Nazeera Anvar
The Assistant Executive Engieer,220kV substation,Pothencode
Replacement of faulty ductable split air conditioners at 220kV control room at 220kV substation,Pothencode
2023_KSEB_575110_1
02/AEE-PTCD/2023-24/ Dated 05.05.2023
Open Tender
Miscellaneous Works
Item Wise
45 days
220 kV Substation, Pothencode, Trivandrum
Please refer tender documents
7 documents required · 7 mandatory
₹1,400
Yes
₹15,000
Yes
4 Jul 2023
11 May 2023
27 May 2023
11 May 2023
25 May 2023
12 May 2023
11 May 2023 - 22 May 2023
Amount
Part A - Supply of Material
Supply of air cooled ceiling mounted ductable split air conditioners of normal capacity 11.0 TR with hermetically sealed Scroll.The Compressors shoud have R410A refrigerent, independent refrigerent circuits, expansion devices, HP/LP cut off, Microprocessor controlled control panel, Wired remote control etc. The evaporator coil should be with integrally finned copper tubes and the condensation units should have condensation coil, condenser fan etc. The entire machine must be neatly painted/powder coated.
Description of Work / Item(s)
Amount
Part B - Labour
Dismantling of old ductable split Air Conditioners.
Installation, testing and commissioning of air cooled ceiling mounted ductable split air conditioners of normal capacity 11.0 TR with hermetically sealed Scroll.
Duct mouth alteration and canvas connection.
Copper refrigerent piping with hard drawn 18 SWG for interconnecting the indoor unit with outdoor unit.The refrigerent piping should be insulated and strapped to the wall.
Providing condensing unit supports with ribbed rubber pads.
Providing drain piping for the condensate drain to the nearest drain point with 1' PVC pipe.
Providing 2.5 Sqmm 3 Core electrical cabling between indoor units and outdoor units.
Providing 6 Sqmm 4 Core incoming electrical copper wire to outdoor units.
Description of Work / Item(s)
Total amount quoted by the bidder
Quoted Amount of BOQ1 in figure (Part -A)
Quoted Amount of BOQ1 in figure (Part -B)
PERKINS REFRIGERATION AND AIR CONDITIONING
MARETEK INDIA PVT LTD
PERKINS REFRIGERATION AND AIR CONDITIONING
MARETEK INDIA PVT LTD
PERKINS REFRIGERATION AND AIR CONDITIONING
MARETEK INDIA PVT LTD
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .