 pin combined 2 module, including connecting complete.
Supply and fix White cover plate with frame, 4 module, including connecting complete.
Material & Labour for sub main wiring with 2 run single core multistranded copper conductor cable, of size 2.5 Sqmm each, PVC insulated, unsheathed, fire retardant, low smoke (FRLS) drawn through and including PVC conduit/casing capping and including one run single core multistranded copper conductor cable, of size 2.5 Sqmm, PVC insulated, unsheathed, fire retardant low smoke as earth wire, fixed on wall / ceiling complete. Note: 2 Runs of main cable and one run earth wire including cassing capping will be measured as one unit for payment.
S&F 25mm dia bore, GI Pipe heavy duty for fixing on wall & buried in ground complete or fixed in position suitable for pneumatic pipe line all as specified and as directed by Engg-in-Charge.
S&F SS half cock ball valve 25mm, with SS handle, screwed both ends for Air/Steel pipe complete fixed in position all as specified and directed.
Supply and fix LED Type Aviation warning light comprising of aluminium housing with polycarbonate enclosure LED to be provided fixed in position all as directed.
S & F Single pole and neutral enclosure with a two pin and earth plug and socket complete with one single pole 20 Amp MCB SP, C curve complete all as specified and as directed.
S&F Distribution board made out of sheet metal enclosure (CRCA sheet) dust and vermin proof SPN 8 way with 200 Amps rated copper bus bar neutral bar, earth bar IP 43 protection, single pole and neutral 230 volts, double door type, fixed flush to wall complete all as specified and directed.
Supply and Fix MCB’s single pole of 6 to 32 Amps capacity, 'C' curve fixed in sheet metal board complete including connection complete all as specified and directed.
Supply and Fixing MCB’s single pole & neutral, 6 to 32 Amps capacity,'C' curve fixed in sheet metal board complete including connecting complete all as specified and directed.
Supply and fix wall mounted fan 400 mm sweep, 230 V 50 Hz, with all connected accessories, fixed as per manufacturer's instruction and connecting complete all as specified as directed.
Boring under roads/pavement/hardstanding without disturbing the top surface by trench less technology using ultra sound technique and necessary machine including HDPE pipe of 150 mm dia suitable for 0.4 mpa working pressure for passing through the cables complete all as specified and as directed. (Note : Necessary infrastructure reqd for boring shall be arranged by the Contractor at his own cost).
Taking electrical shut-down and dismantling LT feeder pillar of any size capacity and refixing & testing the same as directed at new location within 50 Mtr. Note:- Quoted rate included the fallowing:- (i) Transportation, Loading & Unloading is included. (ii) Additional Angle iron of size 50x50x6 mm for mounting feeder pillar is included. (iii) PCC works (1:2:4) is include. (iv) Contractor should ensure that LT feeder Pillar should be fixed at new location upto 1.2 mtr above ground level. (v) Two coats of synthetic enamel paints of grey colour (Duly spray paintings) internally & externally is included. (vi) All welding work, including necessary hings, door handles all included in the rate quoted by the contractor.
Supply, jointing connecting and testing, straight through joint, epoxy based complete with jointing material and all standard accessories suitable for XLPE insulated armoured aluminium conductor cable, LT 1100 Volts, aluminium conductor of 2 core 16 sqmm to 35 sqmm or 3core 16 to 25 or 4 core 10 to 16 sqmm. all as specified and as directed by Engineer-In-Charge.
All as per item no 34 above but suitable for (b) 35 sqmm to 50 Sqmm 3.5 core cable.
All as per item no 34 above but suitable for (c) 70 Sqmm to 95 Sqmm 3.5 core cable.
All as per item no 34 above but suitable for (d) 120 Sqmm to 150 Sqmm 3.5 core cable.
Material & Labour for point wiring for one light point controlled by one flame proof switch, complete with 1.5 Sqmm multi-stranded copper conductor PVC insulated, unsheathed, FR-LSH (Flame Retardant Low Smoke & Halogen) cable 1100 volts grade ISI marked drawn and including mild steel ERW conduit class B (ISI marked) not less than 20 mm dia, including all accessories like bend, tees, junction boxes etc. including 1.5 Sqmm......
........multi-stranded copper conductor PVC insulated, unsheathed, FR-LSH cable as a earth wire connected to common earth dolly, etc complete all as specified and directed. ( Note - S&F in repairs of flame proof switches, if any, shall be measured and paid for separately) Makes :- (a) Cable - NICCO / FINOLEX / L&T / RR KABEL / HAVELLS / POLYCAB / KEI/GLOSTER (b) Conduit with fittings - BHARAT/TATA/JINDAL/AKG/BEC /Prakash Surya/Tirupati/NIC
Supply and fix Switch flame proof rotary type with termination box in LM6, 16A, single pole 250V complete all as specified & directed.
Supply and fix flame proof and weather proof metal clad single pole and neutral with earth enclosure industrial plug and socket with suitable size of MCB SP 6 to 32 Amps C type, in aluminium alloy LM 6 Construction, certified by CMRS, Dhanbad for Group I, IIA, IIB, including necessary connection complete all as specified and directed.
Supply and fix Flame proof Ceiling fan 1200 mm in aluminium alloy LM 6 Construction , certified by CMRS , Dhanbad for Group I, IIA, IIB, complete all as specified and directed. Make:- Sudhir Cat No CF/193 or equivalent of make mention in Appx B
Supply and fix Flame proof fan regulators in aluminium alloy LM 6 Construction , certified by CMRS, Dhanbad for Group I, IIA, IIB, complete all as specified and directed. Make:- Sudhir Cat No RI/OA/1010 or equivalent of make mention in Appx B
Supply and fix flame proof exhaust fan of size 305 mm (12'') sweep 240 V 50 Hz ,1440 RPM single phase heavy duty complete with louver shutter and flame proof wire from ceiling rose to exhaust fan, complete all as specified & directed.
Supply and fix flame proof and weather proof industrial type DBs with various combination of incoming and outgoing MCB suitable for and including (a) 01 No MCB SPN 16 Amps, C type (incoming) (b) 1 Nos MCB SP 10 Amps C type(outgoing) type including necessary connection complete. Make:- Sudhir Cat No MCDB/186 or equivalent of make mention in Appx B
Materials & labour for XLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, cross-sectional area 120 sq. mm 3.5 core. Complete all as specified and directed.
Materials & labour for XLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, cross-sectional area 70 sq. mm 3.5 core. Complete all as specified and directed.
Materials & labour for XLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, cross-sectional area 35 sq. mm 3.5 core. Complete all as specified and directed.
S & F pole mounted junction box ( Street light boxes)side hinged-Door fixed to base with hinges for 3 phase 4 wire lighting system, moulded in FRP including provision of busbar insulator- 4 Nos with nut & bolts with fixing arrangement, outdoor type of dimesions 200 X 140X 95 mm. Make:GSJB- 2014 of Sintex or equivalent makes given in appendix 'B'.
Supply & installation of Air Cooled Inverter based split AC unit with cooling functions and suitable to operate at ambient conditions of (-10 to 46 Deg C in cooling Mode). Air conditioner will have following conditions:- (i) Refrigerant - R 410a (ii) EER - min 3.5 w/w (5 star rating) (iii) Tonnage - 2.0 (iv) Indoor Noise Level - Not more than 48 Db (v) Filter - (a) Must have PM 2.5 µ Filter (b) Electrostatic dust filter (c) Oxidizer dust filter
(vi) Functions of remote : (a) Air directional control (b) Auto Timer (c) Economic sleep mode (d) Auto fan speed (e) Auto swing (f) Temp display (g) Turbo mode All specification will be as per IS-1391 (Part 2) 1992 Room Air Conditioners Make: Carrier/ Hitachi/ O General
Note:- Following will be inclusive in rate:- (a) Piping length of 15 mtr will be inclusive in item (b) Installation will include fixing the outdoor unit on the platform as per direction of Engineer in Charge (c) Installation will also include civil work for making hole on the wall and putting the iron sleeve for passing the refrigerant pipe (d) Testing and commissioning of the Air conditioner to the entire satisfaction of Engineer in Charge
(e) Contractor will provide warranty of 5 years for compressor from the date of installation (f) 5% of Air conditioner will be tested by the Garrison Engineer for Energy Efficiency and all the functions provision in the Air conditioner (g) Contractor provide complete free service in warranty period by the company
Supply and installed voltage stabilizer for automatic operation single phase naturally air cooled indoor type and designed for input variation between 170V to 250V without voltage stabilized at 230V with accuracy of (+,-) 2.5 % and capacity 5 KVA .
Material & Labour for sub main wiring with 2 run single core multistranded copper conductor cable, of size 4 Sqmm each, PVC insulated, unsheathed, fire retardant, low smoke (FRLS) drawn through and including PVC conduit/casing capping and including one run single core multistranded copper conductor cable, of size 4 Sqmm, PVC insulated, unsheathed, fire retardant low smoke as earth wire, fixed on wall / ceiling complete. Note: 2 Runs of main cable and one run earth wire including cassing caping will be measured as one unit for payment.
S & F MCCB 63 Amps, 16 KA TPN 4 pole fixed in DB/Panel box complete all as specified and as directed.
Materials & labour for XLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, cross-sectional area 25 sq. mm 4 core. Complete all as specified and directed..
Supply and fix Test point terminal block made of gun metal or phosphorus bronze size of 75 mm x 75 mm x 25 mm drilled and screwed with 3 Nos 8 mm dia 25 mm long hexagonal headed screw, fixed in SMC junction box , fixed on wall complete all as specified and as directed.
Note : Supply and fix of SMC junction box of dimension (170x170x105)mm,shall be included in the quoted rate.
S t modi
Raj brothers
ambika electric co
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .