Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹31.3 LAccepted-AOC | L1 | Accepted-AOC Accepted being L1 | |
| 2 | L2₹36.1 L+₹3.6 L (11.1%)Rejected-Finance HOUSE NO 01 B JANANA DODI OPP AKSHAY HOTEL RAI KA BAGH JODHPUR RAJASTHAN 342010 | 342010 | L2 | Rejected-Finance Rejected being L2 |
Tender Value
₹43 L
EMD Value
₹86,000
Closing Date
24 Sept 2022, 6:00 pmClosed
GE (ARMY) CENTRAL JODHPUR
GE ARMY CENTRAL MULTAN LINES ARMY AREA JODHPUR
REPAIR REPLACEMENT MAINT OF SUB MAIN WIRING EARTHING MAIN DB TPN SUB DB WITH ACCESSORIES AND OTHER E M MISC WORK IN THE AREA OF AGE B R II UNDER GE ARMY CENTRAL JODHPUR
2022_MES_548061_1
GE/J/A OF 2022-23 (9130/E8)
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
JODHPUR
Please refer Tender documents.
8 documents required · 8 mandatory
₹500
GE (ARMY) CENTRAL JODHPUR
₹86,000
Yes
17 Oct 2022
27 Aug 2022
1 Oct 2022
27 Aug 2022
24 Sept 2022
10 Sept 2022
Amount
Note:- (i) All items in BOQ are for "Materials and labour / Supply and fix" and to be executed in "Replacement/Renewal" unless otherwise specifically mentioned as "Supply only" or Fixing only" in BOQ Bidders are requested to quote their rates accordingly.
Taking down copper/aluminium sub main wiring surface/ concealed complete, including fixture and fittings removing materials from site of work complete or removing materials to store for keeping in safe custody or for taking credit and making good disturbed surfaces of walls, floors, etc, complete all as directed by Engr-in-Charge.
S&F sub main wiring with two runs of 6 sqmm & one run of 6 Sqmm earth wire 1100 volt grade PVC insulated but unsheathed multi stranded copper conductor FRLSH cable, single core cable conforming to IS 694 with valid CML No. & ISI Marked, (Phase-Red, Neutral-Black, Earth-Green) drawn through in existing PVC/steel conduit/surface mounted, (ISI marked) fixed in wall or ceiling etc., complete all as specified and as directed by Engr-in-Charge. Note :- Three runs of 6 sqmm shall be measured as one length for the purpose of measurement.
S&F sub main wiring with two runs of 6 sqmm & one run of 6 Sqmm earth wire 1100 volt grade PVC insulated but unsheathed multi stranded copper conductor FRLSH cable, single core cable conforming to IS 694 with valid CML No. & ISI Marked, (Phase-Red, Neutral-Black, Earth-Green) drawn through and including 25mm dia PVC rigid conduit with accessories surface mounted on wall / ceiling with PVC saddles and cadmium plated steel screws and connected to common earth dolly complete all as specified and directed. Note :- Three runs of 6 sqmm and one run of PVC conduit shall be measured as one length for the purpose of measurement.
All as per item No.4.00 here-in-above, but cable drawn through and including 25mm dia PVC rigid conduit with accessories, concealed on wall / ceiling & etc. Note :- Three runs of 6 sqmm and one run of PVC conduit shall be measured as one length for the purpose of measurement.
All as per item No.4.00 here-in-above, but cable size 4 Sqmm Note :- Three runs of 6 sqmm and one run of PVC conduit shall be measured as one length for the purpose of measurement.
Taking down copper/aluminium point wiring surface/ concealed (light, fan, socket or power) complete, including fixture and fittings such as switches, ceiling roses, pendants, regulators, sockets, light fitting, bell etc. removing materials from site of work complete or removing materials to store for keeping in safe custody or for taking credit and making good disturbed surfaces of walls, floors, etc., complete all as directed by Engr-in-Charge.
M&L Point wiring using approved colour coding as per IS code, with multi stranded copper conductor 1.5 sq mm nominal cross-sectional area, single core, PVC insulated and unsheathed FRLSH cable 1100 Volts grade, ISI-694 marked with valid CML No.in and including heavy duty drawn through and including in 25mm dia PVC rigid conduit with all accessories complete surface mounted in wall/roof/floor etc, ISI marked and terminated to and including provision of gang terminal boxes with 3mm thick hylam sheet cover on top for fixing switches, sockets / regulators etc., inciuding PVC insulated multistranded copper conductor 1.5 sq mm nominal cross sectional area single core FRLSH cable as earth continuity conductor to common earth and connecting to earth dolly for,one way switch One light / fan /bell point controlled by one, one way switch complete all as specified and directed .
All as per Serial Item No.8.00 here-in-above but for one 3 pin socket outlet 5/6 Amps on the same board with other switches complete all as specified and as directed.
All as per Serial Item No.8.00 here-in-above but for one 3 pin socket outlet 5/6 Amps on the independent board , complete all as specified and as directed.
All as per Serial Item No.8.00 here-in-above but one light point controlled by two, two-way switches
All as per item No 08 here-in-above but with using 2.5 Sq mm FRLSH single core multistanded copper conductor cable and 2.5 sq mm PVC FRLSH insulated unsheathed stranded copper conductor for common earth wire for 6 pin 16 Amp socket outlet on independent board .
M&L Point wiring using approved colour coding as per IS code, with multi stranded copper conductor 1.5 sq mm nominal cross-sectional area, single core, PVC insulated and unsheathed FRLSH cable 1100 Volts grade, ISI-694 marked with valid CML No.in and including PVC casing & caping on surface mounted in wall / roof / floor etc, ISI marked with PVC terminal box fixed with cadmium plated screws with washers for mounting of switches, sockets and fan regulators etc, with and inciuding PVC insulated multistranded copper conductor 1.5 sq mm nominal cross sectional area single core FRLSH cable as earth continuity conductor to common earth and connecting to earth dolly for,one way switch One light/ fan/bell point controlled by one, one way switch 5Amps complete all as specified and directed .
All as per item No 13 here-in-above but one socket outlet 3 pin 5/6 Amps on same board
All as per item No 13 here-in-above but one socket outlet 3 pin 5/6 Amp on independent board
All as per item No 13 here-in-above but one light point controlled by two, two-way switches
All as per item No 13 here-in-above but with using 2.5 Sq mm single core multistanded copper conductor cable including 2.5 sq mm PVC insulated unsheathed stranded copper conductor for common earth wire for 6 pin 16 Amp socket outlet on independent board .
M&L Point wiring using approved colour coding as per IS code, with multi stranded copper conductor 1.5 sq mm nominal cross-sectional area, single core, PVC insulated and unsheathed FRLSH cable 1100 Volts grade, ISI-694 marked with valid CML No.in and including heavy duty drawn through and including in 20mm dia PVC rigid conduit with all accessories complete concealed (or on surface as per site requirement) in wall/roof/floor etc, ISI marked and terminated to and including provision of sunken 1.6mm thick pressed steel terminal boxes with 3mm thick hylam sheet cover on top for fixing switches, sockets / regulators etc., inciuding PVC insulated multistranded copper conductor 1.5 sq mm nominal cross sectional area single core FRLSH cable as earth continuity conductor to common earth and connecting to earth dolly for,one way switch One light / fan / bell point controlled by one, one way switch complete all as specified and directed .
All as per item No 18 here-in-above but one three pin 5/6 Amp socket on same board with other switches.
All as per item No 18 here-in-above but one three pin 5/6 Amp socket on independent board.
All as per item No 18 here-in-above but one light point controlled by two, two-way switches
All as per item No. 18.00 here-in-above but with 2.5 Sq.mm. (nominal area) cable for one 3 Pin 16 amp socket on independent board including one 2.5 sqmm copper conductor multi stranded green colour PVC insulated unsheathed, FRLSH cable 1100 volts grade as earth wire upto common earth & connected to earth dolly complete all as specified and directed by Eng.-in-charge.
S&F switch piano, flush type, single pole, one way, 5/6 Amps, 230 Volts, ISI Marked, complete all as specified and as directed.
S&F switch piano, flush type, single pole, one way,15/16 Amps, 230 Volts, ISI Marked, complete all as specified and as directed.
S&F socket outlet, flush type, single pole, 2 in 1, 3 Pin, 5/6 Amps, 230 Volts,ISI Marked, complete all as specified and as directed.
S&F socket outlet, flush type, single pole, 2 in 1, 6 Pin, 6/16 Amps, 230 Volts,ISI Marked, complete all as specified and as directed.
M&L ceiling rose, 3 phase / PVC / Polycarbonate, isolated body, ISI Marked, complete all as specified and as directed.
S&F lamp holder insulated body polycarbonate type with back plate, complete all as specified and as directed by Engr-in-Charge.
S&F bell ding dong type AC, 230 Volts, ISI Marked, complete all as specified and as directed.
S&F bell push, single pole, one way, 5/6 Amps, 230 Volts, ISI Marked, complete all as specified and as directed.
S&F Electronic fan regulator, 120W, stepped type, 2 module and connecting electrically, ISI Marked, complete all as specified and as directed by Engr-in-Charge.
Taking down and refixing / Hanging only ceiling fan after servicing (Cleaning, oiling and greasing) and connecting up including provision of cable from ceiling rose or connector to fan including filling cavities with filler, one coat after cleaning all dust etc., complete all as directed.
Taking down and refixing / Hanging only Exhaust fan after servicing (Cleaning, oiling and greasing) and connecting up including provision of cable from ceiling rose or connector to fan including filling cavities with filler, one coat after cleaning all dust etc., complete all as directed.
S&F in replacement of Prewired distribution board (sheet metal enclosures) SPN 4 way with suitable rated 100 Amps bus bar for Double door DB's of apporved gauge conforming to IS relevant, IP-43 protection, 240 volt, including taking down old u/s material, complete all as specified and directed by Engr-in-charge. Note -Rate are deemed to be included for flashing in wall concealed complete, making good and matching existing surface Make :-Legrand/ ABB / Schneider.
S&F in replacement of Prewired distribution board (sheet metal enclosures) SPN 8 way with suitable rated 100 Amps bus bar for Double door DB's of apporved gauge conforming to IS relevant, IP-43 protection, 240 volt, including taking down old u/s material, complete all as specified and directed by Engr-in-charge. Note -Rate are deemed to be included for flashing in wall concealed complete, making good and matching existing surface Make :-Legrand/ ABB / Schneider.
S&F in replacement of Prewired distribution board (sheet metal enclosures) TPN 4 way with suitable rated 100 Amps bus bar for Double door DB's of apporved gauge conforming to IS relevant, IP-43 protection, 240 volt, including taking down old u/s material, complete all as specified and directed by Engr-in-charge. Note -Rate are deemed to be included for flashing in wall concealed complete, making good and matching existing surface Make :-Legrand/ ABB / Schneider.
S&F in replacement MCB single pole 240 volts rating from 6 to 32 Amps, with rupturing capacity 10 KA, 'C' curve type, (ISI marked), with over load and short circuit protection, as in replacement, including taking down old u/s material complete all as specified and as directed by Engg.-in-charge. Make : Legrand/ ABB/ Schneider
S&F in replacement MCB SPN 240 volts rating from 40 Amps, with rupturing capacity 10 KA, 'C' curve type, (ISI marked), with over load and short circuit protection, as in replacement, including taking down old u/s material complete all as specified and as directed by Engg.-in-charge. Make : Legrand/ ABB/ Schneider
S&F in replacement MCB TPN 415 volts rating from 63 Amps, with rupturing capacity 10 KA, 'C' curve type, (ISI marked), with over load and short circuit protection, as in replacement, including taking down old u/s material complete all as specified and as directed by Engg.-in-charge. Make : Legrand/ ABB/ Schneider
S&F in replacement electronic driver as per sample for LED fitting up to 22 watt, complete all as specified and as directed by Engg.-in-charge. Make Havells/Philips/Bajaj
S&F in replacement electronic driver as per sample for LED fitting up to 45 watt complete all as specified and as directed by Engg.-in-charge. Make Havells/Philips/Bajaj
Taking down and re-fixing LED batten fittings 20/22 watt, ,branded make such as any make etc.including 1Nos tube rod complete with all accessories.
Supply and laying (trenches) or fixing or passing through pipe,XLPE insulated cable, 1100 volts grade armoured heavy duty aluminium conductor, cross sectional area 10 Sqmm 2 core nominal, complete all as specified and as directed by Engg.-in-charge.
All as per item No. 43.00 here-in-above, but cable nominal cross sectional area is 16 Sqmm 2 core.
All as per item No. 43.00 here-in-above, but cable nominal cross sectional area is 16 Sqmm 4 core.
All as per item No. 43.00 here-in-above, but cable nominal cross sectional area is 25 Sqmm 4 core.
Supply and fixing LED flood light 70 watt 230 V AC outdoor type with thermal management in multiple optics and equipped with IP66 protection, with impact and corrosion resistant complete with driver and lamp, complete all as specified and as directed by Engg.-in-charge. Make : Philips/ Bajaj/ Havells
Supply and fixing post top lantern LED type 20 watt 230 watt volts AC outdoor type with decorative post top for 360 degree indirect light IP 65 protection with impact and corrosion resistant complete with driver and lamp, complete all as specified and as directed by Engg.-in-charge. Make : Philips/ Bajaj/ Havells
Taking down sunken pressed terminal boxes of any size and S&Fsunken pressed steel terminal boxes in wall of existing size including top sheet of 3 mm thick, switch, sockets complete in all respect and as specified and directed by Engr-in-Charge.
Endura rugby energy saving new generation 10W LED bulk head luminaire with opal diffuser complete with lamp 10W 6000K with all accessories including connecting up with twin core twisted flexible copper conductor cable of suitable size complete all as specified and directed. Make :- Havells Model No. LHEOAOP7UZ6WO1O or techno commercially equivalent make in Bajaj / CG / Philips
S & F LED tube rod upto 22 watt incl connection complete all as specified and directed. Make: Baja/Philips/CG
M&L cutting and taking out old burnout winding & rewinding of submersible pump monoblock type of capacity upto 3 HP, single or three phase, with super enameled copper wire , any make incl connection, testing & commissioning, complete all as specified and directed by Engg.-in-charge
S&F LED bed light upto 5 watt, COB type complete with electronic driver and including connecting up to fiting with flexible cable of suitable size.. Make: Philips/Havells/Wipro.
S&F 7 Watt LED wall mounting light, decorative, SS finish fixture with opal glass diffusure suitable and including 7 Watt LED Lamp (Thrid type ), complete all as specified and as directed. Make Havells Cat No.LHJC02108499 or techno commercially equivalent make in Bajaj / Philips
S&F in replacement connecting, and commissioning of street light fitting 25 watt LED , IP-65 protection, single piece pressure dia cast aluminium alloy housing high impact 4 mm thick heat resistant toughned clear glass cover for lamp and matrix of LEDs in built electronic driver upto 4 KV surge protection device and setting& input power 35 W system lumens 85/W operating voltage 160-260 V contror gear compartment with high voltage, Prewired including 1.20 mtr long 32mm bore light grade GI pipe mounting bracket made to shape with and including MS clamp of F1 40 mmx6mm with bolts , nuts & washers and conductor to fitting with 3 core 1.5 sqmm pvc insulated cable complete all as specified Make : Philips/ Bajaj/ Havells
S&F bracket made out of 32 mm dia GI pipe, medium grade, suitable for Security light, with all accessories and including fixing arrengment etc.complete all as specified and directed.
S&F square shape surface mounted down light LED fittings 15/18 Watt complete with all accessories and including fixing arrengment etc.complete all as specified and directed. Make: Philips/Havells/Wipro.
S&F decorative wall light made up of high grade engineering plastic material suitable for 9 W LED lamp Make:- Havells Cat part No. -LHFOFWE1TZ1W012 or its equivalent model in Philips/bajaj
M&L in repairs for earthing complete with galvanised iron earth plate electrode 600 mm x 600 mm x 6 mm thick, burried directly and preferably vertically in ground, earth pit not less than 2.25 Mtr deep below ground level with top edge of the plate not less than 1.5 m below ground level connetced with galvanised iron earth lead wire of size 4mm dia by means of nuts, bolts, check nuts and washers made of galvanised iron or steel earthing lead to be protected by galvanised iron pipe 40 mm bore (medium grade) and other end connected to earthing test point or lightening arrestor or main controlling switch as directed including providing funnel with 20mm bore galvanised iron pipe (light grade), wire mesh, charcoal or coke and common salt in alternate layer of 15cm (compacted thickness) all round the earth electrode, concrete earth pit in PCC (1:3:6) type C-1 (with 20mm graded aggregate), 50mm thick precast RCC (1:2:4) cover slab (re-inforced with 8mm dia TMT bar @ 15 cm C/C bothways and suitable handle made of 10mm dia) including necessary earth work in excavation, returning filling and removal of surplus earth upto a distance not exceeding 50 m etc all as shown on electrical plate No. 3 of MES Schedule Part-I(2009) complete including testing on completion, complete all as specified and as directed by Engr-in-Charge. Note:- (i) Item includes the cost of 7.5 metre GI pipe for protection of earth lead. (ii) Item includes the cost of 7.5 metre GI earth lead.
All as per tem No. 59.00 here-in-above, but with 25X4 mm copper strip, complete all as specified and as directed by Engr-in-Charge.
S&F earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc. as required galvanised iron earth lead wire of size 4mm dia including taking down old strip complete all as specified and directed.
All as per tem No. 61.00 here-in-above, but with 25X4 mm GI strip, complete all as specified and as directed by Engr-in-Charge.
Excavation in trenches n.exc 1.5m wide and n.exc 1.5 m in depth for laying of cables etc. and n.exc 1.5m in depth and getting out in any type of soil, complete all as specified and directed.
Returning, filling in trenches with excavated soil, including spreading, levelling watering and well remain in la ers not exceeding 25cm thick complete all as specified and directed.
Removing excavated material (soil) not exceeding 50 meter and deposing where directed at a level not exceeding 1.5 meter here-in-above the starting point, complete all as specified and directed.
S&F RCBOs for earth leakage, overload and short circuit protection Double pole, 100mA, 40 Amp, complete all as specified and directed by Engr-in-Charge.
S&F RCBOs for earth leakage, overload and short circuit protection Double pole, 100mA, 63 Amp, complete all as specified and directed by Engr-in-Charge.
M & L pipe galvanized iron "light grade complete with all fitting laid in road crossing and on pole mounting, complete all as specified and directed ISI marked of 40mm bore, complete all as specified and directed by Engr-in-Charge.
S&F in replacement capacitor 2.50 Mfd 220 volts, complete all as specified by Engg.-in-charge.
S&F in replacement sub main wiring with two runs of PVC insulated but unsheathed multi stranded copper conductor FRLSH cable 1100 volt grade, as per IS code 694 with valid CML No. & ISI Marked, of size 6.00 Sqmm and one run of 6.00 Sqmm single core PVC insulated but unsheathed multi stranded copper conductor FRLSH cable (Phase-Red, Neutral-Black, Earth-Green) 1100 volt grade as earth lead drawn through in and including non metallic PVC conduit of size 25 mm dia (external) with wall thickness not less than 1.8 mm, (ISI marked) concealed in wall including accessories like bends, tees junction boxes, etc fixed in wall or ceiling etc., complete all as specified and as directed by Engr-in-Charge. NOTE: Two runs of 6.00 sqmm cable with one run of 6.00 sqmm cable as earth wire and PVC conduit shall be measured & paid for as one length.
S&F in replacement Air termination, single pointed aluminium rod 12mm dia and 300mm long all as direced by Engr-in-Charge.
S&F in replacement Test point terminal block made of gun metal or phosphorus bronze size 75x75x25mm drilled and screwed including 3 nos. 8mm dia 25mm long hex. head screwall as direced by Engr-in-Charge.
S&F in replacement Aluminium strip 25 x 3.15mm with saddles and fixing screws etc. for roof conductors and down conductors here-in-above ground all as direced by Engr-in-Charge.
S&F double compression copper stain less steel gland for fixing armoured cable in panel and DBs of size 4 core 6 Sq mm to 35 sq mm size all as specified and directed by Engr-in-Charge.
Taking down carefully of existing Distribution Box (4 way, 8 way DBs and TPNs) including MCBs and SPNs, seperate the serviceable and Unserviceable items and refixing the same concealed in wall and matching existing surface including arrange of outgoing submain wiring and incoming service cable with lugs in DBs and distribute the load equally for each Phase all as specified and directed by Engr-in-Charge.
S&F switch piano, flush type, single pole, two way, 5/6 Amps, 230 Volts, ISI Marked, complete all as specified and as directed. Make : Havells / Anchor / Crabtree
S&F MCB SPN 240 volts rating from 63 Amps, with rupturing capacity 10 KA, 'C' curve type, (ISI marked), with over load and short circuit protection, as in replacement, including taking down old u/s material complete all as specified and as directed by Engg.-in-charge. Make : Legrand/ ABB/ Schneider
S&F MCB TPN 415 volts rating from 40 Amps, with rupturing capacity 10 KA, 'C' curve type, (ISI marked), with over load and short circuit protection, as in replacement, including taking down old u/s material complete all as specified and as directed by Engg.-in-charge. Make : Legrand/ ABB/ Schneider
M & L GI pipe "light grade" complete with all fitting laid in road crossing and on pole mounting, complete all as specified and directed ISI marked of 15mm bore, complete all as specified and directed by Engr-in-Charge.
S&F modular type PVC rectangular block for mounting, switches, sockets, fan regulator etc. with 3 mm thick plastic laminated sheet cover of size 100 mm x 100 mm and 50 mm deep all as specified and directed by Engr-in-Charge.
S&F PVC rectangular block modular type for mounting, switches, sockets, fan regulator etc. with 3 mm thick plastic laminated sheet cover of size 175 mm x 100 mm and 50 mm deep all as specified and directed by Engr-in-Charge.
S&F PVC rectangular block modular type for mounting, switches, sockets, fan regulator etc. with 3 mm thick plastic laminated sheet cover of size 200 x 150 and 50 mm deep, complete all as specified and directed by Engr-in-Charge.
S&F in replacement 20/25mm dia PVC conduit pipe, heavy duty, as in sub main wiring, Conforming to IS code with vaalid CMLNo., ISI Marked (MMS) grade with clamps and accessories all as specified and directed. Make : Polycab/Plaza/Kalinga
S&F in replacement 1.5 Sqmm PVC insulated and unsheathed FRLSH cable 1100 Volts grade, ISI-694 marked with valid CML No.using, single phase circuit, with multi stranded copper conductor, single core, any length, of any brunt circuit, drawn through in existing steel/PVC rigid conduit with all accessories complete concealed in wall/roof/floor etc, ISI Marked, , complete all as specified and directed by Engr-in-Charge.
All as per item No. 84.00 here-in-above, but cable cross sectional area is 2.50 Sqmm
All as per item No. 84.00 here-in-above, but cable cross sectional area is 4.00 Sqmm
S & F LED strip light for indoor & outdoor with driver, 5mtr in length, COB type, complete all as specified & directed. Make -Crompton Cat part No- LST65RGB . or techno commercially equivalent make in Bajaj / Philips
S&F mirror light fitting, as per sample, with energy efficient light fitting LED type 8/9 watt duly prewired and complete with all acessories etc complete all as specified and as directed. Make : Philips/CG/Wipro/BAJAJ/Havells
S&F in replacement of Prewired distribution board (sheet metal enclosures) SPN 12 way with suitable rated 100 Amps bus bar for Double door DB's of apporved gauge conforming to IS relevant, IP-43 protection, 240 volt, including taking down old u/s material, complete all as specified and directed by Engr-in-charge. Note -Rate are deemed to be included for flashing in wall concealed complete, making good and matching existing surface Make :-Legrand/ ABB / Schneider.
S&F MCB SPN 240 volts rating from 100 Amps, with rupturing capacity 10 KA, 'C' curve type, (ISI marked), with over load and short circuit protection, as in replacement, including taking down old u/s material complete all as specified and as directed by Engg.-in-charge. Make : Legrand/ ABB/ Schneider
S&F in replacement MCCB, 'A' Frame, thermal adjustable magnectic setting, Ics = 75%, 16 kA, 415V, 100 Amp, 4 Pole with over load and short circuit protection, (ISI marked), as in replacement, complete all as specified and as directed by Engg.-in-charge. Make : Legrand/ ABB/ Schneider
S&F in replacement MCCB, 'A' Frame, thermal adjustable magnectic setting, Ics = 75%, 16 kA, 415V, 125 Amp, 4 Pole with over load and short circuit protection, (ISI marked), as in replacement, complete all as specified and as directed by Engg.-in-charge. Make : Legrand/ ABB/ Schneider
All as per item No. 18.00 here-in-above but with 4.00 Sq.mm. (nominal area) cable for one 3 Pin 16 amp socket on independent board including one 4.00 sqmm copper conductor multi stranded green colour PVC insulated unsheathed, FRLSH cable 1100 volts grade as earth wire upto common earth & connected to earth dolly complete all as specified and directed by Eng.-in-charge.
S&F in replacement of LED lights fitting 1x 20W, 220V, AC decorative box type with driver, lamp holder, 4 feet long, including LED tube light connecting up with three core flexible copper conductor cable of suitable size from ceiling rose, including taking down old u/s material, complete all as specified and as directed. Make : Bajaj Cat No. BCLSB 20 WH or Equivalent in Philips/ Havells as approved by GE.
S&F in replacement of LED lights fitting 1x 10W, 220V, AC decorative box type with driver, lamp holder, 2 feet long, including LED tube light connecting up with three core flexible copper conductor cable of suitable size from ceiling rose, including taking down old u/s material, complete all as specified and as directed. Make : Bajaj Cat No. BCLSB 10 WH or Equivalent in Philips/ Havells as approved by GE.
S&F connecting, and commissioning of street light fitting 35 watt LED , IP-65 protection, single piece pressure dia cast aluminium alloy housing high impact 4 mm thick heat resistant toughned clear glass cover for lamp and matrix of LEDs in built electronic driver upto 4 KV surge protection device and setting& input power 35 W system lumens 85/W operating voltage 160-260 V contror gear compartment with high voltage, Prewired including 1.20 mtr long 32mm bore light grade GI pipe mounting bracket made to shape with and including MS clamp of F1 40 mmx6mm with bolts , nuts & washers and conductor to fitting with 3 core 1.5 sqmm pvc insulated cable complete all as specified Make : Philips/ Bajaj/ Havells
S&F exhaust fan, heavy duty steel body, AC single phase 300 mm sweep, 900 RPM complete with louvers including cutting / making holes in wall fixing/grouting of frame & connecting with & including 3 core PVC insulated copper conductor flexible cable of size 23/0.0076 (or eq. Size in mm) from ceiling rose to fan, complete all as specified and as directed by Engg.-in-charge. Make : Havells/ Bajaj/ USHA
Single pole and neutral enclosure with two pin earth plug and socket with one MCB SP 20 Amps complete all as specified and as directed.
S&F Vertical Distribution Board, double Door, suitable for 'A' Frame FP MCCB 100A made out of CRCA mild steel sheet surface with insulated material like polyester or with epoxy powder coating and IP 43 & IK 09 protection, TPN 4 way, 415 volts with bus bar rating 300 Amps, dust and vermin proof, suitable for incorporation of MCB’s and MCCB etc and making all necessary connections, duly flush of wall surface, complete all as specified and directed. Make : Havells Cat Part No DHDLVSRWGOFO04 or its techno commercially equivalent make in Bajaj / Philips Note : MCCB & MCB shall be measured and paid for separately.
S&F in replacement sub main wiring with two runs of 10 sqmm & one run of 10 Sqmm earth wire 1100 volt grade PVC insulated but unsheathed multi stranded copper conductor FRLSH cable, single core cable conforming to IS 694 with valid CML No. & ISI Marked, (Phase-Red, Neutral-Black, Earth-Green) drawn through and including 32mm dia PVC rigid conduit with accessories surface mounted on wall / ceiling with PVC saddles and cadmium plated steel screws and connected to common earth dolly complete all as specified and directed. Note :- Three runs of 10 sqmm and one run of PVC conduit shall be measured as one length for the purpose of measurement.
M&L moldular point wiring using approved colour coding as per IS code, with multi stranded copper conductor 1.5 sq mm nominal cross-sectional area, single core, PVC insulated and unsheathed FRLSH cable 1100 Volts grade, ISI-694 marked with valid CML No.in and including heavy duty drawn through and including in 20mm dia PVC rigid conduit with all accessories complete concealed (or on surface as per site requirement) in wall/roof/floor etc, ISI marked and terminated to and including provision of sunken 1.6mm thick pressed steel terminal boxes with 3mm thick hylam sheet cover on top for fixing switches, sockets / regulators etc., inciuding PVC insulated multistranded copper conductor 1.5 sq mm nominal cross sectional area single core FRLSH cable as earth continuity conductor to common earth and connecting to earth dolly for,one way switch One light / fan / bell point controlled by one, one way switch complete all as specified and directed .
All as per item No 101 here-in-above but one three pin 5/6 Amp socket on same board with other switches.
All as per item No 101 here-in-above but one three pin 5/6 Amp socket on independent board.
All as per item No. 101.00 here-in-above but with 2.5 Sq.mm. (nominal area) cable for one 3 Pin 16 amp socket on independent board including one 2.5 sqmm copper conductor multi stranded green colour PVC insulated unsheathed, FRLSH cable 1100 volts grade as earth wire upto common earth & connected to earth dolly complete all as specified and directed by Eng.-in-charge.
All as per item No. 101.00 here-in-above but with 4.0 Sq.mm. (nominal area) cable for one 3 Pin 16 amp socket on independent board including one 4.0 sqmm copper conductor multi stranded green colour PVC insulated unsheathed, FRLSH cable 1100 volts grade as earth wire upto common earth & connected to earth dolly complete all as specified and directed by Eng.-in-charge.
S&F switch piano, modular type, single pole, one way, 5/6 Amps, 230 Volts, ISI Marked, complete all as specified and as directed.
S&F switch piano, modular type, single pole, one way,15/16 Amps, 230 Volts, ISI Marked, complete all as specified and as directed.
S&F socket outlet, modular type, single pole, 2 in 1, 3 Pin, 5/6 Amps, 230 Volts,ISI Marked, complete all as specified and as directed.
S&F socket outlet, modular type, single pole, 2 in 1, 6 Pin, 6/16 Amps, 230 Volts,ISI Marked, complete all as specified and as directed.
S&F bell multi music type AC, 230 Volts, ISI Marked, complete all as specified and as directed.
S&F modular type bell push, single pole, one way, 5/6 Amps, 230 Volts, ISI Marked, complete all as specified and as directed.
S&F Electronic fan regulator, 120W, modular type, 2 module and connecting electrically, ISI Marked, complete all as specified and as directed by Engr-in-Charge.
NOTE:- (i)- Quantities are clubbed in BOQ for different Jobs. For which ref. Annexure-I on Sl. page. No. 35(R) to 36(R) of tender document. (ii)- The contract sum shall be arrived at after duducting amount of schedule of "Credit" from the Total quoted amount
Nvimal Engineers and Contractor
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .