Setting up of Government Medical College at Idukki Balance Electrical Works of Hospital Block
2025_KITCO_817237_1
HFWD/KITCO/EL/01/2025-26
Open Tender
Electrical Works
Item Rate
240 days
Idukki
As per tender
7 documents required · 7 mandatory
₹11,800
Yes
₹2 L
Yes
KITCO HO
30 Oct 2025
30 Oct 2025
17 Dec 2025
30 Oct 2025
15 Dec 2025
10 Nov 2025
30 Oct 2025 - 3 Nov 2025
6 Nov 2025
HT EQUIPMENTS
itemH294
itemH293
TRANSFORMER AND DG SETS
itemH295
itemH296
OD88523/2025-2026:EXHAUST PIPES; Supplying and fixing the following size exhaust gas piping ofsuitable dia, welded black M.S, B class pipe confirming to IS:3589 cut to requiredlengths and installed with necessary bends, supports and clamps, anti-vibrationmountings, insulation of exhaust system with mineralWool/ Rockwool 50 mm thickwire mesh & 0.63mm aluminium cladding etc., as required as perspecifications.suitable rain cap for top to avoid rain water entry. The distance between exhaustpipeat top and rain cap should be higher than diameter of pipe. Horizontal run ofexhaust piping shouldslope downwards away from engine to the condensate trap.Silencer should be installed with drainplug at bottom. Fixing shall be done withproper clamps, expansion bolts, and all other accessories as instructed by theEngineer and the rate inclusive of all minor civil works required, bolts, clamps etcasrequired for istallation. Support to exhaust piping should be done in such amanner that load ofexhaust piping is not exerted to turbo charger and the verticalrun of the pipes shall be provided withindirect supporting method so that when thepipes are hot and expanded they will be lifted into thesupports. Exhaust pipeheight shall be 3m more than the top of any adjacent building within 16mradius ofthe exhaust. Sizing shall be based on the backpressure calculation furnished bythe OEMand shall be approved by EIC. 150 dia exhaust pipe
OD88522/2025-2026:EXHAUST PIPES; Supplying and fixing the following size exhaust gas piping ofsuitable dia, welded black M.S, B class pipe confirming to IS:3589 cut to requiredlengths and installed with necessary bends, supports and clamps, anti-vibrationmountings, insulation of exhaust system with mineralWool/ Rockwool 50 mm thickwire mesh & 0.63mm aluminium cladding etc., as required as perspecifications.suitable rain cap for top to avoid rain water entry. The distance between exhaustpipeat top and rain cap should be higher than diameter of pipe. Horizontal run ofexhaust piping should slope downwards away from engine to the condensate trap.Silencer should be installed with drainplug at bottom. Fixing shall be done withproper clamps, expansion bolts, and all other acessories asinstructed by theEngineer and the rate inclusive of all minor civil works required, bolts, clamps etcasrequired for istallation. Support to exhaust piping should be done in such amanner that load ofexhaust piping is not exerted to turbo charger and the verticalrun of the pipes shall be provided withindirect supporting method so that when thepipes are hot and expanded they will be lifted into thesupports. Exhaust pipeheight shall be 3m more than the top of any adjacent building within 16mradius ofthe exhaust. Sizing shall be based on the backpressure calculation furnished bythe OEMand shall be approved by EIC. 200 dia exhaust pipe
TPN SANDWITCH BUSDUCT
OD89133/2025-2026:Supply installation, testing and commissioning of Tap of Unit Tap of Unit with MCCB (Plug in box) 160A, 36kA 4P Thermal magnetic release type MCCB suitable for sandwich type busduct<br>
OD89132/2025-2026:Supply, installation, testing and commissioning of Tap of Unit with MCCB (Plug in box) 63A, 36kA 4P Thermal magnetic release type MCCB suitable for sandwich type busduct.<br>
itemH298
itemH297
LT PANEL BOARDS AND ACCESSORIES
OD88315/2025-2026:11KV/0.433KV, 1600KVA Dry Type Transformer (Supplied & Installed as per previous contract) Maintenance, Servicing, Calibration, Testing and Commissioning of Indoor type 1600 kVA, 11kV/433V 3Ph, 50 Hz, dry type, vector DYN-11 Transformer, copper wound, Class F insulation, indoor distribution Transformer with IP23 enclosure (Unipower make) available at site. The transformer shall connected Delta on HV side and Star on LV side with On Load Tap Changer in steps of + 5% to -15% in steps of 2.5 with RTCC and AVR. The transformer shall have neutral CT with suitable enclosure on earthed star point with connector for connection to low set earth fault relay, REF relay provided in HT/LT panel, winding temperature alarm and trip, The enclosure shall be IP 23 protection and having HV cable box suitable for termination of HT XLPE cable and LV chamber suitable for termination of busduct and complete with all standard fittings and accessories etc including necessary louvers with cooling fan/duct as required complete and as per specifications attached in all respects as required and necessary control cabling for alarm, tripping & indication as required. Voltage Ratio: 11/0.433 kV Type
OD88525/2025-2026:Supply, Installation, Testing and Commissioning of indoor type 500KVA (or nearest higher rated) water cooled, radiator type, four stroke, electric start prime duty D.G Set with acoustic enclosure in conformity with CPCB IV+ requirement with indoor type standard control panel consisting of ACB, relays, meters, indication lamps etc. suitable for AMF operation from the MSB panel with AMF operation, load sharing and load management facilities and the DG sets shall be compatible for synchronisation. The alternator shall be brushless, self excited, self regulated, suitable for continuous operation at 1500 rpm, generating 415 V +/- 1% at 0.8 p.f, 50Hz, 3 phase, 4 wire system generally conforming to BS: 5514 & ISO: 3046. Both engine and alternator shall be mounted on common channel iron base frame, and with standard accessories such as antivibration pad, sealed maintenance free batteries (or as specified by engine manufacturer) and engine driven battery charger along with leads, battery stand etc. A seperate battery charger with trickle and boost charge facilities shall also be supplied along with each DG set. Integrated fuel tank suitable for 8 hours of operation with necessary fuel pipe from fuel tank to engine etc. complete with residential type silencer. Appropriate size cable terminal box shall be provided for terminating 3 No. of 3.5x400 sq mm XLPE insulated and PVC sheathed armoured aluminium conductor cable without strain at alternator side and control panel side. The DG set shall match the requirements as per the attached single line diagram & detailed technical specifications. Rate shall be inclusive of all lift, lead etc. The work should be done as per BIS and in compliance with CEA & Kerala State Pollution control board norms.
OD89204/2025-2026:Enclosure with MCCB - Supply Installation , Testing & Commissioning of following capacities of MCCB inside sheet enclosure fabricated from 1.60 mm CRCA sheet duly powder coated with all necessary accessories.250 A, 36 kA, 415 V, FP MCCB with OL and SC protections
OD88524/2025-2026:EXHAUST PIPES; Supplying and fixing the following size exhaust gas piping ofsuitable dia, welded black M.S, B class pipe confirming to IS:3589 cut to requiredlengths and installed with necessary bends, supports and clamps, anti-vibrationmountings, insulation of exhaust system with mineralWool/ Rockwool 50 mm thickwire mesh & 0.63mm aluminium cladding etc., as required as perspecifications.suitable rain cap for top to avoid rain water entry. The distance between exhaustpipeat top and rain cap should be higher than diameter of pipe. Horizontal run ofexhaust piping shouldslope downwards away from engine to the condensate trap.Silencer should be installed with drainplug at bottom. Fixing shall be done withproper clamps, expansion bolts, and all other acessories asinstructed by theEngineer and the rate inclusive of all minor civil works required, bolts, clamps etcasrequired for istallation. Support to exhaust piping should be done in such amanner that load ofexhaust piping is not exerted to turbo charger and the verticalrun of the pipes shall be provided withindirect supporting method so that when thepipes are hot and expanded they will be lifted into thesupports. Exhaust pipeheight shall be 3m more than the top of any adjacent building within 16mradius ofthe exhaust. Sizing shall be based on the backpressure calculation furnished bythe OEMand shall be approved by EIC. 250 dia exhaust pipe
3.13.3:Supplying, installing by suspension on ceiling/ along the wall, testing and commissioning of following capacity Sandwich Type Rising Mains for use on 3 phase 4 wire 415 volts, 50Hz A.C. supply with metal clad enclosure having IP-54 rating after fixing the tap off boxes and all accessories, made of 1.6mm thick steel sheet duly powder coated in convenient sections complete with 4 Nos aluminium bus bars having current density of 130 A/ sq cm at nominal current rating, necessary joints, elbow joints & expansion joints and bends, fire barrier at each floor, provision of tapping at every meter, adopter box and copper flexible for joints, continuous earthing with 2 Nos aluminium strip of suitable size (one on each side) including, G.I. clamping brackets, suspenders, angle iron bracket, steel fasteners. connecting to earthing system etc. as required 630 amps 50 KA SC for 1 sec
OD89129/2025-2026:Supply, installation, testing and commissioning of 250A, 415V, 40 kA, 50Hz, AC 4 Pole Sandwich Aluminum Bus Duct with 100% neutral bus made out of 14 SWG powder coated and painted extruded aluminum in IP54 enclosure complete with flexible end terminations, fittings & accessories like elbows, offset sections, tees, reducers, adaptor boxes, flanges, flexible connections , expansion joints, ground strips, OEM recommended supporting system, continuous earthing with 2 runs of 25x3 mm Cu earth strip etc. as required complete. (The rate shall be quoted for running meter and the elbows, bends, adaptor boxes are also measured under running meter and the rate shall be inclusive all associated accessories)
OD99957/2025-2026:Supply of surface/Suspended Mounted LED Batten of maximum wattage below 40W with System efficacy of more than 120 lm/W and lumen output of luminaire greater than 4000 lumen. LED luminaire shall have sleekdesign with Extruded Aluminum Section. The luminaire shall have Optically Efficient Polycarbonate Diffuser for Uniform illumination and wider light distribution. The LED shall be compliant with LM80 standard with Useful L70 life of 50000 Hrs tested at maximum current. The CRI >80 and 4 KV internal surge protection. Power factor greater than 0.95, CCT 5700K+/-300K, ripple factor<5 and total harmonic distortion (THD) of less than 10% should be integral to the luminaire and EMI/EMC compatible.
3.13.9:Supplying, installing by suspension on ceiling/ along the wall, testing and commissioning of following capacity Sandwich Type Rising Mains for use on 3 phase 4 wire 415 volts, 50Hz A.C. supply with metal clad enclosure having IP-54 rating after fixing the tap off boxes and all accessories, made of 1.6mm thick steel sheet duly powder coated in convenient sections complete with 4 Nos aluminium bus bars having current density of 130 A/ sq cm at nominal current rating, necessary joints, elbow joints & expansion joints and bends, fire barrier at each floor, provision of tapping at every meter, adopter box and copper flexible for joints, continuous earthing with 2 Nos aluminium strip of suitable size (one on each side) including, G.I. clamping brackets, suspenders, angle iron bracket, steel fasteners. connecting to earthing system etc. as required 2500 amps 50 KA SC for 1 sec
OD89207/2025-2026:Supply, Installation, Testing and Commissioning of 125 kVA or nearest higher available rating UPS in N+1 arrangement, three phase input, three phase output, true on-line modular UPS system with 30 minutes back up at unity pf, including all required accessories, SMF batteries VRLA type with powder coated CRCA cabinet including all accessoriessuch as cabling etc. asrequired complete having following specification. The UPS system shall be with multiple units of modular units (with a combination to maintain N+1 configuration with a total rating of minimum 125 kVA) and must have a minimum N+1 rack for mounting UPS modules with hots swappable. The set of battery bank shall be mounted in battery racks. Fully digital controlled based on DSP with DPA architects (Each Modules should have Inverter, rectifier, charges, static bypass etc) Output shall be pure sine wave, power factor 0.95. Full time output voltage & frequency regulation. Auto regulation of battery end voltage Intelligent interface with LED/LCD display switch for manual bypass, auto temperature compensation etc. as required. true on-line UPS system with THDv <1% in nonlinear load, and 97% efficiency at 50-75% load, compliance to IEC 62040-1 for general Safety, compliance to IEC 62040-2 for Electromagnetic Compatibility, including all accessories, as per the detailed technical specifications.( The system shall be complete with battery rack, isolator and Interconnecting cables.)
OD89206/2025-2026:STREET LIGHTING SYSTEM Outdoor Lighting Panel (ODP)Supply, Installation, Testing and Commissioning of Outdoor Lighting Panel (ODP) cubicle type, totally enclosed, IP 65, ,IK-08 free standing, floor mounting, dust and vermin proof, water proof suitable for operation on 3 phase, 415 V, 50Hz AC supply with provision for fixing in
OD100820/2025-2026:Supply and fixing of IP65 & IK08 LED surface mounted Bulkhead fixture with System efficacy of more than 120lm/W. Luminaire shall be made up of Die Cast Aluminium for efficient heat dissipation. Luminaire shall have Poly carbonate diffuser for Uniform illumination and wider light distribution. The LEDs used should be with CCT of 5000-6000K and CRI >80, Power factor greater than 0.95 and total harmonic distortion (THD) of less than 10% including all accessories necessary as required to complete installation
coming & outgoing switches fabricated using Polycarbonate boxes, including internal wiring with suitable size wires/cable, interconnection etc., The panel shall be fabricated from a firm having CPRI certification with test certificates for similar panel (required for short circuit rating, temperature rise and IP classification) including following switchgears accessories for the LT Panel.(Ref Drawing No.DP 667 DRG EL 02 002 Sheet 2 of 10 and technical specification for more details ).INCOMERSurge Arrestor Type 1+2 Combination- 1 Set63 A, FP, 36kA, MCCB with adjustable thermal magnetic release with OL & SC protection - 1 NoBUSBARS63 Amp TPN busbars of high conductivity electrolytic quality aluminium alloy - 1 SetINSTRUMENTS4A, C curve SP MCB - 3 Nos.RYB indication lamp, LED type - 1 SetVoltage Surge Protector-1 Nos24 hrs Digital time switch with inbuilt battery - 3 Nos.25A, AC-1 contactor - 3 NosOUTGOINGS25 A, FP RCCB (100mA)-3Nos25 A C Curve FP MCB-3 Nos
OD89205/2025-2026:Enclosure with MCCB - Installation , Testing & Commissioning of following capacities of MCCB inside sheet enclosure fabricated from 1.60 mm CRCA sheet duly powder coated with all necessary accessories. (Department Supply)-630 A, 50 kA, 415V, FP MCCB with OL and SC protections
90.14.8.1:800 A, 3 pole, manual draw out type, microprocessor based ACB with overload , instantaneous SC , delayed SC and ground fault protection 50kA
CABLES AND CABLING HT CABLING
OD91666/2025-2026:LPSSB (LPSSB-OP-GF, LPSSB-OP-FF, LPSSB-OP-SF) -(Supplied & Installed as per previous cont
10.3.4:Supplying and making straight through cable jointing with cast resin compound, including ferrule and other jointing materials, for following size of 3 core, XLPE aluminium conductor cable of 11 KV grade as required:300 sq. mm
10.4.4:Supplying and making indoor cable end termination with heat shrinkable jointing kit complete with all accessories including lugs suitable for following size of 3 core, XLPE aluminium conductor cable of 11 KV grade as required:300 sq. mm
OD92273/2025-2026:Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 11 KV grade of 300sq mm through Horizontal Drilling Method with HDP Pipes
OD92272/2025-2026:Excavation for entry/exit pits in Tarr/Berm/Concrete road/landscape and Installation of 2 nos of 160 mm HDPE pipe using using HDD (Horizontal Directional Drilling) method in accordance with requirements of laying of power lines at min 1000mm depth from ground level, Back fill of entry/exit pits after pipe installation.
OD91658/2025-2026:AC Plant MCC (AC-SSB) (Supplied & Installed as per previous contract)Shifting ,leading from GF to 6th Floor ,Installation, Maintenance, Sevicing, Calibration, Testing & Commissioning of AC Plant MCC , cubicle type, made out of 2mm thick CRCA sheet,totally enclosed, IP 42, free standing, floor mounting, dust and vermin proof, indoor, compartmentalised, conforming to form 4B construction suitable for operation on 3 phase , 415 V, 50Hz AC system with busbars , including internal wiring with suitable size wires/cable, interconnection, duly powder coated with seven tank process etc., including following components as per drawing and technical specifications.(Ref Drawing No.DP 667 DRG EL 02 002 Sheet3 of 10 and technical specification for more details ).Incomer 800A, TP+NL, 35 KA, Electrical Draw Out type ACB with microprocessor based adjustable overcurrent and earth fault re
OD92285/2025-2026:Supply of following size 1.1 KV grade XLPE insulated, PVC sheathed, armoured Aluminium conductor cable conforming to IS 7098 (Part 1) amended upto date.<br>4C 25 Sq.mm AL
OD92268/2025-2026:Supply of following sizes of XLPE insulated PVC sheathed, Aluminium conductor armoured power cable of 11 KV grade conforming to IS 7098 amended upto date. 3C 300 Sq. mm Al<br>
OD92269/2025-2026:Supply of 3.5C 240 Sq.mm size 1.1 KV grade XLPE insulated, PVC sheathed,<br>armoured aluminium conductor cable conforming to IS 7098 (Part 1) amended upto date
10.5.4:Supplying and making outdoor cable end termination with heat shrinkable jointing kit complete with all accessories including lugs suitable for following size of 3 core, XLPE aluminium conductor cable of 11 KV grade as required :300 sq. mm
8.1.2:Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 11 KV grade of following size direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc as required.Above 120 sq. mm and upto 400 sq. mm
OD92296/2025-2026:Supply of 12C 2.5 sqmm Cu 1.1 KV grade XLPE insulated, PVC sheathed, armoured copper conductor cable conforming to IS 7098 (Part 1) amended upto date.
OD92460/2025-2026:Supply of 5C 2.5 sqmm Cu 1.1 KV grade XLPE insulated, PVC sheathed, armoured copper conductor cable conforming to IS 7098 (Part 1) amended upto date.
OD92461/2025-2026:Supply of following 4C 2.5 Sq.mm Cu size 1.1 KV grade XLPE insulated, PVC sheathed, armoured copper conductor cable conforming to IS 7098 (Part 1) amended upto date.
OD92459/2025-2026:Supplying and making straight through joint with heat shrinkable kit including ferrules and other jointing materials for following
8.3.2:Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 11 KV grade of following size in the existing RCC/ HUME/ METAL pipe as required.Above 120 sq. mm and upto 400 sq. mm
OD92276/2025-2026:Supply of 3.5C 120 Sq.mm Al size 1.1 KV grade XLPE insulated, PVC sheathed, armoured Aluminium conductor cable conforming to IS 7098 (Part 1) amended upto date
OD92277/2025-2026:Supply of 3.5C 70 Sq.mm size 1.1 KV grade XLPE insulated, PVC sheathed,armoured Aluminium conductor cable conforming to IS 7098 (Part1)amended upto date
OD92278/2025-2026:Supply of 3.5C 35 Sq.mm Al size 1.1 KV grade XLPE insulated, PVC sheathed, armoured Aluminium conductor cable conforming to IS 7098 (Part 1) amended upto date
OD92287/2025-2026:Supply of 4C 16 Sq.mm Al size 1.1 KV grade XLPE insulated, PVC sheathed, armoured Aluminium conductor cable conforming to IS 7098 (Part 1) amended upto date
OD92286/2025-2026:Supply of 4C 6 Sq.mm Al size 1.1 KV grade XLPE insulated, PVC sheathed,armoured Aluminium conductor cable conforming to IS 7098 (Part 1) amendedupto date
OD92300/2025-2026:Supply of 3C 10 Sq.mm size 1.1 KV grade XLPE insulated, PVC sheathed,armoured aluminium conductor cable conforming to IS 7098 (Part 1)amended upto date
OD92299/2025-2026:Supply of following size 1.1 KV grade XLPE insulated, PVC sheathed, armoured Aluminium conductor cable conforming to IS 7098 (Part 1) amended upto date 3C 6 Al
OD92298/2025-2026:Supply of following 3C 4 Sq.mm Al size 1.1 KV grade XLPE insulated, PVC sheathed, armoured aluminium conductor cable conforming to IS 7098 (Part 1) amended upto date.
OD92297/2025-2026:Supply of 2C 6 Sqmm Al size 1.1 KV grade XLPE insulated, PVC sheathed, armoured aluminium conductor cable conforming to IS 7098 (Part 1) amended upto date.
7.1.1:Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc as required.Upto 35 sq. mm
7.1.2:Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc as required.Above 35 sq. mm and upto 95 sq. mm
7.1.3:Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc as required.Above 95 sq. mm and upto 185 sq. mm
7.1.4:Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc as required.Above 185 sq. mm and upto 400 sq. mm
7.2.1:Laying of one number additional PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade
of following size direct in ground in the same trench in one tier horizontal formation including excavation, sand cushioning, protective covering and refilling the trench etc as required.Upto 35 sq. mm
7.2.2:Laying of one number additional PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground in the same trench in one tier horizontal formation including excavation, sand cushioning, protective covering and refilling the trench etc as required.Above 35 sq. mm and upto 95 sq. mm
7.2.3:Laying of one number additional PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground in the same trench in one tier horizontal formation including excavation, sand cushioning, protective covering and refilling the trench etc as required.Above 95 sq. mm and upto 185 sq. mm
7.2.4:Laying of one number additional PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground in the same trench in one tier horizontal formation including excavation, sand cushioning, protective covering and refilling the trench etc as required.Above 185 sq. mm and upto 400 sq. mm
7.5.1:Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing RCC/ HUME/ METAL pipe as required.Upto 35 sq. mm
7.5.2:Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing RCC/ HUME/ METAL pipe as required.Above 35 sq. mm and upto 95 sq. mm
7.5.3:Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing RCC/ HUME/ METAL pipe as required.Above 95 sq. mm and upto 185 sq. mm
7.5.4:Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing RCC/ HUME/ METAL pipe as required.Above 185 sq. mm and upto 400 sq. mm
7.7.1:Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on wall surface as required.Upto 35 sq. mm (clamped with 1mm thick saddle)
7.7.2:Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on wall surface as required.Above 35 sq. mm and upto 95 sq. mm (clamped with 25x3mm MS flat clamp)
7.7.3:Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on wall surface as required.Above 95 sq. mm and upto 185 sq. mm (clamped with 25/40x3mm MS flat clamp)
7.7.4:Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on wall surface as required.Above 185 sq. mm and upto 400 sq. mm (clamped with 40x3mm MS flat clamp)
7.8.1:Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on cable tray as required.Upto 35 sq. mm (clamped with 1mm thick saddle)
7.8.2:Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on cable tray as required.Above 35 sq. mm and upto 95 sq. mm (clamped with 25x3mm MS flat clamp)
7.8.3:Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on cable tray as required.Above 95 sq. mm and upto 185 sq. mm (clamped with 25/40x3mm MS flat clamp)
7.8.4:Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on cable tray as required.Above 185 sq. mm and upto 400 sq. mm (clamped with 40x3mm MS flat clamp)
size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. 3.5C X 400 Sq. mm. Cable
OD93053/2025-2026:Supplying and making end termination with brass compression gland and aluminium/Copper lugs for following size of XLPE insulated PVC sheathed aluminium/copper conductor cable of 1.1 kV grade as required.4C 2.5 sqmm Cu
OD93052/2025-2026:Supplying and making end termination with brass compression gland and aluminium/Copper lugs for following size of XLPE insulated PVC sheathed aluminium/copper conductor cable of 1.1 kV grade as required.5C 2.5 sqmm Cu
OD93051/2025-2026:Supplying and making end termination with brass compression gland and aluminium/Copper lugs for following size of XLPE insulated PVC sheathed aluminium/copper conductor cable of 1.1 kV grade as required.12C 2.5 sqmm Cu
OD93050/2025-2026:Supplying and making end termination with brass compression gland and aluminium/Copper lugs for following size of XLPE insulated PVC sheathed aluminium/copper conductor cable of 1.1 kV grade as required.3C 4 Sq.mm Al
14.13.1:Providing, laying and fixing following dia G.I. pipe (medium class) in ground complete with G.I. fittings including trenching (75 cm deep)and re-filling etc as required50 mm dia
OD93068/2025-2026:Supplying and making end termination with brass compression gland and aluminium/Copper lugs for following size of XLPE insulated PVC sheathed aluminium/copper conductor cable of 1.1 kV grade as required.4C 6 Sq.mm Al
OD93067/2025-2026:Supplying and making end termination with brass compression gland and aluminium/Copper lugs for following size of XLPE insulated PVC sheathed aluminium/copper conductor cable of 1.1 kV grade as required.3C 6 Sq.mm Al
14.13.3:Providing, laying and fixing following dia G.I. pipe (medium class) in ground complete with G.I. fittings including trenching (75 cm deep)and re-filling etc as required100 mm dia
14.13.4:Providing, laying and fixing following dia G.I. pipe (medium class) in ground complete with G.I. fittings including trenching (75 cm deep)and re-filling etc as required150 mm dia
14.14.1:Providing, laying and fixing following dia RCC pipe NP2 class (light duty) in ground complete with RCC collars, jointing with cement mortar 1:2 (1 cement : 2 fine sand) including trenching (75 cm deep) and refilling etc as required.100 mm dia
14.14.2:Providing, laying and fixing following dia RCC pipe NP2 class (light duty) in ground complete with RCC collars, jointing with cement mortar 1:2 (1 cement : 2 fine sand) including trenching (75 cm deep) and refilling etc as required.150 mm dia
4.10.1:Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray "Reducer" (galvanisation not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc as required.100 mm width x 50 mm depth x 1.6 mm thickness
4.10.3:Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray "Reducer" (galvanisation not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc as required.900 mm width X 75 mm depth X 2.0 mm thickness
4.10.4:Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray "Reducer" (galvanisation not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc as required.300 mm width x 50 mm depth x 1.6 mm thickness
4.10.6:Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray "Reducer" (galvanisation not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc as required.450 mm width x 50 mm depth x 2.0 mm thickness
9.1.1:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.2 X 6 sq. mm (19mm)
9.1.20:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 1/2X25 sq.mm (28mm)
9.1.21:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 1/2X 35 sq. mm (32mm)
9.1.23:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 1/2X 70 sq. mm (38mm)
9.1.25:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 1/2 X 120 sq. mm (45mm)
4.10.7:Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray "Reducer" (galvanisation not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc as required.600 mm width x 50 mm depth x 2.0 mm thickness
4.7.1:Supplying and installing following size of perforated Hot Dipped Galvanized Iron cable tray "bends" (galvanization not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc. as required.100mm width X 50 mm depth X 1.6mm thickness
4.7.3:Supplying and installing following size of perforated Hot Dipped Galvanized Iron cable tray "bends" (galvanization not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc. as required.225mm width X 50mm depth X 1.6 mm thickness
4.7.6:Supplying and installing following size of perforated Hot Dipped Galvanized Iron cable tray "bends" (galvanization not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc. as required.450mm width X 50mm depth X 2 mm thickness
4.7.7:Supplying and installing following size of perforated Hot Dipped Galvanized Iron cable tray "bends" (galvanization not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc. as required.600mm width X 50mm depth X 2 mm thickness
4.7.8:Supplying and installing following size of perforated Hot Dipped Galvanized Iron cable tray "bends" (galvanization not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc. as required.300mm width X62.5mm depth X 2.0 mm thickness
4.8.1:Supplying and installing following size of perforated Hot Dipped Galvanized Iron cable tray "Tee" (galvanization not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc. as required.100 mm width X 50 mm depth X 1.6 mm thickness
4.8.3:Supplying and installing following size of perforated Hot Dipped Galvanized Iron cable tray "Tee" (galvanization not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc. as required.225 mm width X 50 mm depth X 1.6 mm thickness
4.8.4:Supplying and installing following size of perforated Hot Dipped Galvanized Iron cable tray "Tee" (galvanization not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc. as required.300 mm width X 50 mm depth X 1.6 mm thickness
4.8.6:Supplying and installing following size of perforated Hot Dipped Galvanized Iron cable tray "Tee" (galvanization not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc. as required.450mm width X 50 mm depth X 2.0 mm thickness
4.8.7:Supplying and installing following size of perforated Hot Dipped Galvanized Iron cable tray "Tee" (galvanization not less than 50 microns) wi
th perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc. as required.600 mm width X 50 mm depth X 2mm thickness
4.9.1:Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray "Cross member" (galvanisation not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc as required.100 mm width x 50 mm depth x 1.6 mm thickness
4.9.3:Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray "Cross member" (galvanisation not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc as required.225 mm width x 50 mm depth x 1.6 mm thickness
4.9.4:Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray "Cross member" (galvanisation not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc as required.300 mm width x 50 mm depth x 1.6 mm thickness
4.9.6:Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray "Cross member" (galvanisation not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc as required.450 mm width x 50 mm depth x 2.0 mm thickness
4.9.7:Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray "Cross member" (galvanisation not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc as required.600 mm width x 50 mm depth x 2.0 mm thickness
7.9:Supplying and making cable route marker with cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size ) of size 60 cm X 60 cm at the bottom and 50 cm X 50 cm at the top with a thickness of 10cm including inscription duly engraved as required.
7.10:Supplying and fixing cable route marker with 10 cm X 10 cm X 5 mm thick G.I. plate with inscription there on, bolted /welded to 35 mm X 35 mm X 6 mm angle iron, 60 cm long and fixing the same in ground as required.
9.1.27:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 1/2X 185 sq. mm (57mm)
90.12.9.10:Supplying, laying and jointing of the following sizes of double wall corrugated (DWC) pipes made out of HDPE conforming to IS 14930 Part II for mechanical protection to underground power cables with all required accessories in ground in the existing trench160/135 mm or nearest size
OD93346/2025-2026:Clean Agent Modular type Ceiling mounted Fire Extinguisher of 5 Kg Capacity, suitable for Class A, B and C of Fire complete in all respect with Charge of Clean agent Gas - HFC Blend A, blend of Hydro Fluorocarbon and organic detossificant essence P26. The sprinkler body will comprise of temperature sensitive quartsoid bulb of temperature rating of 68 Degree Celsious. Make: STENTOR
OD93348/2025-2026:Supply and fixing of chequered plate of 6 mm thick including cutting to required size using gas cutter and lay the same over the trench, fixing of nosing angle and supports for chequered plate, related civil works, finishing etc. and painting with two coats of enamel paint over one coat of Zinchromate primer as required.
OD93349/2025-2026:Installing following size of perforated Hot Dipped Galvanised Iron cable tray cable tray with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc as required.100 MM WIDTH X 50 MM DEPTH X 1.6 MM THICK
OD93350/2025-2026:Installing following size of perforated Hot Dipped Galvanised Iron cable tray cable tray with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc as required.225 MM WIDTH X 50 MM DEPTH X 1.6 MM THICK
OD93351/2025-2026:Installing following size of perforated Hot Dipped Galvanised Iron cable tray cable tray with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc as required.300 MM WIDTH X 50 MM DEPTH X 2 MM THICK
OD93352/2025-2026:Installing following size of perforated Hot Dipped Galvanised Iron cable tray cable tray with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc as required.450 MM WIDTH X 50 MM DEPTH X 2 MM THICK
OD93353/2025-2026:Installing following size of perforated Hot Dipped Galvanised Iron cable tray cable tray with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc as required.600 MM WIDTH X 50 MM DEPTH X 2 MM THICK
OD93354/2025-2026:Installing following size of perforated Hot Dipped Galvanised Iron cable tray “bends “ ( galvanisation not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc as required.100 MM WIDTH X 50 MM DEPTH X 1.6 MM THICK
OD93355/2025-2026:Installing following size of perforated Hot Dipped Galvanised Iron cable tray “bends “ ( galvanisation not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc as required.225 MM WIDTH X 50 MM DEPTH X 1.6 MM THICK
OD93356/2025-2026:Installing following size of perforated Hot Dipped Galvanised Iron cable tray “bends “ ( galvanisation not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc as required.300 MM WIDTH X 50 MM DEPTH X 2 MM THICK
9.1.29:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 1/2X 240 sq. mm (62mm)
9.1.31:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 1/2X 400 sq. mm (82mm)
9.1.32:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.4 X 10 sq. mm (25mm)
OD93357/2025-2026:Installing following size of perforated Hot Dipped Galvanised Iron cable tray “bends “ ( galvanisation not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc as required.450 MM WIDTH X 50 MM DEPTH X 2 MM THICK
OD93358/2025-2026:Installing following size of perforated Hot Dipped Galvanised Iron cable tray “bends “ ( galvanisation not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc as required.600 MM WIDTH X 50 MM DEPTH X 2 MM THICK
9.1.33:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.4 X 16 sq. mm (28mm)
9.1.7:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 X 10 sq. mm (22mm)
4.6.1:Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc as required. 100 mm width X 50mm depth X 1.6 mm thickness
4.6.3:Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc as required. 225 mm width X 50 mm depth X 1.6 mm thickness
4.6.4:Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc as required. 300 mm width X 50 mm depth X 1.6 mm thickness
OD93362/2025-2026:Installing following size of perforated Hot Dipped Galvanised Iron cable tray “Tee” ( galvanisation not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc as required.450 MM WIDTH X 50 MM DEPTH X 2 MM THICK
OD93363/2025-2026:Installing following size of perforated Hot Dipped Galvanised Iron cable tray “Tee” ( galvanisation not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc as required.600 MM WIDTH X 50 MM DEPTH X 2 MM THICK
OD93369/2025-2026:Installing following size of perforated H
ot Dipped Galvanised Iron cable tray “Reducer” ( galvanisation not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc as required.100 MM WIDTH X 50 MM DEPTH X 1.6 MM THICK
OD93370/2025-2026:Installing following size of perforated Hot Dipped Galvanised Iron cable tray “Reducer” ( galvanisation not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc as required.225 MM WIDTH X 50 MM DEPTH X 1.6 MM THICK
OD93371/2025-2026:Installing following size of perforated Hot Dipped Galvanised Iron cable tray “Reducer” ( galvanisation not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc as required.300 MM WIDTH X 50 MM DEPTH X 2 MM THICK
OD93372/2025-2026:Installing following size of perforated Hot Dipped Galvanised Iron cable tray “Reducer” ( galvanisation not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc as required.450 MM WIDTH X 50 MM DEPTH X 2 MM THICK
4.6.6:Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc as required. 450 mm width X 50 mm depth X 2.0 mm thickness
OD93373/2025-2026:Installing following size of perforated Hot Dipped Galvanised Iron cable tray “Reducer” ( galvanisation not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc as required.600 MM WIDTH X 50 MM DEPTH X 2 MM THICK
OD93374/2025-2026:Fabrication, supply and installation of following size of Ladder type GI hot dip galvanised cable tray including horizontal and vertical reducers, tees, cross members and other accessories as required and duly suspended from the ceiling with MS suspenders and painting etc as required600 MM WIDTH X 50 MM DEPTH X 2 MM THICK
OD93375/2025-2026:Fabrication, supply and installation of following size of Ladder type GI hot dip galvanised cable tray including horizontal and vertical reducers, tees, cross members and other accessories as required and duly suspended from the ceiling with MS suspenders and painting etc as required450 MM WIDTH X 50 MM DEPTH X 2 MM THICK
4.6.7:Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc as required. 600mm width x 50 mm depth x 2.0 mm thickness
OD93347/2025-2026:Supply and installation of Fire Barrier mortar with minimum 2 (two) hours fire rating when tested in accordance with UL 1479 standards, for fire rated vertical openings in floors or slabs and floors made of concrete, masonry, meta
EARTHING AND SAFETY EQUIPMENTS
OD94369/2025-2026:Installation, Testing & Commissioning of maintenance free earthing system using the already supplied 3 mtrs length, 20mm dia 250 microns molecularly copper bonded steel rod with stainless steel connectors and fasteners for connecting earth strip, earth enhancing compound (12.5 kg mineral compound / 22.6 kg low resistivity graphite compound), FRP (UFE FRP) earth electrode inspection chamber with heavy duty cover of 300mmx 300mmx 300mm dimension havinng bearing capacity of 15KN etc as required. The rate shall be inclusive of installation charges, including digging bore, providing all required accessories like terminal connector, screw for fixing earth pit cover etc
OD94370/2025-2026:Supply, Installation, Testing & Commissioning of all the materials required for maintenance free earthing system including 3 mtrs length, 20mm dia 250 microns molecularly copper bonded steel rod with stainless steel connectors and fasteners for connecting earth strip, earth enhancing compound (12.5 kg mineral compound / 22.6 kg low resistivity graphite compound), FRP (UFE FRP) earth electrode, inspection chamber with heavy duty cover of 300mmx 300mmx 300mm dimension havinng bearing capacity of 15KN etc as required.The rate shall be inclusive of installation charges,including digging bore, providing all required accessories like terminal connector, screw for fixing earth pit cover etc. as required
90.16.1.3:Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required3.15 mm copper conductor ( 10 SWG)
5.14:Providing and fixing 25 mm X 5 mm copper strip on surface or in recess for connections etc. as required.
5.15:Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for connections etc. as required.
OD94429/2025-2026:Laying following GI or copper strip (tinned at the points of contacts) / wire on the surface/recess with mounting saddles for conductor earth electrode including welding etc as required.-25mm x 5 mm GI
OD94428/2025-2026:Supplying and laying following GI or copper strip(tinned at the points of contacts) / wire at 0.6m below ground level including excavation and refilling for conductor earth electrode including welding etc as required.40mm X10mm GI
l, gypsum partition, after passing service lines like Cable, Cable trays, Bus Duct or Metal pipes. The mortar shall be a light weight cementitious product and shall carry test certificate in accordance with IEC 60068-2-57:1999-11 (Environmental Testing) as per Part 2-57: Test for Vibration- Time-history method and VERTEQII for seismic zone 4. Expanding fire stop foam with minimum 2-hour fire rating when tested in accordance with UL 1479 standards, shall be used to seal areas that are highly dense or are not accessible and cannot be sealed with fire stop mortar properly. The expanding foam shall expand minimum seven times its volume to fill the cavity at the time of dispensing the material and shall fully cure within two minutes after dispensing. The expanding foam shall also be repenetratable. The products shall be age tested as per Dafstb and DIBT standards. The products shall carry test certificate for mold resistance rating of 0 as determined by ASTM G21-96. The products shall be UL listed & classified and shall bear the UL approval logo on the packing. Engineering Judgements (EJs) should be used for situations where a tested system is not available. The application to be executed by manufacturer approved firestop contractor.
OD94447/2025-2026:Supplying and laying following GI or copper strip(tinned at the points of contacts) / wire at 0.6m below ground level including excavation and refilling for conductor earth electrode including welding etc as required.75mm X10mm GI
5.8:Supplying and laying 25 mm X 5 mm copper strip at 0.50 metre below ground as strip earth electrode, including connection/ terminating with nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of brass nut bolt & spring washer spaced at 50mm)
5.9:Supplying and laying 25 mm X 5 mm G.I strip at 0.50 metre below ground as strip earth electrode, including connection/ terminating with G.I. nut, bolt, spring, washer etc. as required.(Jointing shall be done by overlapping and with 2 sets of G.I. nut bolt & spring washer spaced at 50mm)
OD94462/2025-2026:Supply and fixing of of fire retardant/extinguishing electrical insulated synthetic mat of size 2m x 1m for 3.3kV grade 2mm thick, +/- 10% confirming to BIS: DOC No. ET-02 (5440) meeting requirements of IS:15652:2006 (with upto date amendment), suitable for 3.3kV voltage and having minimum width of 1000mm +/-<br>20mm and including supply of required quantity of adhensive / compound
OD94463/2025-2026:Supply and fixing of First aid box
OD94464/2025-2026:Supply and fixing glass framed shock treatment chart
2.21:Providing and fixing M.V. danger notice plate of 200 mm X 150 mm, made of mild steel, at least 2 mm thick, and vitreous enameled white on both sides, and with inscription in single red colour on front side as required.
LIGHTNING PROTECTION
OD98909/2025-2026:Providing and laying Hot Dip Galvanised Steel Flat 30X3 mm thick with Zinc coating>70 micron coating from test joint to earth electrode in ground/surface and for ring equipotential bonding etc.as required.
OD98964/2025-2026:Providing and Fixing of Test Joint , suitable to fix 8 mm Aluminium conductor to 30 X 3 GI strip as per IEC 62305-3
OD99526/2025-2026:Supply and fixing of 8 mm Aluminum Round Conductor as vertical down conductor with the required mounting clamps , cross connectors , expansion piece and other accessories required as per IEC 62305-3
OD99528/2025-2026:Supply and Fixing of 8 mm Aluminum Round Conductor as horizontal air terminal suitable for installation on flat roof with the required mounting clamps , cross connectors, T connectors , expansion piece and other accessories required as per IEC 62305-3
OD99866/2025-2026:Supply and Fixing of 8 mm Aluminum Round Conductor suitable for installation on parapet as horizontal air terminal with the required mounting clamps , cross connectors, T connectors , expansion piece and other accessories required as per IEC 62305- Part 3
OD99901/2025-2026:Supply and Fixing of 2 meter high air terminal with 16mm rod tapered to 10 mm aluminium rod with all the accessories for fixing Air terminals as per IEC -62305 -Part 3
STREET LIGHTING SYSTEM
OD94428/2025-2026:Supplying and laying following GI or copper strip(tinned at the points of contacts) / wire at 0.6m below ground level including excavation and refilling for conductor earth electrode including welding etc as required.40mm X10mm GI
90.15.3.7:Supply installation testing and commissioning of O
OD93359/2025-2026:Installing following size of perforated Hot Dipped Galvanised Iron cable tray “Tee” ( galvanisation not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc as required.100 MM WIDTH X 50 MM DEPTH X 1.6 MM THICK
ctogaonal Pole made of hot dip galvanised GI sheet 70 mm top diameter, 130 mm bottom diameter thickness 3mm base plate dimensions of 200x200x16 mm suitable for wind speed as per IS 875 Part III single arm bracket 0.5mt including connector foundation bolt 4 nos fixed in existing RCC foundation and junction box etc. complete 8 Meters
OD93360/2025-2026:Installing following size of perforated Hot Dipped Galvanised Iron cable tray “Tee” ( galvanisation not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc as required.225 MM WIDTH X 50 MM DEPTH X 1.6 MM THICK
OD93361/2025-2026:Installing following size of perforated Hot Dipped Galvanised Iron cable tray “Tee” ( galvanisation not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc as required.300 MM WIDTH X 50 MM DEPTH X 2 MM THICK
90.15.4.3:Supply Conveyance, installation, testing and commissioning of 70W LED street light output greater than 105lumen/W 4000-6000 K with IP 66 protection LED Chip make Cree/Lumilled/Nichea with power factor greater than 0.95 at full load, internal surge protection up to 8 KV,and Aluminium pressure die-cast Powder coated housing,acrylic cover complete with THD Less than 10%, power factor greater than 0.98, RoHS compliant, duly wired up for use on 230 V AC supply. Driver compartment should be seperatly accessible for maintenance (LM 79&80 certificates from NABL accredited Third party lab to be produced mentioning chip manufacturer)
90.16.1.4:Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required4.00 mm copper conductor ( 8 SWG)
MCBs AND MCB DISTRIBUTION BOARDS
90.11.1.10:Supply and installation of sheet steel, phosphatised and painted, dust and vermin proof enclosure of MCB DB including copper /brass bus bar, neutral link, earth bus and DIN rail suitable for fixing MCB/ isolator etc. fixed on wall using suitable anchor bolts or fixed in recess including cutting hole on the wall , making good the damages, colour washing etc. as required4 way (8+12) - three phase double cover (IP 42/43)
2.11:Supplying and fixing single pole blanking plate in the existing MCB DB complete etc. as required.
OD95535/2025-2026:SITC of following isolator in weatherproof sheet steel powder coated enclosure on surace confirming to IEC 60947-3 complete with all accessories , connections testing and commissioning etc as required and as instructed by engineer in charge also making good any damages made during installations.63A FP ISOLATOR
OD95536/2025-2026:SITC of following isolator in wetherproof sheet steel powder coated enclosure on surace confirming to IEC 60947-3 complete with all accessories , connections testing and commissioning etc as required and as instructed by engineer in charge also making good any damages made during installations..40A FP ISOLATOR
OD95537/2025-2026:SITC of following isolator in weatherproof sheet steel powder coated enclosure on surace confirming to IEC 60947-3 complete with all accessories , connections testing and commissioning etc as required and as instructed by engineer in charge also making good any damages made during installations. 32A DP ISOLATOR
OD95538/2025-2026:Supply, Installation, Testing & Commissioning of following isolator in metal enclosure duly painted with powder coated finishing on surface including all the mounting accessories, internal wiring etc as required complete.63A FP
OD95539/2025-2026:Supply, Installation, Testing & Commissioning of following isolator in metal enclosure duly painted with powder coated finishing on surface including all the mounting accessories, internal wiring etc as required complete.40A FP
OD95540/2025-2026:Supply, Installation, Testing & Commissioning of following isolator in metal enclosure duly painted with powder coated finishing on surface including all the mounting accessories, internal wiring etc as required complete.32A FP
OD95541/2025-2026:Supply, Installation, Testing & Commissioning of following isolator in metal enclosure duly painted with powder coated finishing on surface including all the mounting accessories, internal wiring etc as required complete.32A DP
OD95542/2025-2026:Supply and fixing of following rating, 10 KA, Miniature Circuit Breakers as<br>required.<br> 6-32A SP MCB,<br>D-CURVE<br>
OD95543/2025-2026:Supply and fixing of following rating, 10 KA, Miniature Circuit Breakers as<br>required.<br> 40-63A TP MCB,<br>C-CURVE<br>
OD95544/2025-2026:Supplying and fixing Cable End Box (Loose Wire Box) (IP 43) suitable for following MCB distribution board, 415 V, on surface/ recess, complete with testing and commissioning etc. as required. For 12 way, Double door SPNDB
OD98809/2025-2026:Fixing of following ways surface/ recess mounting, vertical type, 415 volts, TPN MCB distribution board of sheet steel, dust protected, duly powder painted, inclusive of 200 amps tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCB's (but without MCB's and incomer ) as required. 4 way (8 + 12), Double door
OD98810/2025-2026:Fixing of following ways surface/ recess mounting, vertical type, 415 volts, TPN MCB distribution board of sheet steel, dust protected, duly powder painted, inclusive of 200 amps tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCB's (but without MCB's and incomer ) as required. 8 way (8 +24), Double door
OD98811/2025-2026:Fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 volts, on surface/recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted includin earthing etc. as required. (But without MCB/RCCB/Isolator) 6 way (8 + 18), Double door
OD98812/2025-2026:Fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 volts, on surface/recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted includin earthing etc. as required. (But without MCB/RCCB/Isolator) 8 way (8 + 24), Double door
OD98813/2025-2026:Fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 volts, on surface/recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) 4 way (8 + 12), Double door
OD98814/2025-2026:Fixing following rating, four pole, (three phase and neutral), 415 volts, residual current circuit breaker (RCCB), having a sensitivity current 100 milli amperes in the existing MCB DB complete with connections, testing and commissioning etc. as required. 63 Amp
OD98815/2025-2026:Fixing following rating, four pole, (three phase and neutral), 415 volts, residual current circuit breaker (RCCB), having a sensitivity current 100 milli amperes in the existing MCB DB complete with connections, testing and commissioning etc. as required. 40 Amp
OD98816/2025-2026:Fixing following rating, four pole, (three phase and neutral), 415 volts, residual current circuit breaker (RCCB), having a sensitivity current 30 milli amperes in the existing MCB DB complete with connections, testing and commissioning etc. as required. 40 Amp
OD98817/2025-2026:Fixing following rating, four pole, (three phase and neutral), 415 volts, residual current circuit breaker (RCCB), having a sensitivity current 30 milli amperes in the existing MCB DB complete with connections, testing and commissioning etc. as required. 25Amp
OD98818/2025-2026:Fixing 5 amps to 32 amps rating, 240/415 volts, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.Single pole
OD98819/2025-2026:Fixing 5 amps to 32 amps rating, 240/415 volts, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.Triple pole
OD98820/2025-2026:Fixing 5 amps to 32 amps rating, 240/415 volts, "D" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.Single pole
OD98821/2025-2026:Fixing 40 amps to 63 amps rating, 240/415 volts, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with
connections, testing and commissioning etc. as required.Triple pole
OD98822/2025-2026:Fixing the following types & current rated control gears & switchgears conforming to IS 13947 suitable for 440 V, 50 Hz, AC supply in the existing panel assembly as required 250Amp,16KA,FPMCCB
OD98823/2025-2026:Fixing the following types & current rated control gears & switchgears conforming to IS 13947 suitable for 440 V, 50 Hz, AC supply in the existing panel assembly as required 160Amp,16KA,FPMCCB
OD98824/2025-2026:Fixing the following types & current rated control gears & switchgears conforming to IS 13947 suitable for 440 V, 50 Hz, AC supply in the existing panel assembly as required 125Amp,16KA,FPMCCB
OD98825/2025-2026:Installation of sheet steel, phosphatised and painted, dust and vermin proof enclosure of MCCB DB including copper /brass bus bar, neutral link, earth bus and DIN rail suitable for fixing MCB/isolator etc. fixed on wall using suitable anchor bolts or fixed in recess including cutting hole on the wall , making good the damages, colour washing etc. as required) 4 way TPN
OD98826/2025-2026:Installation of sheet steel, phosphatised and painted, dust and vermin proof enclosure of MCCB DB including copper /brass bus bar, neutral link, earth bus and DIN rail suitable for fixing MCB/isolator etc. fixed on wall using suitable anchor bolts or fixed in recess including cutting hole on the wall , making good the damages, colour washing etc. as required) 8 way TPN
OD93364/2025-2026:Installing following size of perforated Hot Dipped Galvanised Iron cable tray “Cross member” ( galvanisation not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc as required.100 MM WIDTH X 50 MM DEPTH X 1.6 MM THICK
OD98827/2025-2026:Supply and Fixing following rating, four pole, (three phase and neutral), 415 volts, residual current circuit breaker (RCCB), having a sensitivity current 100 milli amperes in the existing MCB DB complete with connections, testing and commissioning etc. as required. 40 Amp
90.14.29.3:S & F Motor starters accessories of the followingPush button station for starters
LIGHT FIXTURES AND FANS
OD99950/2025-2026:Supply of surface/Suspended Mounted LED Batten of maximum wattage below 20W with System efficacy of more than 120lm/W and lumen output of luminaire greater than 2000 lumen. LED luminaire shall have sleek design with Extruded Aluminum Section. The luminaire shall have Optically Efficient Polycarbonate Diffuser for Uniform illumination and wider light distribution. The LED shall be compliant with LM80 standard with Useful L70 life of 50000 Hrs tested at maximum current. The CCT5000 - 6000K, CRI >80, ripple factor<5 and 4KV internal surge protection. Power factor greater than 0.95 and total harmonic distortion (THD) of less than 10% should be integral to the luminaire and EMI/EMC compatible
OD93365/2025-2026:Installing following size of perforated Hot Dipped Galvanised Iron cable tray “Cross member” ( galvanisation not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc as required.225 MM WIDTH X 50 MM DEPTH X 1.6 MM THICK
OD99953/2025-2026:Supply of surface mounted LED Batten of maximum wattage below 10W with System efficacy of more than 120lm/W and lumen output of luminaire greater than 1000 lumen. The luminaire shall have designed extruded channel in thermally conductive material with plastic with HET diffuser. The LED shall be compliant with LM80 standard with Useful L70 life of 50000Hrs tested at maximum current. The CRI>80 and 4KV internal surge protection. Power factor greater than 0.95, CCT 5700K+/-300K, ripple factor <5 and total harmonic distortion (THD) of less than 10% should be integral to the luminaire and EMI/EMC compatible
OD93366/2025-2026:Installing following size of perforated Hot Dipped Galvanised Iron cable tray “Cross member” ( galvanisation not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc as required.300 MM WIDTH X 50 MM DEPTH X 2 MM THICK
OD93367/2025-2026:Installing following size of perforated Hot Dipped Galvanised Iron cable tray “Cross member” ( galvanisation not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc as required.450 MM WIDTH X 50 MM DEPTH X 2 MM THICK
OD99960/2025-2026:Supply of LED recess mounted downlight made of die cast aluminium, along with driver ,surge protection, maximum system wattage of 10Watts,lumen output of luminaire greater than or equal to 1100lumens, power factor>0.95,rated life of L70@50,000hours,system efficacy greater than or equal to 110lumen/watt. The CRI>80 and 4KV internal surge protection, CCT 5700K+/- 300K,UGR</=19 and total harmonic distortion(THD) of less than 10% should be integral to the luminaire.
OD93368/2025-2026:Installing following size of perforated Hot Dipped Galvanised Iron cable tray “Cross member” ( galvanisation not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc as required.600 MM WIDTH X 50 MM DEPTH X 2 MM THICK
OD100012/2025-2026:Supply of LED IP54 cleanroom recess mounted panel light fixture light made of CRCA, with System efficacy of more than 110lm/W along with driver of maximum system wattage below 40W with lumen output not less than 4000 lumens. The LED shall be compliant with LM80 standard with Useful L70 life of50000Hrs tested at maximum current. The CRI>80 and 4KV internal surge protection. Power factor greater than 0.95, CCT5700K+/-300K, ripple factor<5, UGR</=19 and total harmonic distortion (THD) of less than 10% should be integral to the luminaire and EMI/EMC compatible
OD102986/2025-2026:Providing and constructing of Cable chamber of inner dimension 1200 (L)x 1200(W) x 1500(D) using RCC and cover slab of heavy duty classifications. The mix shall be machine mixed design mix M-25 grade cement concrete for reinforced cement concrete work, steel reinforcement of of grade Fe-500D or more. The work shall be all inclusive of excavation, centering and shuttering including strutting, concreating, refilling providing suitable openings as per the requirements etc.
OD100038/2025-2026:Supply and fixing of LED recess mounted 2x2 panel light fixture, along with driver,<br>with chain and wiring using 3runs of 1.5 sqmm FRLSPVC insulated stranded<br>copper conductor cable as required etc. on false ceiling. The maximum system<br>wattage of 36 Watts, lumen output of luminaire greater than or equal to 4000<br>lumens, power factor> 0.95, rated life of L70 @50,000 hours, system efficacy<br>greater than or equal to 110 lumen/watt. The CRI >80 and 4KV internal surge<br>protection, CCT5700K+/-300K, ripple factor<5, UGR</=19 and total harmonic<br>distortion (THD) of less than 10% should be integral to the luminaire and<br>EMI/EMC compatible
OD94368/2025-2026:Supplying and laying following GI or copper strip (tinned at the points of contacts) / wire on the surface/recess with mounting saddles for conductor earth electrode including welding etc as required.75mm X10mm GI
OD94374/2025-2026:Supplying and laying following GI or copper strip (tinned at the points of contacts) / wire on the surface/recess with mounting saddles for conductor earth electrode including welding etc as required.40mm X10mm GI
OD100743/2025-2026:Supply and fixing of LED IP54 cleanroom recess mounted panel light fixture light made of CRCA, with System efficacy of more than 110lm/W along with driver of maximum system wattage below 60W with lumen output not less than 6000 lumens. The LED shall be compliant with LM80 standard with Useful L70 life of 50000Hrs tested at maximum current. The CRI>80 and 4KV internal surge protection. Power factor greater than 0.95, CCT5700K+/-300K, ripple factor<5, UGR</=19 and total harmonic distortion (THD) of less than 10% should be<br>integral to the luminaire and EMI/EMC compatible.
90.15.4.2:Supply Conveyance, installation, testing and commissioning of 36/40W LED street light output greater than 105lumen/W 4000-6000 K with IP 66 protection LED Chip make Cree/Lumilled/Nichea with power factor greater than 0.95 at full load, internal surge protection up to 8 KV,and Aluminium pressure die-cast Powder coated housing,acrylic cover complete with THD less than 10%, power factor greater than 0.98, RoHS compliant, duly wired up for use on 230 V AC supply. Driver compartment should be seperatly accessible for maintenance (LM 79&80 certificates from NABL accredited Third party lab to be produced mentioning chip manufacturer)
OD100850/2025-2026:Supply of 450 mm sweep,900 rpm heavy duty exhaust fan in metal body with louvers working on 230 V<br>AC supply complete with all accessories as required
OD100867/2025-2026:Installation, testing and commissioning of LED down lighter fittings on false ceiling with all mounting accessories as required complete including interconnections using 3 runs 1.5 sqmm FRLS PVC insulated flexible copper conductor as required.
OD100882/2025-2026:Installation, testing and commissioning of Wall fan, including all the supports as required and wiring using<br>3 runs of 1.5 sqmm FR PVC insulated stranded copper conductor etc complete
OD100894/2025-2026:Installation testing and commissioning of prewired fluorescent fittings of all types including LED complete with all accessories, lamps etc. on false ceiling including supplying and fixing of GI chain and hook arrangement, upto 60cm length, and wiring using 3 runs of 1.5 sqmm FRLS PVC insulated stranded copper conductor cable as required.
1.41:Installation, testing and commissioning of pre - wired, fluorescent fitting/ compact fluorescent fitting of all types, complete with all accessories and tube etc. directly on ceiling/ wall, including connection with 1.5 sq.mm FRLS PVC insulated, copper conductor, single core cable and earthing etc. as required.
1.42:Installation, testing and commissioning of pre-wired, fluorescent fitting / compact fluorescent fitting of all types, complete with all accessories and tube etc., including supplying and fixing ball and socket arrangement, 2 no. down rods of 20 mm dia X 1.6 mm thick steel conduit upto 30 cm length, painting and wiring the down rods and connection with 1.5 sq. mm FRLS PVC insulated, copper conductor, single core cable and earthing etc. as required.
1.43:Providing and fixing extra conduit down r
OD94461/2025-2026:Supply and fixing of of fire retardant/ext
inguishing electrical insulated synthetic mat of size 2m x 1m for 11kV grade 3mm thick, +/- 10% confirming to BIS: DOC No. ET-02 (5440) meeting requirements of IS:15652:2006 (with upto date amendment), suitable for 11kV voltage and having minimum width of 1000mm +/- 20mm and including supply of required quantity of adhensive / compound
2.23.2:Supplying and fixing Cable End Boxes (IP 43) suitable for following single pole and neutral, sheet steel, MCB distribution board, 240 volts, on surface/ recess, complete with testing and commissioning etc. as required. For 8 way, Double door SPN MCBDB
od of 20 mm dia, 2X10 cm length wiring with 2 X1.5 sq.mm FRLS PVC insulated, copper conductor, single core cable including painting etc. as required. (Note: More than 5 cm length shall be rounded to the nearest 10 cm and 5 cm or less shall be ignored)
2.10.1:Supplying and fixing 5A to 32 A rating, 240/415 volts, 10 kA, ""C"" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. Single pole
2.10.4:Supplying and fixing 5A to 32 A rating, 240/415 volts, 10 kA, ""C"" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. Triple pole
1.44:Installation, testing and commissioning of ceiling fan, including wiring the down rods of standard length (upto 30 cm) with 1.5 sq. mm FRLS PVC insulated, copper conductor, single core cable etc. as required.
1.50.1:Installation of exhaust fan in the existing opening, including making good the damage connection testing, commissioning etc. as required.Upto 450 mm sweep
OD100927/2025-2026:Supply of LED recess mounted downlight made of die cast aluminium, along with driver, surge protection, maximum system wattage of 18Watts, lumen output of luminaire greater than or equal to 1800 lumens, power<br>factor>0.95, rated life of L70 50,000hours, system efficacy greater than or equal to 110lumen/watt. The CRI>80 and 4KV internal surge protection, CCT5700K+/- 300K, ripple factor <5, UGR</=19 and total harmonic distortion (THD) of less than 10% should be integral to the luminaire and EMI/EMC compatible.
OD100941/2025-2026:Supply and fixing of surface mounted LED Industrial Batten of maximum wattage below 40W with System efficacy of more than 120lm/W and lumen output of luminaire greater than 4000 lumen. LED luminaire shall have sleek design with Extruded Aluminum Section. The luminaire shall have Optically Efficient Polycarbonate Diffuser for Uniform illumination and wider light distribution along with driver and surge protection, IP65 dust and water proof LED. The LED shall be compliant with LM80 standard with Useful L70life of 50000Hrs tested at maximum current. The CRI>80 and 4KV internal surge protection. Power factor greater than 0.95,CCT5700K+/-300K, ripple factor <5 and total harmonic<br>distortion(THD)of less than 10% should be integral to the luminaire and EMI/EMC<br>compatible
WIRING AND ACEESORIES
OD101215/2025-2026:Supplying and fixing of 3 pin 5/6 amps modular socket outlet and 5/6 amps modular switch, on existing modular box with necessary connection etc. as required. (For light plugs to be used in non residential buildings).
1.14.1:Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface / recessed medium class PVC conduit as required2x1.5 sq.mm + 1x1.5 sq.mm earth wire
1.14.2:Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface / recessed medium class PVC conduit as required2X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire
1.14.3:Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface / recessed medium class PVC conduit as required2 X 4 sq. mm + 1 X 4 sq. mm earth wire
1.14.4:Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface / recessed medium class PVC conduit as required2 X 6 Sq.mm + 1 x 6 sq.mm earth wire
1.14.7:Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface / recessed medium class PVC conduit as required4 X 2.5 sq. mm + 2 X 2.5 sq. mm earth wire
1.14.8:Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface / recessed medium class PVC conduit as required4 X 4 sq. mm + 2 X 4 sq. mm earth wire
1.14.9:Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface / recessed medium class PVC conduit as required4 X 6 sq. mm + 2 X 6 sq. mm earth wire
1.21.1:Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required.20 mm
1.21.2:Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required.25 mm
1.21.3:Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required.32 mm
1.24.1:Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.5/6 amps switch
1.24.3:Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.15/16 amp switch
1.24.4:Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.3 pin 5/6 amp socket outlet
1.24.5:Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.6 pin 15/16 amp socket outlet
1.24.8:Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.Bell push
1.25:Supplying and fixing two module stepped type electronic fan regulator on the existing modular plate switch box including connections but excluding modular plate etc. as required.
1.26:Supplying and fixing modular blanking plate on the existing modular plate & switch box excluding modular plate as required.
1.27.1:Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required.1 or 2 Module (75mmX75mm)
1.27.2:Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required.3 Module (100mmX75mm)
1.27.3:Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required.4 Module (125mmX75mm)
1.27.4:Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required.6 Module (200mmX75mm)
1.27.5:Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required.8 Module (125mmX125mm)
1.27.6:Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required.12 Module (200mmX150mm)
1.28.1:Supplying and fixing following Modular base & cover plate on existing modular metal boxes etc. as required.1 or 2 Module
1.28.2:Supplying and fixing following Modular base & cover plate on existing modular metal boxes etc. as required.3 Module
1.28.3:Supplying and fixing following Modular base & cover plate on existing modular metal boxes etc. as required.4 Module
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 2.44 MB
BOQ_1369255.xls
BOQ • 0.60 MB
Technicalbidelec.pdf
Tender Documents • 13.00 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .