2. SITC of Medical Gas Pipe Line System work for construction of Sub District Hospital at Atru.
2026_MEDIC_586655_2
NIT No 07/2026-27 EXECUTIVE ENGINEER MEDICAL AND HEALTH KOTA
Open Tender
Electrical Works
Percentage
90 days
KOTA
Please refer Tender documents.
2 documents required · 2 mandatory
₹1,500
RTGS-NEFT TO HDFC BANK AC 50100255592722
₹1.8 L
14 Sept 2026
13 Aug 2026
15 Sept 2026
13 Aug 2026
14 Sept 2026
13 Aug 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | SITC of MGPS pipe of medically grade as per BSEN-13348 with third party certification from Lloyds/TUV degreased [ie free from oil, grease and particulate matters) seamless copper pipe confirming to ASTM B88 and all copper joining done by brazing with AWSA5.8, classification BCuP-5 or BS 1845 following procedure in accordance with ASTM B828 after purging with nitrogen. All pipe cutting shall be carried out with a radial pipe cutter and copper pipe fitting's shall comply with B4 alloy designation. Adequate support shall be provided while laying pipeline testing shall be done at 17 bar and after testing pipe shall be painted with two coat of enamel paint as per colour codification as per ISO 7396-Part-1 2016.Thisd partyTest reportshall be submitted. all as per approved by Engineer in charge. | 2,360 | kg | - | - |
| 2 | SITC of non lubricated ball type nicel Coated Isolation Valve with adapter & PTFE Seat having quarter turn / Butterfly handle opening of following sizes suitable fo flow capacity of required LPMas per the size of valve at 4.7 bar with maximum allowable pressure of 30 bars and suitable for working temperature renging - 20 °C to 130 °C. Appropriate Test Certificate/ report of product/ accessories from OEM shall be submitted. All a per approved by Engineer in charge. For 12 MM OD pipe (only to be used in oxygen line) | 110 | Each | - | - |
| 3 | For 15 MM OD pipe | 25 | Each | - | - |
| 4 | For 22 MM OD pipe | 25 | Each | - | - |
| 5 | For 28 MM OD pipe | 16 | Each | - | - |
| 6 | For 42 MM OD pipe | 6 | Each | - | - |
| 7 | For 54 MM OD pipe | 6 | Each | - | - |
| 8 | SITC of Gas outlet point Oxy, (AR-4), (AR-7) and Vaccum (8.7 psig) for dispeensing medical pgases (oxygen/air/Vaccum) at point of use confirming to BSEN ISO 9 170-1:2008.. The gas outlet are quick connect type. it should have colour coding for dieffrent gas source and should accept only respective adapters as required.appropriat Test Certificate/ report of product/accessories from OEM shall be submitted. The Product should be CE Certified /CE marked. (oxygen - 100nos, vaccum - 100nos, air-4 -50(only in OT,ICU or where ventilator is installed), air-7 - 5nos(only in OT), nitrous - 5nos(only in OT) | 280 | Each | - | - |
| 9 | SITC of BPC (back pressure compensated) flow meter with Humidifire made of nickei plated body. Double jacketed with flow gradations CE Marked on it. Desired flow will be setteided through rotary knob. Flow range shuld be between 0 to 15 lpm & work should be executed as per direction of engineer in charg. Appreoprite Test Certificate / report of product /accessories from OEM shall be submitted. The Product should be CE Certified/ CE Marked. | 103 | Each | - | - |
| 10 | SITC of ward suction unit (Sution Controller and Collevtion Jar - 600 ml caapicity) with posibility to configure required capcity collection Jar and should meets the reuirements as per BSEN ISO 10079-3:2009. The unit must designed to operate with the vaccum line of MGPS. The collection jar must accumpained with Vaccum regulator suitable for 0-14.7 psig with flow rate 0-55 lmp (min)for operating tempurature - 18 °C to 50 °C with ON/OFF facility. The collection Jar should be transparent, made of hogh quality polycarbonate that can be autoclaved at 121 °C for 20 minuts for reuse and provided with auto stop to avoid over spill and contamination of the suction source when the jar collection reached optimized level. The completer unit supplied with filter to protect the source and pipe line from baceterial contamination. Appropriate Test Certificate / report of product/ accessories from OEM shall be submitted . The Product shpuld be CE Certificate / CE marked | 103 | Set | - | - |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 1.98 MB
Tendernotice_2.pdf
PDF • 5.33 MB
Tendernotice_3.pdf
PDF • 1.59 MB
Tendernotice_4.pdf
PDF • 0.64 MB
BOQ_1041893.xls
BOQ • 0.26 MB
DATECORRI.pdf
PDF • 0.22 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at [email protected].