| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹14.5 LAccepted-AOC | ₹14.5 L Quoted ₹14.9 L | L1 | Accepted-AOC Lowest bidder |
| 2 | L2₹17.9 L+₹2.9 L (19.7%)Rejected-Finance D NO 38 22 40 NEAR LAKSHMI NARASHIMA THEATER 104 AREA VISAKHAPATNAM 530007 | VISAKHAPATANAM | ANDHRA PRADESH | 530007 | ₹17.9 L+₹2.9 L (19.7%) | L2 | Rejected-Finance Other than Lowest Bidder |
| Sl No | Description | Qty | Unit | AYYAPPA CONSTRUCTIONS L2 | PAVANI INFRAS L1 |
|---|---|---|---|---|---|
| 1.00 | M&L for Servicing/ Health Check for 11 KV SF6/ Vacuum Circuit Breaker, Ring Main Unit, Load Break Switches etc. as Physical Operation check with Interlocks, Provide Lubrication as require, Check Tightness of contacts and etc. problem rectification including replacement of minor parts and wiring as required complete all as specified and directed.
Note:- The make of existing HT RMU panel is ABB (Minimum - 2 To Maximum - 4 Feeders per Panel) | 8 | Job | 12,000 ₹96,000 | 10,000 ₹80,000 Lowest |
| 2.00 | M&L for overhauling, checking of wiring system, replacement of minor defective spare parts, setting of tripping plugs according to the load, carrying out Complete checking like Insulation Resistance Test, Calibration with Secondary Current Injection Test, Setting, Relay and Control Circuit Test, CT Ratio check, for 3 Phase, 11 kV, 50 Hz, VCB based Panel for each way /circuit, tripping of system as per setting, complete all as specified and as directed.
Note:- The make of Numeric Relay is C&S, Ashida. | 2 | Job | 8,500 ₹17,000 | 7,000 ₹14,000 Lowest |
| 3.00 | M&L for Replacement of 90 degree lug boot for HT terminals on each phase for protection of the HT terminals from moisture/dust etc complete all as specified and as directed. | 4 | Set of 3 | 3,000 ₹12,000 | 2,000 ₹8,000 Lowest |
| 4.00 | M&L for replacement of Self powered numeric relay for accurate tripping system and closing any opening of panel with necessary sheet and fixing, setting the relay for desired values and checking on completion complete all as specified and directed. | 2 | Each | 17,000 ₹34,000 | 15,000 ₹30,000 Lowest |
| 5.00 | M&L for replacement of tripping coil in existing 11 kV, HT VCB based RMU Panel with new tripping coil of same specifications and checking complete all as specified and as directed. | 2 | Each | 2,500 ₹5,000 | 2,000 ₹4,000 Lowest |
| 6.00 | M&L in replacement of induction type CT over HT Cable of rating 40/1 Amps, Class 1, SP10, with burden 15kA as per existing model in ABB HT RMU Panel complete all as specified and as directed. | 2 | Each | 9,500 ₹19,000 | 8,000 ₹16,000 Lowest |
| 7.00 | M&L for Dehydration/ Filtration of transformer of capacity 75 kVA to 250 kVA installed at site with portable plant to improve the dielectric strength 50 to 60 kV during filling of oil, after initial filtration, including testing of dielectric strength after dehydration at site.
Note:-
(i)The contractor shall produce the transformer oil test results before and after filtration for each transformer. Test Report to be produced before payment.
(ii) The quoted rate shall be inclusive of arranging supply to portable plant. | 1,850 | Litre | 90 ₹1,66,500 Lowest | 90 ₹1,66,500 Lowest |
| 8.00 | Supply & filling of transformer oil in transformer in situ/ at site for topping up the level of oil having dielectric strength 40-60 kV during filling conforming to IS-335 complete all as specified and directed.
Note: transformer oil shall be supplied in sealed container. | 150 | Litre | 300 ₹45,000 | 200 ₹30,000 Lowest |
| 9.00 | M&L for shifting of transformer from MES substation to Workshop (located at Vijayawada) exc 90 km and n.exc 120 km by hiring separate vehicle for repairs and shifting of transformer back to MES Substation, along with hiring of crane for loading and unloading of transformer, complete all as specified and as directed. | 2 | Job | 11,000 ₹22,000 | 10,000 ₹20,000 Lowest |
| 10.00 | M&L in replacement of burnt HT and LT winding coils in one phase with copper coils of same gauge as existing, along with complete insulation over HT and LT coils as per standard specifications and refixing the same in transformer complete all as specified and as directed. | 220 | Kg | 2,500 ₹5,50,000 | 2,000 ₹4,40,000 Lowest |
Tender Value
₹15 L
EMD Value
₹30,000
Closing Date
18 Jul 2026, 6:00 pmClosed
CWE AF Trivandrum
HQ CWE AF TRIVANDRUM HQ SAC IAF Complex Akkulam Thruvikkal Post Trivandrum 11
REPAIR/REPLACEMENT OF HT PANELS, CABLES, JOINT KITS ALONG WITH TRANSFORMER OIL FILTRATION AT AF STN SURYALANKA
2026_MES_772245_1
82671/E8
Open Tender
Electrical and Maintenance Works
Item Rate
270 days
AGE I AF Suryalanka
Please refer Tender documents.
7 documents required · 7 mandatory
₹500
AGE I AF Suryalanka
₹30,000
Yes
28 Jul 2026
15 Jun 2026
20 Jul 2026
15 Jun 2026
18 Jul 2026
29 Jun 2026
15 Jun 2026 - 25 Jun 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | M&L for Servicing/ Health Check for 11 KV SF6/ Vacuum Circuit Breaker, Ring Main Unit, Load Break Switches etc. as Physical Operation check with Interlocks, Provide Lubrication as require, Check Tightness of contacts and etc. problem rectification including replacement of minor parts and wiring as required complete all as specified and directed.
Note:- The make of existing HT RMU panel is ABB (Minimum - 2 To Maximum - 4 Feeders per Panel) | 8 | Job | - | - |
| 2 | M&L for overhauling, checking of wiring system, replacement of minor defective spare parts, setting of tripping plugs according to the load, carrying out Complete checking like Insulation Resistance Test, Calibration with Secondary Current Injection Test, Setting, Relay and Control Circuit Test, CT Ratio check, for 3 Phase, 11 kV, 50 Hz, VCB based Panel for each way /circuit, tripping of system as per setting, complete all as specified and as directed.
Note:- The make of Numeric Relay is C&S, Ashida. | 2 | Job | - | - |
| 3 | M&L for Replacement of 90 degree lug boot for HT terminals on each phase for protection of the HT terminals from moisture/dust etc complete all as specified and as directed. | 4 | Set of 3 | - | - |
| 4 | M&L for replacement of Self powered numeric relay for accurate tripping system and closing any opening of panel with necessary sheet and fixing, setting the relay for desired values and checking on completion complete all as specified and directed. | 2 | Each | - | - |
| 5 | M&L for replacement of tripping coil in existing 11 kV, HT VCB based RMU Panel with new tripping coil of same specifications and checking complete all as specified and as directed. | 2 | Each | - | - |
| 6 | M&L in replacement of induction type CT over HT Cable of rating 40/1 Amps, Class 1, SP10, with burden 15kA as per existing model in ABB HT RMU Panel complete all as specified and as directed. | 2 | Each | - | - |
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.93 MB
Tenderdocmerged.pdf
Tender Documents • 1.80 MB
BOQ_864726.xls
BOQ • 1.33 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .