Repair and renovation of electrical installation work for proposed enhancement of toilet facilities inside Sealdah Court premises.--- SITC of FIRE detection System.
2026_WBPWD_5076438_1
WBPWD/EE/52/IR/T/KCED/II of 2026-27(2nd Call)
Open Tender
Electrical Work/ Equipment
Item Rate
45 days
Sealdah Court Complex
Please refer Tender documents.
4 documents required · 4 mandatory
₹7,329
Office_of_EE_KCED_PWD
27 Oct 2026
29 Sept 2026
29 Oct 2026
29 Sept 2026
27 Oct 2026
1 Oct 2026
1 Oct 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Supply, Installation,Testing & Commisioning of Microprocessor based addressable fully networkable fire alarm 2 loop control panel (VDS/UL/ERTL/ LPCB/FM approved) suitable for the devices as stated in the previous items of this BOQ along with 20% spare capacity with each loop loading not exceeding 80% of the full capacity of detectors and devices taken together, complying to IS 2189:2008 IP 50 rating or its latest amendments, and with minimum 600 character alphanumeric liquid crystal display. The panel shall be soft addressable type and shall be able to give pin point location of all fire/fault conditions. Further, the panel must be able to automatically switch off respective control switches with help monitor module whenever any alarm is triggered. The Panel should be able to store sufficient numbers of log events in its Memory as per recommended standards. The panel should have extra loop card slot for expansion of capacity twice.
The panel shall have in built rectifier, provision for external & internal printer ( if required), Loop cards, LCD unit to indicate Fire/Fault Signal with address and analog output, complete in all respects, in built Surge protection facility, integral SMF lead acid batteries with sealed cells of 24 V capable of running for 24 hours normal working and then be capable of operating the system for 60 minutes during Emergency condition, with integral battery charger complete in all respect as required.
The FACP shall be capable of being networked ( future expansion) with other Similar FACP located at different part of the premises through single RS 485 modbus. The FACP shall have provision for interfacing with the public address system, remote computer and BMS interface. The system must be preloaded with licenced software. (Approved Make: Cerberus Pro / Johnson Controls / Edward/ Secutron/ Securiton/Apollo / Morley / Eaton /System Sensor/Esser) | 1 | Set | - | - |
| 2 | Supply, Installation, Testing & Commisioning of Micropresssor controlled Addressable multisensor detector IP 42 (VDS / UL/ERTL/LPCB / FM approved) with inbuilt optical smoke sensors and heat detector sensors andheat detector sensor with inbuilt short circuit fault isolator as per NFPA style 7wiring complete with base (Note: Detectors without built-in fault isolator is alsoacceptable provided one independent short circuit fault isolator is to be providedextra as per NFPA without extra cost) the detectors should have built in LEDresponse indicator. The detector should have 360 degree optical view with single/multiple LED that blinks on actuation of detector. Reverse polarity or faulty zone wiring shall not damage the detectors. (Approved Make: Cerberus Pro / Johnson Controls / Edward/ Secutron/ Securiton/Apollo / Morley / Eaton / System Sensor/Esser). | 40 | Nos. | - | - |
| 3 | Supplying installation, testing and commissioning of LED type Response Indicator (VDS/UL/ERTL/LPCB / FM approved) having 2 Nos. red coloured LED lamps including connections etc. (Approved Make: Cerberus Pro/ Johnson Controls/ Edward /Secutron/ Securiton/ Apollo/Morley / Eaton/System Sensor/Esser). | 16 | Nos. | - | - |
| 4 | Supply, Installation,Testing & Commisioning of Addressable Manual Call Point (VDS/UL/ERTL/LPCB / FM approved) with in built short circuit fault isolator as per NFPA style 7 wiring complete as required. (Approved Make:Cerberus Pro/Johnson Controls/Edward/Secutron/ Securiton/Apollo / Morley / Eaton/GST/Honeywell) . | 4 | Nos. | - | - |
| 5 | Supply, Installation, Testing & Commissioning of Addressable Loop Powered Hooter (sound output of minimum 90 db) cum strobe (strength of light 10 cd) complete with inbuilt short circuit fault isolator. Degree of protection IP65 (VDS /UL/ERTL/ LPCB / FM approved) approved. (Approved Make: Cerberus Pro/ Johnson Controls / Edward /Secutron/ Securiton/ Apollo / Morley / Eaton/ System Sensor/Esser). | 4 | Nos. | - | - |
| 6 | Supply & Laying of 2 Core 1.5 sq.mm FRLS shielded copper Cable (For Loop). (Make- Finolex /Polycab /RR Kable /Gloster/KEI) through 20 mm size PVC rigid conduit 'FR' [Precision Make] on wall, ceiling with saddles and other accessories as required and mending good damages to building works as per GS. | 200 | Mtr. | - | - |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.73 MB
2911.pdf
Tender Documents • 0.51 MB
BOQ_5170029.xls
BOQ • 0.37 MB
DC.pdf
PDF • 0.36 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .