Loading…
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
Tender Value
₹44.9 L
EMD Value
₹89,810
Closing Date
10 Dec 2025, 2:30 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
Superintending Engineer
9, Institutional Area, Pankha Road, Janakpuri, New Delhi-110058
Operation and Comprehensive AMC of all type of electrical fixtures, high mast, pump sets i/c whole net work of electrical cable, panel, feeder pillar and other accessories at Fruit and Vegetable Market Gazipur for 2 years
2025_DAMB_282294_1
25(22)/375/2025/DAMB/Engg
Open Tender
Repair and Maintenance Services
Percentage
Fruit and Vegetable Market Gazipur
Please refer Tender documents.
14 documents required · 14 mandatory
₹0
₹89,810
Yes
20 May 2026
3 Dec 2025
10 Dec 2025
3 Dec 2025
10 Dec 2025
3 Dec 2025
Providing staff round the clock and T&P required for a period of one year for repair, maintenance and operation of all type of electrical fixtutres, fans, pumps, D.G. Sets, High Mast, electrical panels, feeder pillars, cables network and other accessories (as per list enclosed) installed at APMC office and F & V Gazipur. The minor items i.e. PVC tape, Nut bolt, washers, dhoti for execution work shall be provided by the contractors. The minimum staff to be deployed by the contractor shall be as under: a) Wireman Gd -I 2 No b) DG/Pump Operator 2 Nos
Comprehensive AMC of Below Mentioned DG set complete with all respect i.e. diesel engine,altrernator,battery charger,radiator,battery,fuel tank, control panel and all Major/minor parts of DG System.And servicing of DG set twice a year (Every 6 months or 500 Hrs running whichever is earlier) which included 1. Change of engine oil. 2. Change oil filter, fuel filter, bypass filter. 3. Change Air Filter. 4. Change water Separator 5. Radiator cleaning with chemical NOTE:- Diesel will be provided by department for day to day uses.
DG set 200 KVA capacity with control panel.
DG set 160 KVA capacity with control panel.
Operation & Comprehensive annual maintenance contract of Various Pumps Mentioned Below along with control panel i.c repair/ replacement of all major / minor parts.
3 HP Submersible Pump along with control panel- 1 Nos
5 HP Submersible Pump along with control panel- 2 Nos
25 HP Booster Pump along with control panel-3 Nos
5 HP Vaccuum Pump along with control panel- 2 Nos
3 HP Submerged Sewage Pump along with control panel- 1 Nos
12 HP Centrifgal Sewage Pump along with control panel- 2 Nos
5 HP Diesel Engine Pump along with control panel And servicing of DG pump twice a year (Every 6 months or 500 Hrs running whichever is earlier) which included 1. Change of engine oil. 2. Change oil filter, fuel filter, bypass filter. 3. Change Air Filter. Quantity - 1 No
Repair / Rewinding of ceiling fan / wall fan/Exhaust fan/Bracket fan including replacement of bearing, capacitor, shaft etc. as required.Schedule as below
Ceiling fan/wall fan
Exhaust fan
Bracket fan
Taking out of defective submersible pumpset from the borewell along with all pipes, submersible cable etc from a depth of Approx 60 mtrs as required.
Installation of submersible pumpset in the borewell along with all pipes,submersible cable etc at a depth of Approx 60 mtrs as required.
Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on wall surface as required.Upto 35 sq. mm (clamped with 1mm thick saddle)
Laying and fixing of one number PVC insulated and PVC sheathed/XLPE power cable of 1.1 KV grade of following size recessed in RCC /HUME/HDPE pipe in ground etc as required.
Upto 35 sq. mm
Above 35 sq. mm and upto 95 sq. mm
Supplying of following genuine & approved ISI marked material as and when required during contract period of one year. The price should be inclusive of all taxes, cartage etc. and should be valid for one year.
1.5 sq. mm ISI marked, FRLS PVC insulated, single core copper conductor cable
2.5 sq. mm ISI marked, FRLS PVC insulated,single core copper conductor cable
4.0 sq. mm ISI marked, FRLS PVC insulated,single core copper conductor cable
6.0 sq. mm ISI marked, FRLS PVC insulated,single core copper conductor cable
16 sq. mm ISI marked, FRLS PVC insulated,single core copper conductor cable
32 mm dia. ISI marked, PVC conduit
Ceiling rose, 3 pin, 5 amps ISI marked
S.P. 5/6 amps, one way modular switch, ISI marked
S.P. 15/16 amps, one way modular switch, ISI marked
3 pin 5/6 amps modular socket outlet, ISI marked
Modular bell push, ISI marked
Stepped type Modular Fan regulator (2 module)
Modular base & cover plate for 3 module
Modular base & cover plate for 4 module
Call bell/ buzzer, single phase
PVC Batten/ Angle Holder
4 pole MCCB,100A,30KA
4 pole MCCB, 200A, 36KA
4 pole MCCB,400A, 50KA
4 pole MCCB,630A, 50KA
6 amps. to 32 amps. ratings , SP MCB, “C” curve,10 KA breaking capacity
6 amps. to 32 amps. ratings , DP MCB, “C” curve,10 KA breaking capacity
63 amps., 4 pole isolator
12 way, SPN, double door, MCB DB
Aluminium lugs for 25 sq. mm cable
Aluminium lugs for 50 sq. mm cable
Aluminium lugs for 70 sq. mm cable
Aluminium lugs for 120 sq. mm cable
Straight through cable jointing kit with heat shrinkable kit with ferrules for 3½ X 35 sq. mm 1.1 KV grade cable
Straight through cable jointing kit with heat shrinkable kit with ferrules for 3½ X 50 sq. mm 1.1 KV grade cable
Straight through cable jointing kit with heat shrinkable kit with ferrules for 3½ X 70 sq. mm 1.1 KV grade cable
Straight through cable jointing kit with heat shrinkable kit with ferrules for 3½ X 95 sq. mm 1.1 KV grade cable
Straight through cable jointing kit with heat shrinkable kit with ferrules for 3½ X 120 sq. mm 1.1 KV grade cable
G.I. Hooks made of 8 SWG GI wire/ GI clip
Condenser 2.5 MFD
Tube Light 36 Watt LED Battern
Aluminium Cable, Un-Armoured 2 x10 Sq.mm
Aluminium Cable, Armoured 4x 25 Sq.mm
Aluminium Cable, Armoured 4x35 Sq.mm
Aluminium Cable, Armoured 4x95 Sq.mm
MCB 4 Pole 63 Amp
Supplying of 50 mm dia GI medium pipe with flanges welded on both sides in length of 3 mtrs.
Repair of 90 W - 120 W LED Flood Light
Repair of 200 W - 250 W LED Flood Light
Supply and fixing of Single phase junction box of size 140 mmx140 mmx95 mm along with the busbars, busbar supporter & M.S. clamps with nut bolts.
Buyback of released Ferrous material and cables
stage.html
html • 0.02 MB
cancelled_1.pdf
pdf • 0.14 MB
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 1.05 MB
BOQ_372985.xls
BOQ • 0.37 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .