Loading…
Loading…
| # | Company | Status |
|---|---|---|
| 1 | Admitted-Finance | Admitted-Finance |
| 2 | Admitted-Finance 201 PLOT NO 32 SHALAKA BLDG TPS II JUHU ROAD SANTACRUZ WEST MUMBAI SUBURBAN MAHARASHTRA 400054 | MUMBAI SUBURBAN | MAHARASHTRA | 400054 | Admitted-Finance |
| 3 | Admitted-Finance | Admitted-Finance |
| 4 | Admitted-Finance | Admitted-Finance |
| 5 | Admitted-Finance | Admitted-Finance |
Tender Value
₹16.6 L
EMD Value
₹33,300
Closing Date
28 Dec 2019, 6:00 pmClosed
AGM Electrical
Office of AGM Electrical, AAI, Vijayawada Airport
Modification and Extension of International Arrival Block at Vijayawada Airport SH Electrical works
2019_AAI_38307_1
AAI/BZ/ENGGE/AGM/NIT12/2019
Open Tender
Electrical Works
Item Rate
90 days
Airports Authority of India, Vijayawada Airport
As per NIT criteria
8 documents required · 8 mandatory
₹1,180
Airports Authority of India
₹33,300
3 Jan 2020
17 Dec 2019
1 Jan 2020
18 Dec 2019
28 Dec 2019
18 Dec 2019
18 Dec 2019 - 27 Dec 2019
Amount
Supply of following sizes of 1.1 KV grade, XLPE insulated, PVC sheathed,armoured, aluminium conductor power cable confirms to IS 7098(part -1) with up to date amendments etc complete as required (a) 3.5 x 185 sq.mm.
Supply of following sizes of 1.1 KV grade, XLPE insulated, PVC sheathed,armoured, aluminium conductor power cable confirms to IS 7098(part -1) with up to date amendments etc complete as required (a) 4 x 35 sq.mm.
Supply of following sizes of 1.1 KV grade, XLPE insulated, PVC sheathed,armoured, aluminium conductor power cable confirms to IS 7098(part -1) with up to date amendments etc complete as required (a) 4 x 25 sq.mm.
Supplying and laying of 90 mm outer dia and 76 mm inner dia PN-6, PE-63, HDPE pipe ISI marked along with all accessories like socket, bend, couplers etc. conforming to IS 4984:2016, complete with fitting and cutting, jointing etc..direct in ground (75 cm below ground level) including excavation and refilling the trench but excluding sand cushioning and protective covering etc., complete as required.
Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing masonry open duct as required. Above 95 sq. mm and upto 185 sq. mm
Laying of one number PVC/XLPE insulated and PVC sheathed power cable of 1.1 KV grade of size above 95 sq.mm and upto 185 sq.mm in the existing RCC/Hume/STONEWARE/METAL pipe as required.
Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on wall surface as required. Upto 35 sq. mm (clamped with 1mm thick saddle)
Excavation of the cable trenches in hard rock not exceeding 1.5 metres in width, and lift upto 1.5 metres, including getting out the excavated soil and disposal of excavated soil as directed within a lead of 50 metres.
Supplying and making indoor end termination with brass compression gland and alluminium lugs for following sizes of PVC insulated, PVC sheathed/XLPE aluminium conductor cable of 1.1 KV grade etc as required. (a) 3.5 x 185 sq.mm (57 mm).
Supplying and making indoor end termination with brass compression gland and alluminium lugs for following sizes of PVC insulated, PVC sheathed/XLPE aluminium conductor cable of 1.1 KV grade etc as required. (a) 4 x 35 sq.mm (32 mm).
Supplying and making indoor end termination with brass compression gland and alluminium lugs for following sizes of PVC insulated, PVC sheathed/XLPE aluminium conductor cable of 1.1 KV grade etc as required. (a) 4 x 25 sq.mm (28 mm).
Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing along with existing surface/ recessed conduit/ submain wiring/ cable as required.
Supply, Installation, Testing & Commissioning of maintenance free chemical Earthing with Copper bonded Earth Electrode of 3/4" dia, 3 Meter Long, treatment using Ground enhanced material of 50kg, submission of CPRI type Test report of earth electrode, excavation of suitable pit and treating the earthing pit using ground enhance material, civil inspection chamber withy cement plastered of size 300X300X300mm, concrete lid (to cover the earth pit) painted black with min. 50mm. thick having pulling hooks etc., complete as required.
Providing and fixing 25 mm X 5 mm G.I. strip in 40 mm dia G.I. pipe from earth electrode including connection with G.I. nut, bolt, spring, washer excavation and re-filling etc. as required.
Supply of 36-40 W Recess mounting 2' x 2' LED flat panel fitting made of CRCA sheet steel duly power coated with high efficient LEDs & glare free full opal diffuser, IP20 protection, suitable to operate on 230V, 50 Hz, AC Supply, with mounting accessories etc complete as required.
Supply of 24 W Recess mounting 1' x 1' LED flat panel fitting made of CRCA sheet steel duly power coated with high efficient LEDs & glare free full opal diffuser, IP20 protection, suitable to operate on 230V, 50 Hz, AC Supply, with mounting accessories etc complete as required.
Supply of 400 mm sweep Wall mounted fans suitable to operate on 230 volts,50 Hz AC supply etc.as required
Installation, testing and commissioning of pre-wired, fluorescent fitting / compact fluorescent fitting of all types, complete with all accessories and tube/lamp etc. directly on ceiling/ wall, including connections with 1.5 sq. mm FRLS PVC insulated, copper conductor, single core cable and earthing etc. as required.
Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required. GROUP-B
Wiring for group controlled (looped) light point/fan point/exhaust fan point/ call bell point (without independent switch etc.) with 1.5 sq. mm FRLS PVC insulated copper conductor single core cable in surface/ recessed PVC conduit, and earthing the point with 1.5 sq. mm FRLS PVC insulated copper conductor single core cable etc. as required.
Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required. 2 X 4 sq. mm + 1 X 4 sq. mm earth wire
Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required. 2 X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire
Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required. 2 X 1.5 sq. mm + 1 X 1.5 sq. mm earth wire
Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) 8 way (4 + 24), Double door
Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator). 6 way , Double door
Supply and fixing of 5 A to 32 A, rating 240 V/415 V "C" curve miniature circuit breaker suitable for inductive load of following pols in the exsting MCB DB complete with connection, testing and commissioning etc. as requred. A) Single Pole
Supply and Fixing of folowing rating 4 pole (3 phase & Netural) 415 V RCCB having a sensitivity current up to 30 Milli Ampres, 10 KA in the existing MCB DB, complete with Connection, testing and commissioning etc. as requred. A) 63 Amp
Supply and Fixing of folowing rating 2 pole ( phase & Netural) 240 V RCCB having a sensitivity current up to 30 Milli Ampres, 10 KA in the existing MCB DB, complete with Connection, testing and commissioning etc. as requred. A) 40 Amp
Supply and Fixing of folowing rating 2 pole ( phase & Netural) 240 V RCCB having a sensitivity current up to 100 Milli Ampres, 10 KA in the existing MCB DB, complete with Connection, testing and commissioning etc. as requred. A) 40 Amp
Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 & 15/16 amps modular socket outlet and 15/16 amps modular switch, connection etc. as required
Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 3 pin 5/6 amps modular socket outlet and 5/6 amps modular switch, connection etc. as required. (For light plugs to be used in non residential buildings).
Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required. (a) 32 mm
Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required. (a) 25 mm
Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required. (a) 20 mm
DEEPAKELECTRICALS
POWER TECH ENGINEERING SERVICES
S S TECHNOS
Shantha ELectricals and Engineers Pvt Ltd
DElite System Engineering (India) Pvt. Ltd.
stage.html
html • 0.03 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .