Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹12,567Accepted-AOC SALEM | SALEM | SALEM | TAMIL NADU | L1 | Accepted-AOC Lower Amount Quoted | |
| 2 | L1₹85,611Accepted-AOC 28 85 16 THRISSUR CAPITAL TOWER PATTURAIKKAL JUNCTION VILLAGE TOWN PATTURAIKKAL CITY THRISSUR THRISSUR KERALA 680022 INDIA | THRISSUR | KERALA | 680022 | L1 | Accepted-AOC Lower Amount Quoted | |
| 3 | L1₹1.3 LAccepted-AOC | L1 | Accepted-AOC Lower Amount Quoted | |
| 4 | L1₹2.1 LAccepted-AOC 10 359 AKSHAYA ASSOCIATES OLD BUS STAND THALASSERY KANNUR KERALA 670101 | KANNUR | KERALA | 670101 | L1 | Accepted-AOC Lower Amount Quoted | |
| 5 | L1₹3.3 LAccepted-AOC 1ST FLOOR TC 26 1279 CHETTUPUZHA BUILDING PALAKKAL ANGADI THRISSUR KERALA 680001 THRISSUR THRISSUR KERALA 680001 | THRISSUR | KERALA | 680001 | L1 | Accepted-AOC Lower Amount Quoted |
Tender Value
₹12.6 L
EMD Value
₹12,578
Closing Date
23 Feb 2021, 5:00 pmClosed
The Principal
Govt. Brennen College, Dharmadam
Supply of Lab Equipment to Zoology Department of Govt. Brennen College, Dharmadam
2021_HEdD_414196_1
A3-83/2021/GBRCTLY/S
Open Tender
Laboratory and scientific equipment
Supply
30 days
Dharmadam
Please refer Tender documents.
4 documents required · 4 mandatory
₹2,920
Yes
₹12,578
Yes
9 Apr 2021
11 Feb 2021
26 Feb 2021
11 Feb 2021
23 Feb 2021
11 Feb 2021
Zoology Department
Class ABC (dry) fire extinguishers, 2kg
Class B Carbon dioxide type fire extinguisher, 2kg
First aid kit : Kit contents:, Material description and Qty, HE*Gloves ,w/opowder,nitr,M,disp,box- 1, Tape,adhesive,Z.O.,2.5cmx5m -2, Tape ,adhesive,Z.O,perforated,10cmx5m -1, Bandage,elastic,7.5cmx5m,roll -2, Bandage ,gauze,8cmx4m,roll -10, First Aid bag,UNICEF,blue,410x280x170mm -1, Compress ,gauze,10x10cm,n/ster/PAC-100 -1, Compress,paraffin,10x10cm,ster/BOX-10 -1, Compress,gauze,10x10cm,ster/PAC-5 -10, Pin,safety,medium size/PAC-12- 1, Soap,toilet,bar,approx.110g,wrapped -1 , Blanket,survival,220x140cm- 1, Towel ,huck,430 x 500mm- 1, Forceps,dressing,standard,155mm,str- 1, Forceps ,artery,Kocher,140mm,str -1, Scalpel blade,ster,disp,no.20 Scissors,Deaver ,140mm,str,s/b 1, Ibuprofen 200mg tabs/PAC-100- 1, Tetracycline eye ointment 1%/TBE-5g -1, Chlorhexidine conc. sol. 5%/BOT-100ml -1
Laboratory Fume hood : STANDARD FUME HOOD PERFORMANCE REQUIREMENTS Fume hoods shall be of complete airfoil design to insure maximum operating efficiency. Foil sections at the front facias of the hood shall minimize eddying of air currents at the hood face and the rear baffle system shall minimize turbulence in the upper portion of the hood.interior. MATERIALS AND CONSTRUCTION A. Fume Hood Superstructure Frame: A free-standing rigid frame structure of steel angle shall be provided to support exterior panels and interior liner and baffle panels. To allow for maintenance and replacements, the interior liner panels shall be removable without disassembly of the frame structure and outer steel panels. Likewise, the exterior steel panels shall be removable without disassembly of the frame structure and inner liner panels. Fume hoods that require disassembly of the superstructure for liner replacement are not acceptable. B. Fume Hood Interior Walls: Double wall ends, not more than 4” wide, shall be provided to maximize interior working area. The area between the double wall ends shall be closed to house the remote control valves. The front vertical facia section shall have a full 135 degree 1” radius at the front leading edge to provide a streamlined section and insure smooth even flow of air into the hood. The vertical facias shall contain the required service controls, electrical switches and receptacles. The hood interior end panels and sash track shall be flush with the facia to prevent eddy currents and back flow of air. C. Fume Hood Baffles : A stable, non-adjustable baffle with three fixed horizontal slots shall be provided to aid in distributing the flow of air into and through the hood. The baffle shall be spaced out 2-1/4” from the back liner. The baffle shall be removable for cleaning D. Fume Hood Duct Collar : A 12” diameter polyethylene bell-mouthed duct collar shall be located in the top of the hood plenum chamber. Coated common steel duct collars are not acceptable E. Fume Hood Lighting: A one-tube, energy-efficient, T-5 fluorescent light fixture of the size given below shall be provided in the hood roof. Illumination at 13” above the worksurface shall be at least 100 foot-candles. Hood Size, Ft. Nominal Fixture Length, Ft. 5 4 The light fixtures shall be isolated from the hood interior by a 1/4” thick tempered glass panel sealed from the hood cavity. F. Fume Hood Electrical Service: The hood superstructure shall be pre-wired and contain wire gauge, connections, fixtures and wire color coding. Wiring electrical services shall consist of two duplex receptacles and a light switch. 4 nos of 5/15 Amps (Make: North West), 230 Volt AC, and 3-wire polarized grounded with ground fault interruption. The receptacles shall be of specification grade, side wired only, to insure a positive connection. The light switch shall be 5 Amps. 230 volt AC and 3-wire polarized grounded. Wiring shall terminate in one 6” x 6” x 4” service junction box located on the fume hood roof G. Hood Work Surface:Black Granite: Hood worksurface shall be 1-1/4” thick jet black granite made in the form of a watertight pan, not less than 3/8” deep to contain spillage with a 8”& 6” wide safety ledge across the front edge. A cup drain flush with the recessed worksurface shall be provided. The worksurface and cup drain shall be available in black. H. Polyethylene Cup Sinks: Molded polyethylene cup drains shall be molded in one-piece of acid-resistant polyethylene. They shall have an integral mounting flange and an integral tailpiece with a 1-1/2" I.P.S. male straight thread outlet. The completed finish system in standard colors shall meet the performance test requirements specified under PERFORMANCE TEST RESULTS
Fire Blankets : 1.8m x 1.8m, with good fire resistant meterials
Laminar air flow chamber (vetical air flow): Laminar airflow chamber with vertical airflow, UV lamp, HEPA filter, Burner, Stainless Steel 304 grade 1.2 mm complete, internal dimension 1317 x 630 x 610 MM (L x B x H), air velocity 90 FPM at 6” from face of the filter +/- 20 Feet Per Minute, table top Stainless Steel 304 Grade 1.2 mm Thickness, Front Top Loading Pre-Filters / Complete work area will be of SS 304 including HEPA Grill, Table Top and Light Canopy Internal surface. As per IEST – RP – CC002.4, cleanliness class ISO Standard 14644 – 1 -Class 5, stages of filtration 1)Pre-Filters = 10µ with an efficiency of 90% (Washable HDPE media in FRP PU Coated Frame) 2) 2) Mini pleat HEPA Filter Encased in Aluminum Frame Final = 0.3µ with an efficiency of 99.999% (HEPA Filter).
Biosafty cabinet: The Bio safety cabinet should be Type A2 in which 70% Air should be re- circulated and 30% of the air should be exhausted with HEPA Filter The Bio Safety Cabinet must include two DC motors. High power consuming AC motors should not be used The motor must automatically adjust the airflow speed without the use of a damper to ensure continuous safe working conditions, even without maintenance adjustments. In order to preserve safety to the user and the environment, the exhaust blower on the cabinet must continue operating when the supply blower stops working. If the exhaust blower should fail, the supply filter will also be turned off. In order to ensure consistent and reliable down flow velocity across the supply HEPA filter over the life of the cabinet, the cabinet must use a pressure sensor (rather than anemometer) to detect pressure drop across the supply filter, rather than in just one point across the down flow. The pressure sensor must be encased in order to protect the sensor from temperature, humidity and other environmental phenomena that can impact the sensor’s performance. The microprocessor must display the inflow and down flow air velocities in real- time on an LED display to ensure the user knows whether or not the cabinet is working under safe operatingconditions. The dimension should 4 Feet Wide Cabinet; The Biosafety Cabinet should have microprocessor controller and same must be located on a slanted front panel so it is easy to see and reach from a seated working position in front of the cabinet.; The biological safety cabinet must be capable of achieving current state-of- the- art in energy efficiency. A biological safety cabinet with lights on and fan at operating speed should consume less than 200 watts for a nominal four foot width and have a reduced energy mode for non-operational maintenance on containment in the work area. The cabinet must automatically reduce fan/blower motor speed to 30% when the front window sash is in closed position to ensure reduced energy consumption when the cabinet is not is use. In order to provide maximum effectiveness, efficiency and safety to laboratory Personnel, UV light must be programmable to allow for specific exposure times from 0 to 24 hours. The automatic shut off feature on the UV light saves money on replacement of the bulbs. The Bio safety Cabinet should be NSF certified with listing on NSF website. The cabinet Should be provided with Microprocessor controller and large LED display for inflow and Down flow air velocity and hours of operation, Audible and visual Alarms for HEPA filter failure, blower failure, airflow speed failure, Incorrect window position. The BSC must incorporate an LED Indicator to indicate filter loading and should provide visual and audible alarm to indicate excessive HEPA filters loading which can result in unsafe airflowsdeviation from the NSF recommended inflow and down flows air velocity values measured inmeters per second or foot per minute. The cabinet should be provided with fixed / adjustable Height Stand, UV Light and one set of detachable arms rest and one / two electrical outlet.
Hot air oven: External cabinet size 90 x 85 x 170cm and Internal cabinet size 60 x 60 x 125 cm. Bottom Heated, Temperature from ambient +5°C up to 250°C, Temperature range: 50℃ to 250℃, Control accuracy: ±1 ℃, Uniformity: ± 2.0 at 100.0℃, Heating element on all sides, Minimum 3 No. of Shelves with height adjustable in 25mm steps. Digital temperature controller with timer, Aero dynamic internal design for achieving horizontal air circulation. Solid and plain bottom without electrical. Outer body made up of Mild steel, Inner body made of Stainless steel with clear bottom, Certifications: CE , ISO 9001:2015 and ISO 13485: 2003 (Medical devices), Should be provided IQ/OQ/PQ Certification. Power Supply : 220V, Single phase, 50 Hz, AC supply, Display : Digital LED Display, Vendor should be provided Manufacture authorization certificate for Specific tender
Bacterial incubator: External cabinet size 90 x 85 x 170cm and Internal cabinet size 60 x 60 x 125 cm. Temperature range from ambient +3°C to 60°C, Microprocessor, PID control / Temperature calibration / Automatic tuning. Free from noise, vibration, and mechanical troubles by film type heating method, ntuitive control panel with bright LED display. (0.1℃resolution), Dual wait on/off timer modes. (1 min. to 99 hr. 59 min.), Convenient preset function for 3 most commonly used temperature settings.Convenient sample monitoring without affecting chamber temperature via the inner tempered-glass door.Rounded inner chamber corners for easy cleaning and optimal airflow. Stackable up to 2 units using the optional stacking kit
Autoclave : Material-Stainless steel,Electrically operated Inside made up of Stainless steel and Outer Mild Steel Pedal Lifting Arrangement Superior Quality Immersion heating having Automatic Ejection Device Pressure Gauge Steam Release cock Safety Valve Operating pressure 15 PSI Operating Temperature: 121°C Power: 230 V, 50 Hz, Single phase Certifications: CE certified, ISO 13485: 2003 (Medical devices) & ISO 9001: 2015 Documentation: IQ, OQ & PQ with Manufacturer’s test reports and Users manual Vendor should be provided OEM Manufacturer Authorization Certificate Warranty: 2 Years on site warranty with periodic preventive inspection every 3 months during the warranty period Chamber Size: 250x450 mm (Diameter x Height) Capacity: 22 ltrs Rating: 1.5 KW Complete with the following: Digital Microprocessor based Temperature Indicator cum controller Water level cut off device Pressure cut off switch Digital Timer
Haemoglobinometer – BOX
Haemocytometer BOX, RBC and WBC pipets, High Quality LASER/diamont etched counting chamber with cover glass
Digital PH meter with combined electrode
Double Distillation unit
Induction top 2000W
Digital microscope: Stand : Infinity optical system, C shaped , Stable and Modular base Viewing Head : Trinocular sidentpol tube , Inclined 30deg , 360 deg Rotatable, anti fungal treated Eye Piece : WF 10X/22mm paired with eyeguard Nose Piece : Quadruple inward tilt revolving nosepiece (ball bearing) Objectives : DIN Plan infinity corrected , Achromatic objectives 4x,10x,40x 100x (oil) Stage : Mechanical single rectangular stage, area 210mm x 140mm Moving range : 70mm x65mm with graduated scale and verniers Focusing :Coaxial coarse and fine focusing mechanism with stopper to protect slides Condenser : Abbe condenser N.A =1.25 with iris diaphragm and filer holder , moving up and down Illumination : Built in Kocheler illumination , Bright white LED , Brightness adjustable , power input : 110 V -240 V 50Hz Vendor Should be Provided OEM Authorization Certificate Certifications: CE and ISO Digital Camera: Standard C-Mount camera with Aptina CMOS sensor; With hardware resolution among 3.0M to 14M; Integrated zinc aluminum alloy housing; USB2.0 interface ensuring high frame rate; Ultra-Fine color engine with perfect color reproduction capability With advanced video & image processing application Providing Windows/Linux/Mac OS multiple platforms SDK Native C/C++, C#/VB.NET, DirectShow, Twain Control API Sensor & Size : 5.1M/MT9P001©1/2.5"(5.7x4.28) Pixel( m) µ : 2.2x2.2 G Responsivity Dynamic range SNRmax :0.53 V/lux-sec , 66.5dB, 40.5dB FPS/Resolution :5@2592x1944, 18@1280x960, 60@640x480 Binning :1x1,2x2,4x4 Exposure : 0.294ms~2000ms Spectral Range :380-650nm (with IR-cut Filter White Balance : ROI White Balance/ Manual Temp Tint Adjustment/NA for Monochromatic Sensor : Color Technique Ultra-FineTM Color Engine/NA for Monochromatic Sensor Capture/Control API :Native C/C++, C#/VB.NET, DirectShow, Twain and Labview Recording System :Still Picture and Movie Cooling System : Natural Power Supply : DC 5V over PC USB Port Branded PC: Microsoft® Windows® XP / Vista / 7 / 8 /10 (32 & 64 bit) OSx(Mac OS X) Linux CPU: Equal to Intel Core2 2.8GHz or Higher Memory:2GB or More USB Port:USB3..0 High-speed Port Display:17” or Larger CD-ROM
Compound microscope : Viewing Body : Monocular tube, 45º inclined, 360ºrotatable, Eyepieces : Integrated Wide Field 10X/18mm With Foldable Eyegurad, Anti Fungus coating,, Nosepiece : Quadruple nosepiece (Ball bearing type)., Objectives : EP Series DIN Semi Plan Achromatic Objectives 10X 40X(SL) & 100X(SL), Stage : Mechanical Stage 135x125mm with low drive co-axial control, Ball bearing slides with graduated scale. SS Holder for slide 75 x 50m, movement., Focusing : Coaxial coarse and fine focusing system with ball bearin, guide ways., Condenser : ABBE Condenser N.A 1.25 with aspheric Lens Iris diagram, with snap in blue Filter, Illumination : Built in LED illumination
Dissection microscope : heavy round base , Sensitive focusing by rack-pinion movement, A joint revolving arm, replaceable bya special bulls eye lens (83mrndia.), A plano-concave mirror , Detachable hand rests on both sides, Provided with l0x & 20x eye pieces and special bulls eye lens (83mm dia.).
Calgon Scientific CO
INNATE ANALYTICS
Scientific Medical Equipments (Kerala) Pvt.
UNIVERSAL AGENCIES
UNIQUE SCIENTIFIC
Akshaya Associates
Prominent
JUPITER CHEMICALS AND LABORATORY EQUIPMENT SUPPLIERS
Scientific Enterprises
stage.html
html • 0.07 MB
tech_eval.pdf
fin_eval.pdf
aoc.pdf
finance_588355.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .