Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹84,687Accepted-AOC | L1 | Accepted-AOC L1 | |
| 2 | L2₹84,806+₹119 (0.14%)Rejected-AOC | L2 | Rejected-AOC L2 |
Tender Value
₹85,789
EMD Value
₹2,150
Closing Date
17 Jan 2022, 2:00 pmClosed
ASST. ENGINEER
LID AND EW SECTION PUNNAPRA SOUTH GP
Electrification work Improvements to anganavadi No 30 in ward 15 under Punnapra south gp
2022_LSGD_466231_1
01/2021/ELE/AE/LSGD/PSGP
Open Tender
Electrical Works
Item Rate
60 days
ALAPPUZHA
Please refer Tender documents.
6 documents required · 6 mandatory
₹500
Yes
₹2,150
Yes
14 Feb 2022
10 Jan 2022
20 Jan 2022
10 Jan 2022
17 Jan 2022
10 Jan 2022
Amount
Part I-Electrification .( DLTC approved list of make of materials attached)
90.2.1.1 : Supply and wiring points according to IS 732-1989 using rigid PVC conduit of minimum size 20 mm with specials conforming to IS 9537 part III 1983 and with suitable size specials conforming to IS 3419-1988, fixing the conduit using metal saddles spacing not exceeding 50 cm or concealed suitably and with 1.00 sq mm FRLS PVC insulated stranded single core copper conductor cable 650V grade, including providing switch board main and continuous earthing with No.14 SWG bare copper,required quantity of copper earth socket, brass bolt and nut crimping/ soldering etc complete with suitable size modular type metal switch boxes, modular type front plates (white) etc. up to and including 6A modular type SP switches and making good the surface of wall, colour washing etc. complete. All the terminations in the switch boards and DB's shall be tinned and the wires shall be drawn and fixed along the periphery of the box using suitable ties, tie mounts etc as required. (RoHS compliant modular accessories).
90.2.1.3 : Supply and wiring points according to IS 732-1989 using rigid PVC conduit of minimum size 20 mm with specials conforming to IS 9537 part III 1983 and with suitable size specials conforming to IS 3419-1988, fixing the conduit using metal saddles spacing not exceeding 50 cm or concealed suitably and with 1.00 sq mm FRLS PVC insulated stranded single core copper conductor cable 650V grade, including providing switch board main and continuous earthing with No.14 SWG bare copper,required quantity of copper earth socket, brass bolt and nut crimping/ soldering etc complete with suitable size modular type metal switch boxes, modular type front plates (white) etc. up to and including 6A modular type SP switches and making good the surface of wall, colour washing etc. complete. All the terminations in the switch boards and DB's shall be tinned and the wires shall be drawn and fixed along the periphery of the box using suitable ties, tie mounts etc as required. (RoHS compliant modular accessories).
90.2.1.4 : Supply and wiring points according to IS 732-1989 using rigid PVC conduit of minimum size 20 mm with specials conforming to IS 9537 part III 1983 and with suitable size specials conforming to IS 3419-1988, fixing the conduit using metal saddles spacing not exceeding 50 cm or concealed suitably and with 1.00 sq mm FRLS PVC insulated stranded single core copper conductor cable 650V grade, including providing switch board main and continuous earthing with No.14 SWG bare copper,required quantity of copper earth socket, brass bolt and nut crimping/ soldering etc complete with suitable size modular type metal switch boxes, modular type front plates (white) etc. up to and including 6A modular type SP switches and making good the surface of wall, colour washing etc. complete. All the terminations in the switch boards and DB's shall be tinned and the wires shall be drawn and fixed along the periphery of the box using suitable ties, tie mounts etc as required. (RoHS compliant modular accessories).
90.2.1.6 : Supply and wiring points according to IS 732-1989 using rigid PVC conduit of minimum size 20 mm with specials conforming to IS 9537 part III 1983 and with suitable size specials conforming to IS 3419-1988, fixing the conduit using metal saddles spacing not exceeding 50 cm or concealed suitably and with 1.00 sq mm FRLS PVC insulated stranded single core copper conductor cable 650V grade, including providing switch board main and continuous earthing with No.14 SWG bare copper,required quantity of copper earth socket, brass bolt and nut crimping/ soldering etc complete with suitable size modular type metal switch boxes, modular type front plates (white) etc. up to and including 6A modular type SP switches and making good the surface of wall, colour washing etc. complete. All the terminations in the switch boards and DB's shall be tinned and the wires shall be drawn and fixed along the periphery of the box using suitable ties, tie mounts etc as required. (RoHS compliant modular accessories).Combined plug point with 6 A, 5 pin plug socket controlled by 6 A, switch in the same switch board as that of light points
90.2.1.7 : Supply and wiring points according to IS 732-1989 using rigid PVC conduit of minimum size 20 mm with specials conforming to IS 9537 part III 1983 and with suitable size specials conforming to IS 3419-1988, fixing the conduit using metal saddles spacing not exceeding 50 cm or concealed suitably and with 1.00 sq mm FRLS PVC insulated stranded single core copper conductor cable 650V grade, including providing switch board main and continuous earthing with No.14 SWG bare copper,required quantity of copper earth socket, brass bolt and nut crimping/ soldering etc complete with suitable size modular type metal switch boxes, modular type front plates (white) etc. up to and including 6A modular type SP switches and making good the surface of wall, colour washing etc. complete. All the terminations in the switch boards and DB's shall be tinned and the wires shall be drawn and fixed along the periphery of the box using suitable ties, tie mounts etc as required. (RoHS compliant modular accessories).Independent plug - Short point
90.4.1 : Supply and installation of suitable size MS rod type fan clamp in the RCC slab as per IS 732 as required.
od1540972/2021_2022 : Supply & installation of 1200mm sweep ceiling fan complete with it's standard accessories with out regulator & giving connection with 16/0.20mm 3 core round copper conductor flex wire as required. ( crompton high speed/ Havells (SS-390)
90.6.10.1 : Supply and fixing of following sizes of light gauge PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required
90.6.10.2 : Supply and fixing of following sizes of light gauge PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required
1.17.3 : Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 X 1.5 sq.mm
1.17.12 : Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 x 2.5 sq. mm
1.17.21 : Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 x 4 sq. mm
1.24.1 : Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.5/6 amps switch
1.24.3 : Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.15/16 amp switch
1.24.4 : Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.3 pin 5/6 amp socket outlet
1.24.5 : Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.6 pin 15/16 amp socket outlet
90.10.3.23 : Supply and Fixing the following modular switches & accessories in the existing front plates and giving necessary connections as required (RoHS compliant )
1.27.1 : Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required.1 or 2 Module (75mmX75mm)
1.27.2 : Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required.3 Module (100mmX75mm)
1.27.5 : Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required.8 Module (125mmX125mm)
2.3.3 : Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCBIRCCB/Isolator12 way, Double door
2.10.1 : Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.Single pole
2.12.1 : Supplying and fixing following rating, double pole, 240 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.40 amps
2.14.1 : Supplying and fixing following rating, double pole, (single phase and neutral), 240 V, residual current circuit breaker (RCCB), having a sensitivity current 30 mA in the existing MCB DB complete with connections, testing and commissioning etc. as required.25 amps
od1540973/2021_2022 : Earthing with GI earth pipe 2 mtr. long 40mm dia. medium class including providing 12mm dia,drilled holes minimum 20 nos along the entire length in alternate arrangement providing 40x25mm GI reducer at top & test joint using 2 nos ,25x3mm GI strip minimum size 25cm suitably shaped and tightly clamped to the pipe electrode using 25x6 mm steel bolts ,nuts &washer & providing 2 nos ,6mm dia. drilledholes for clamping & bolting earth lead & making massoary chamber with cover plate having locking arrangement and etc. charcoal& salt are shall be filled at 30 cm dia. around the earth elcetrode.
90.4.8 : Charges for cutting holes suitable for accommodating exhaust fans up to 305mm sweep including plastering colour washing etc. as required.
90.16.1.3 : Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required
90.16.5.1 : Supply of superior quality copper earth socket for the following size of earth conductor including crimping etc. as required.
90.16.5.3 : Supply of superior quality copper earth socket for the following size of earth conductor including crimping etc. as required.
od1540974/2021_2022 : Supply and providing 12x3 mm brass bolt and nut with washers on the existing MS box / earth bus etc. as required including drilling necessary holes as required
od1540975/2021_2022 : Supply and providing 25x6 mm brass bolt and nut with washers on the existing MS box / earth bus etc. as required including drilling necessary holes as required
90.3.20.3 : Supply & installation of light fittings on TW round block <br> Supply, conveyance installation testing and commissioning the light fittings of following types made of CRCA with 0.5mm thickness complete with all accessories and lamps etc. directly on wall or ceiling with PVC round block neatly painted to suit the fitting and giving connection with required length of 16/0.20mm 3 core copper conductor flex wire conforming to relevant ISS and giving connections as required.
od1540976/2021_2022 : Supply & installation of dust and vermin proof, wall mounting, sintex meter box of (GS-MB.3425). 350x250x150mm or nearest size suitable for fixing KSEB meter,fuse units, neutral link. etc, hinged door construction for the front side with compartments if necessary, providing vision panel for the meter compartment, knock out for cable entry and exit.<br>
od1540977/2021_2022 : Supply & providing 32A,415V,2 way neutral link onDMC/SMC base.
od1540978/2021_2022 : Supply & fitting 32 A fuse holder for BS type blade fuses with suitable capacity HRC fuse on existing meter box and giving connection as required.<br>
od1540979/2021_2022 : Supply & fitting 2 pole metal enclosure in position as required
od1540980/2021_2022 : Supply and fixing angle / straight brass lined skirt type, bakelite batten holder with 200mm polished shade with 9W LED and giving connection etc as required
od1540981/2021_2022 : Supply & providing 0.5 HP centrifugal 1 phase motor pump set V-guard model No.VSPA H-80 with discharge of 1900 to 750 lpm at a head of 6m to 24 m or equivalent kirloskaar make on suitable concrete foundation.
od1540982/2021_2022 : Supply, conveyance, installation, testing and commissioning of the following sizes of exhaust fans in the existing opening, fixing necessary bolt and nuts, making good the damages etc. as required including giving connections with required length of 24/0.20mm PVC insulated and PVC sheathed 3 core round copper conductor flex wire conforming to relevant ISS. <br> 305 mm, single phase, heavy duty, 1400 rpm exhaust fan in metal frame
1.51 : Extra for fixing the louvers/ shutters complete with frame for a exhaust fan of all sizes
od1540983/2021_2022 : Supply and providing anchor bolt hook type on wall /parapet for binding KSEB Service connection cacable as required.
od1540985/2021_2022 : Supply, conveyance, installation, testing and commissioning of 200 mm, single phase, light duty exhaust fan in plastic body with self opening louvers in the existing opening, fixing necessary bolt and nuts, making good the damages etc. as required including giving connections with required length of 24/0.20 mm PVC insulated and PVC sheathed 3 core round copper conductor flex wire conforming to relevant ISS.
od1540986/2021_2022 : Supply & fixing Aluminium stove enameled bulk head fitting with deep drawn anodised aluminium body, epoxy power coated, heat resistant prismatic glass cover with 9w LED to wall/ ceiling including giving connection with required length of 16/0.20mm PVC to PVC 3 core round copper flex wire as required. (mepro /Philips / crompton/ Bajaj.)
od1540987/2021_2022 : Charges for preparing load details sketch and application for KSEB connection.
od1541118/2021_2022 : Supply & fitting 400mm or nearest dia. wall fan complete with it's standard accessories on wall & giving connection. Almonard /orient make.
od1541119/2021_2022 : KSEB charges for availing single phase service connection with out post .Re- imburse actual KSEB bill amount.
CHANDRAMOHANAN
Bidder Name
CHANDRAMOHANAN
AJITH
stage.html
html • 0.04 MB
tech_eval.pdf
fin_eval.pdf
aoc.pdf
finance_667601.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .