GE AF TRIVNADRUM
Office of Garrison Engineer AF, Pulayanarkotta, Thuruvikkal Post, Trivandrum-695011
MAINT REPAIR TO EARTHING SYSTEM OF VARIOUS INSTALLATIONS, FIRE FIGHTING SYSTEM SUCH AS REPAIR TO HYDRANTS, PUMP SETS, VALVES, SENSOR PANELS, HOSE CABINETS ETC AT VARIOUS LOCATIONS AND OTHERS ALONG WITH MISC WORK AT HQ SAC UNDER GE AF TRIVANDRUM
2026_MES_771092_1
8624
Open Tender
Electrical and Maintenance Works
270 days
TRIVANDRUM
Please refer Tender documents.
7 documents required · 7 mandatory
₹500
GE AF TRIVANDRUM
₹78,100
Yes
10 Jun 2026
10 Jun 2026
4 Jul 2026
10 Jun 2026
1 Jul 2026
24 Jun 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | M&L for removal of conventional earth pits and Supply, Installation, Commissioning and Testing of Maintenance Free Earthing system comprising of Copper-Bonded Steel Earth Rod of 3-meter length and 17.2 mm diameter. Auger a hole of diameter 4 inches and 9 feet depth in the soil, placing the Earth rods into the augured hole, hammering the rods to 1 feet depth, and removing excavated material. Make: NVENT ERICO Cat Part No: CODE 613400 or techno-commercially equivalent of SIEMENS/HERGER complete all as specified and as directed. Brief features/ specifications of CBSE Rod are as follows:- (a) The outer surface must be molecularly bonded with a uniform layer of 250-micron Copper, 99.9% pure electrolytic copper coating.(b) Rods have a high-carbon steel core and tip that provide superior strength when driving. A nickel interface must be provided between the copper and steel to avoid galvanic corrosion. Copper coating will not crack when bent or tear when driven
(c) Must be capable of withstanding a fusing current of 25 KA @ 1 Sec.
(d) Earth rod must comply with IEC 62305- 2, NBC 2010 and IEEE 80. Rod should be tested as per the IEC 62561- 2 /ANSI®/NEMA® GR1 standard. UL logo and control number, where applicable stamped on each rod for easy inspection after installation(e) Tensile strength greater than 80000 PSI on 12 mm.(f) High resistance to corrosion.(g) Material category number should be UL listed, Manufacturer Make, Part No and UL mark should be printed in each rod.
(h) Rate includes boring of hole of 4 in ch dia and 3 mtr deep in any type of soil/rock | 15 | Each | - | - |
| 2 | M&L for Ground Enhancement Material (GEM), Per Bag -11.33 Kgs , Conforming to IEC 62561-7 Standard, Premixing the GEM into slurry form using water( not more than 5 L to 6 L per bag), Pouring the GEM mixture in the augured hole and filling. Make ERICO Cat Part No: GEM 25A- 25-1lb or techno-commercially equivalent of HERGER/SIEMENS or approved by higher HQincluding taking down old unserviceable one complete all as specified and as directed. Brief features/ specifications of the same are as follows:- NOTE of 1.30:-(a) Must be a carbon-based, superior conductive material.
(b) Resistivity must be less than 2 Ω-cm.(c) Must not cause corrosion to copper when in contact.
(d) Must not expand or experience any shrinkage once set.(e) Must not depend on the continuous presence of water/moisture/salt to maintain its conductivity.(f) Must not decompose or leach out with time.(g) Must not contain hazardous chemicals as per IEC 62561-7 standard, TCLP Tested and EPA test method 1311.(h) Flexural and possess compressive strength as per the relevant standard(j) Sulphur content must be less than 2%(k) Must be in line with IEEE 80 clause 14.5.d.
(l) Corrosion test shall be conducted on the material under both aggressive and non-aggressive conditions.(m) Installation Instruction and Material DATA sheet should be printed in each package. | 175 | Per BAG | - | - |
| 3 | M&L in replacement for Readymade PVC Heavy duty earth chamber (450 mm x 450mm ) with square cover and minimum 2 ton load bearing capacity, marking plate on top of the chamber cover and mentioning the earth resistance value on it. Complete all as specified and as directed . | 15 | Each | - | - |
| 4 | Disconnection of existing copper/GI/aluminium earth strip by replacing with 10 mm Copper Bonded Steel Round Conductor, minimum copper bonding shall be 254 microns having continuous coin form, compliant with the IEC 62305 and should be tested as per IEC 62561Edition 2.0 standard, material category/ part number should be UL listed, the conductor core should consist of a low-carbon steel grade for improved flexibility. The copper surface of the conductor should provide high conductivity and corrosion resistance properties, should not crack or tear when the conductor is bent, well‐suited as an earth lead conductor or equipotential bonding conductor. Including excavation depth of 50 cm for laying round conductor, treating the horizontal conductor using GEM materials as required quantity in two layers. Removing excavated material, returning filling or fixing with a holder. Make ERICO Cat Part No: CBSC10 or techno-commercially equivalent of HERGER/ SIEMENS complete all as specified and as directed. NOTE of 3.00:-(a) Must be a carbon-based, superior conductive material.
(b) Resistivity must be less than 2 Ω-cm.(c) Must not cause corrosion to copper when in contact.(d) Must not expand or experience any shrinkage once set.
(e) Must not depend on the continuous presence of water/moisture/salt to maintain its conductivity.(f) Must not decompose or leach out with time.
(g) Must not contain hazardous chemicals as per IEC 62561-7 standard, TCLP Tested and EPA test method 1311(h) Flexural and possess compressive strength as per the relevant standard.(j) Sulphur content must be less than 2%.
(k) Must be in line with IEEE 80 clause 14.5.d.(l) Corrosion test shall be conducted on the material under both aggressive and non-aggressive conditions.
(m) Installation Instruction and Material DATA sheet should be printed in each package. | 70 | RM | - | - |
| 5 | Disconnection of existing clamp/nut bolt S & F Clamp Holder made up of 304 grade SS with SS bolt and nut at every 1 m distance of round conductor. The clamp should be suitable for copper-bonded steel Conductor of size 10mm. Make ERICO Cat Part No: CSS 10 or techno-commercially equivalent of HERGER/ SIEMENS complete all as specified and as directed. | 20 | Each | - | - |
| 6 | M & L in replacement of SS terminal connector for termination of equipment body/ Panel body/ Neutral connection with suitable size of CBSC 10mm round conductor by mechanical means using nuts, bolts and all other accessories complete as required by Engr-in-Charge. Make ERICO Cat Part No: BCR10T or techno-commercially equivalent of HERGER/ SIEMENS complete all as specified and as directed. Note: Terminals of existing earth pits shall be cleaned for proper contact with CBSC. | 30 | Each | - | - |
| 7 | M & L in replacement of Cadweld Materials for Connections between Ground Rod with CBSC conductor by Exothermic reaction. Connections to be made with a semi-permanent graphite mould, which shall hold the conductors to be welded. Weld metal must be a mixture of copper oxide and aluminium, should be compliant with IEEE 80 standards and tested as per IEEE 837 -2014 standard. Make ERICO Cat Part No: 150 PLUS F20 or techno-commercially equivalent of HERGER/ SIEMENS complete all as specified and as directed. | 25 | Each | - | - |
| 8 | Material and labour High density Poly ehlene ( HDPE) Pipes of of size 50mm pressure rating 6 Kgf/sqcm for protection of cables/ cu strips etc all as specified and as directed. | 15 | RM | - | - |
| 9 | Supply, installation,testing and commissioning of 50mm dia GI Pipe light grade for laying cable in surface/road crossing complete all as specified and as directed. | 18 | RM | - | - |
| 10 | M/L for PCC 1:3:6 type C1 with 20mm graded aggregate for coping complete including necessary foam work complete all as specified and as directed. | 1 | Cum | - | - |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.65 MB
BOQ_863507.xls
BOQ • 1.51 MB
PS8624.pdf
Additional Documents • 0.53 MB
TP8624.pdf
Tender Documents • 0.89 MB
Download all tender documents and submit your bid