Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹16.6 LAccepted-Finance GROUND FLOOR G 1154 A MANSAROVAR PARK SHAHDARA DELHI 110032 | SHAHDARA | DELHI | 110032 | ₹16.6 L | L1 | Accepted-Finance Selected |
| 2 | L2₹22.3 LAccepted-Finance | ₹22.3 L | L2 | Accepted-Finance Selected |
Tender Value
₹24.8 L
EMD Value
₹49,529
Closing Date
9 Feb 2026, 12:00 pmClosed
Executive Engineer (E)
O/o EE(E) PWD EMD M-351, R.No.185, Old Sectt Delhi
Repairing / Rewiring work of LED fixtures, fans, switch board and Split AC etc. at Place of safety / Special Home for Boys, DWCD, Majnu Ka Tila, Delhi.
2026_PWD_286021_1
112/2025-26/EMD M-351/EE(E)
Open Tender
Miscellaneous Services
60 days
Majnu Ka Tilla
Please refer Tender documents.
11 documents required · 11 mandatory
₹0
₹49,529
9 Feb 2026
2 Feb 2026
9 Feb 2026
2 Feb 2026
9 Feb 2026
2 Feb 2026
Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable in surface/ recessed steel conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable etc. as required. a) Group C
Rewiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable and 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable as earth wire in existing surface/ recessed steel/PVC conduit including dismantling as required. i) Group C
Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc. as required.
3 Module (100 mmX75 mm)
6 Module (200 mmX75 mm)
8 Module (125 mmX125 mm)
12 Module (200 mmX150 mm)
Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface/ recessed steel/ PVC conduit as required.
3 x 1.5 sq. mm
3 x 4 sq. mm
3 x 6 sq. mm
Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required.
Supplying and fixing of following sizes of steel conduit along with accessories in surface/recess including painting in case of surface conduit, or cutting the wall and making good the same in case of recessed conduit as required.
Supplying and fixing 5 A to 32 A rating, 240/415 V, 10kA, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.
Single pole
Supplying and fixing of following ways surface/ recess mounting, vertical type, 415 V, TPN MCB distribution board of sheet steel, dust protected, duly powder painted, inclusive of 200 A tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCBs (but without MCBs and incomer) as required. (Note: Vertical type MCB TPDB is normally used where 3 phase outlets are required.)
8 way (4 + 24), Double door
Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.
5/6 A switch
15/16 amp switch
3 pin 5/6 A socket outlet
6 pin 15/16 A socket outlet
Supplying, Installation, Testing & Commissioning of SMC pole Box of size 250mm x 200mm x 105mm with hinged cover on surface/ recess/pole complete with aluminium connector strip - 2 Nos, MS Clamp - 2 Nos., 6-32amp. C series SPMCB- 1 No., having IP: 66 protection connection etc. as reqd.
Supplying, Installation, Testing & Commissioning of Flood Light, powder coated pressure die cast aluminium body with built in or separate driver as per the requirement with Driver efficiency >85%, Input voltage: Input voltage: 140-270 Volt AC, frequency 50/60 hz, Operating temp range -5 0C to 50 0C, internal surge protection of 5 KV L,N,E as per IEC 61000-4-5, Driver efficiency >85%,THD < 10% as per IEC 61000-3-2, P. F.≥0.95, IP-66,IK-10, CRI >70, under voltage and over voltage protection, EMI-EMC as per CISPR-15, lenses for beam angle 30 deg-120deg as per the application and the project requirement, suitable tilt able fitting, life time (LED, Driver & electrical circuitry) of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends as per LM80 extrapolation IES TM-21-11 report, CCT 3000°K / 4000°K / 5700°K /6500°K (As per ANSI Bin), SDCM(Standard Deviation Colour Matching) <5, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard complete in all respect i/c external connections with 1.5 sq.mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥120 and <135 lm/Watt output. LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C).
Supplying, installation, Testing & Commissioning of Street light LED fixture powder coated pressure die cast aluminium body with driver as per the requirement with Driver efficiency >85%, Input voltage: 140-270 Volt AC, frequency 50/60 hz, Operating temp range -5 0C to 50 0C, internal surge protection of 5 KV L,N,E as per IEC 61000-4-5, Driver efficiency >85%,THD < 10% as per IEC 61000-3-2, P. F.≥0.95, IP-66,IK-10, CRI >70, under voltage and over voltage protection, EMIEMC As per CISPR 15 , lenses for beam angle as per IESNA type I/II/III as per the width of the road and the project requirement., suitable to fit in up to 65mm dia pipe, life time (LED, Driver & electrical circuitry) of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends as per LM80 extrapolation IES TM-21-11 report, CCT 3000°K / 4000°K / 5700°K /6500°K (As per ANSI Bin), SDCM(Standard Deviation Colour Matching) <5, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard complete in all respect i/c external connections with 1.5 sq mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥120 <135 lm/Watt output. LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C).
Supplying, Installation, Testing & Commissioning of Panel light 2x2 ft., of following body material and construction as per IS : 10322 with driver as per the requirement with Driver efficiency >85%, Operating voltage AC 140-270 Volt, frequency 50/60 hz, Operating temp range -5 0C to 40 0C, internal surge protection of 2.5 KV with Short & Open circuit protection ,THD < 10% , P. F.≥0.95, IP20, CRI >80, UGR (Unified Glare Rating) <19, Flicker free, (flicker should be below 5 %), life time (LED, Driver & electrical circuitry), of minimum 50000 Burning Hours with , 70% of initial Lumen maintained till life ends, CCT 3000°K / 4000°K / 5700°K /6500°K (As per ANSI Bin), SDCM(Standard Deviation Color Matching) <3, Maximum power consumption should not more than the specified rating and Fixture shall be of elevant BIS standard. Manufactures Word Mark/ Name Engraved/Embossing/ Screen printing on housing. complete in all respect i/c external connections with 1.5 sq mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 years OEM warranty. System lumen efficacy ≥120 <135 lm/Watt output. LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C). Powder coated die cast /Extruded aluminium Body (Thickness > 1.20 mm)
Supplying, installation, Testing & Commissioning of LED Recessed/ surface Down lighter (Round/ square/ Rectangular) SMD type of following body material with PMMA and prismatic diffuser and construction as per IS : 10322 with driver as per the requirement with Driver efficiency >85%, Operating voltage AC 140-270 Volt, frequency 50/60 hz, Operating temp range -5 0C to 40 0C centigrade, internal surge protection of 2.5 KV with Short & Open circuit protection ,THD < 10%, P. F.≥0.95, IP20, CRI >80, UGR (Unified Glare Rating) <19, Flicker free (flicker should be below 5 %), life time (LED, Driver & electrical circuitry), life time of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends, CCT 3000°K / 4000°K / 5700°K /6500°K (As per ANSI Bin), SDCM(Standard Deviation Color Matching) <3, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard. Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing Complete in all respect i/c external connections with 1.5 sq mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 years OEM warranty. System lumen efficacy ≥120 <135 lm/Watt output. LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in- Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C). Powder coated die cast /Extruded aluminium Body including trim.
Supplying, installation, Testing & Commissioning of LED surface mounted Batten light of following body material and construction as per IS : 10322 with driver (Replaceable) as per the requirement with Driver efficiency >85%, Operating voltage AC 140- 270 Volt, frequency 50/60 hz, Operating temp range -5 0C to 40 0C, internal surge protection of 2.5 KV with Short & Open circuit protection ,THD < 10% , P. F.≥0.95, IP20, CRI >80, Flicker free (flicker should be below 5 %), life time (LED,Driver & electrical circuitry), of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends, CCT 3000°K / 4000°K / 5700°K /6500°K (As per ANSI Bin), SDCM(Standard Deviation Colour Matching) <3, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard. Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing. complete in all respect i/c external connections with 1.5 sq.mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥120 <135 lm/Watt output. LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C). Powder coated die cast /Extruded aluminium Body (Thickness > 1.20 mm)
Supplying, Installation, Testing and Commissioning of 300 mm Sweep 900 RPM Heavy Duty ISI Marked Exhaust fan with louvers & shutters in the existing opening, including making good the same, connection, testing, commissioning etc. as reqd.
Supply, Installation, Testing and Commissioning of ceiling fan with Brush Less Direct Current (BLDC) Motor, class of insulation: B, 3 nos. metal (Aluminium alloy) blades, 30 cm long down rod, 2 nos. canopies, shackle kit, safety rope, copper winding, steel/Al body. Power Factor not less than 0.9, Service Value (CM/M/W) minimum as below, 350 RPM (tolerance as per IS : 374-2019), THD (Total Harmonic Distortion) less than 10%, remote (preferably mobile app based) for speed control and all remaining accessories including safety pin, nut bolts, washers, temperature rise=75 0C (max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase AC supply Ceiling Fan compliant to IS 374:2019 fan i/c external connections with 1.5 sq.mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required.
1200mm, service value ≥ 6.0 CM/Min/Watt, air delivery 210 CM/Min (Minimum)
Providing & fixing following switchgears and accessroies in the existing cubical panel board i/c drilling holes and making connections, testing etc. as reqd.
100 A, TP MCCB 16 KA
200 Amp, 25 KA, TPMCCB
Supplying , Installation, Testing and Commissioning of Air Cooled Hi Wall split type Air conditioners complete with Indoor unit(IDU), Out door unit (ODU), surface / concealed copper Refrigerant piping with insulation (closed cell elastomeric nitrile rubber tubular pipe section) upto 3 Mtr (IDU to ODU), copper power cable upto 3.5 Mtr (IDU to ODU) i/c drain pipe R-32/R-410/ R-407 Green Refrigerant, wireless Remote control, suitable for working between 180- 260V with low & high voltage cutoff and 50 hz ,1 phase AC supply capable of performing cooling, dehumidification, air circulation of following capacity with Scroll / rotary compressor. The system shall be able to deliver 100% of the rated capacity upto 42 0C. Min 5 year Original Equipment Manufacturer (OEM) warranty both compressor and Printed Circuit Board (PCB). Must comply : Electrical cable IS 694 or IS 9968 temperature sensing control IS /International Electrotechnical Commission (IEC) 60730, hermetic compressor IS 10617, heat exchanger IS 11329, capacitor IS 2993 and motor IS 12615. Complete as per CPWD specification and IS : 1391 Part II 2023. The system shall be able to operate up to 50 0C (out door ambient temperature). Inverter Type - Cooling only.
1.5 TR with 5 Star BEE Rating
Providing & Laying of refrigerant copper piping of size 1/4" or 3/8" & 5/8" diameter from indoor unit to outdoor unit of split type Air Conditioner unit along with 4 core 2.5 sq.mm PVC insulated and PVC sheathed flexible copper conductor cable including 20 mm size of cotton thread ribbed PVC flexible pipe from drip tray of Air Conditioner unit to drain pipe along with necessary support complete etc all as per Direction of Engineer-in-charge .
Supplying & fixing suitable size GI box with modular plate and cover in front on surface or in recess including providing and fixing 25 A modular socket outlet and 25 A modular SP MCB, "C" curve including connections, painting etc. as required.
Supply, installation, testing and commissioning of Reverse Osmosis System with capacity of 250 LPH designed for Treatment of saline water in the TDS range of 500-2000ppm which are Completely assembled /Pre-piped/Pre-wired with Microprocessor-based control Pannel for ease of operation and inbuilt process Logic having provision for Auto start/stop based on Water level in the Tank with MCB for Plant operation and Raw water pump integrated with Plant. Integrated pretreatment Module for removal of suspended solids along with pressure gauges, Robust high Pressure Pump in SS 304 Construction, Inbuilt Protection to high Pressure Pump by Way of Low Pressure Switch/high Pressure switch and Glycerine filled SS Pressure gauges for durability, On line Rota meter for measuring permeate flow and Powder coated MS skid with plated hardware. RO plant have Pressure Sand Filter of 1000 LPH, Activated carbon Filter of 1000 LPH, Antiscalant Dosing System with tank capacity of 50 Litre, Micron cartridge filter of 5 micron, 10" long, High pressure pump of 1000 LPH , 1.2 KW, RO membrane of 4"*40" - 1 Nos. of GE/Equivalent having backwash facility along with 1 Year Maintenance wrt Replacement of Micron Cartridge Filter and Antiscalant Chemical. The Company is having their NABL Accredited Lab Testing facilities in Delhi. Our Product Is ISO 9001 , Indian Medical Association Certified GC (Green Company) Mark BIS certificate,ISO 14001, ISO17025, ISO9001 etc. as required.
SITC of 50 LPH Capacity Fully Automatic with auto cut off Reverse Osmosis plant for water Purification System having suitable Nos. of membranes, sediment filter, ACF etc, suitable for operation on 230 Volts ± 10%, 50 Hz,. AC supply including water inlet & outlet connection etc. as required.
Supplying, installation, testing & commissioning of following capacity water storage vertical type geyser working on 230 +/- 10 V single phase 50 Hz Frequency, tank with altra thick super cold rolled steel plates, puff insolation, rated pressure: 8 bar, Temperature range 75 degree C, heating indicator, temperature setting: manual, power consumption: min 2 kw i/c Thermostate, Thermal cut off, multifactional sefety valve complete with necessary accessories & flexible heavy duty pvc connection of sutiable length (2 Nos.) and 25 amp plug top etc, as reqd.
50 ltrs. Rating Minimum 4 star
Supplying, Installation, Testing & Commissioning of self contained storage type water cooler suitable for operation on 230 V single phase A.C. supply having following capacity per hour cooling capacity & storage capacity with SS304 stainless steel body, air circulation R-32/R-410 /R-407/ R134a Green Refrigerant with Scroll / rotary compressor with min 5 year OEM warranty of compressor, water over flow 1/2 BSP (connections) i/c MS Angle Iron Stand of suitable size, complete and other accessories i/c connection testing etc as reqd.
storage 150 ltr, cooling capacity 150 ltr per hr
SITC of following capacity openwell Mono Submersible Pump Set horizontal type suitable for 3 phase, 415 V AC supply having a discharge capacity mentioned with them of with C.I. Impeller i/c dismentling of old pump and repairing of broken sump edges and remove the existing sump cover and providing and fixing GI Main hole cover of size not less than 1200 X 1200 mm made from 4mm sheet complete with all required accessories i/c credit for old defective pump set and sump cover etc. complete as reqd.
10 HP ( 32 LPS at Head of 12 Mtr )
Rewinding, repair and servicing of following monoblock/ mono submersible pump set/ submersible pump set suitable for run 3 phase, 440volt, 50 Hz AC supply i/c dismental from existing location and carriage (to and fro) to the workshop and testing, commissioning with credit of scrap copper wire and other parts etc. as required.
Lifting of existing submersible open well 5 to 10 HP cap. Pump set from the open well with chain pulley block & tripod stand i/c cartage charge at site from the work shop etc, as reqd.
Lowering of 5 to 10 HP open well pumpset in the bore well with chain pulley block and tripod stand i/c cartage charge pump set from work shop to site etc, as reqd.
Supplying of Recessed type Trimless LED Fulllit Linear of size 1ft x 4ft alongwith frame suitable for POP/Gypsum Ceiling having PS diffuser for UGR <19, color temperature 5700K-6500K system efficacy ≥ 110lm/W (not LED Chip efficacy), CRI≥80, Mimimum System Ouput ≥ 3960 Lumens, useful life of 50,000 hrs at L70B10. & driver having PF ≥ 0.95 & THD<10% and Surge Protection of 3 KV & External SPD -6KV in the existing false ceiling with the help of 1x4 Frame & steel chain approx 1mtr x 2 nos i/c supplying & fixing MS flexible conduit from light point to fittings and connections with 3x1.5sqmm copper wire etc complete as required. BIS Certificate issued to the approved make along with LM79 report with ULR Code from NABL lab must be shared at the time of supply. LT FULLLIT LINEAR PR 36W. And Recess 1x4 Frame -ALS0001-1X4 Frame for Gypsum or POP ceiling.
Supplying and laying one number PVC insulated and PVC sheathed / XLPE aluminium power cable of 1.1 kV grade of following size on existing DWC Pipe/on wall surface etc as required. i) 3 x 10 sqmm
Credit for old dismantle items
MCCB DB
100 Amp MCCB
200 Amp MCCB
Assorted switch &Socket
Assorted size LED Fixtures
Assorted size RO
Assorted size Water Cooler
Assorted size Geyser
Assorted size Split/Window AC
Assorted size copper wire
Please Enable Macros to View BoQ information
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 2.42 MB
112RepairingRewiringSpecialHomeBoysDWCDMajnuKaTila.pdf
Tender Documents • 2.40 MB
BOQ_378596.xls
BOQ • 0.48 MB
Download all tender documents and submit your bid