| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹7.8 LAccepted-AOC GEETA COTTAGE NO 03 HOUSE NO 11 OPP CIVIL AIR PORT BHUJ KUTCH 370001 GUJARAT | KACHCHH | GUJARAT | 370001 | L1 | Accepted-AOC being lowest and reasonable | |
| 2 | L2₹8.0 L+₹190.40 (0.02%)Rejected-Finance HAVELI FALIYA NALIYA KUTCH 370 655 | KACHCHH | GUJARAT | 370655 | L2 | Rejected-Finance not L1 | |
| 3 | L3₹10.3 L+₹2.3 L (29.1%)Rejected-Finance | L3 | Rejected-Finance not L1 |
Tender Value
₹9.5 L
EMD Value
₹19,000
Closing Date
14 Feb 2024, 6:00 pmClosed
AGE (I) (CG) Jakhau
CGRA Naliya, Kutch, Gujarat-370655
REPAIRS / MAINT OF HT / LT ELECTRIC PANEL WITH MISC ALLIED WORKS, EXTERNAL WATER SUPPLY, PUMP, MOTORS, RO PLANT AND STP WITH CONNECTED ITEMS AT CGRA AND ICGS STATIONS UNDER AGE (I) (CG) JAKHAU
2024_MES_637840_1
8125/E8
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
Naliya
Please refer Tender documents.
6 documents required · 6 mandatory
₹500
AGE (I) (CG) Jakhau
₹19,000
Yes
4 Mar 2024
17 Jan 2024
15 Feb 2024
17 Jan 2024
14 Feb 2024
31 Jan 2024
Amount
Maintenance / servicing of VCB / RMU 11 KV, 400/ 630 /1200 Amps including removal of VCB trolley, cleaning of all copper male and female contacts, tightening of all connections, checking of all auxiliary contacts, control wiring, servicing of relays, etc. refixing the VCB trolley to its original position including proper setting of manual/motorize operation of VCB, checking/setting of tripping system, etc complete. Note:- (i) Maintenance to be carried out by authorized technician of OEM. (ii) After completion test certificate shall be furnished. (iii) Calibration of relay by injecting High voltage through CTS checking the over load system of VCB upto 90 % rated load and artificial fault creation and setting of relay by 10 to 15 % of rated load removing u/s overload and earth fault relay including connection with power pack. (iv) Opening out the trolly checking the operation of VCB mechanically and electrically through shunt trip coil including energizing of springs automatically including checking of TNC switch
Taking down carefully Transformer of 160/250 KVA and above capacity, any make, any type from pole / plinth/ base, disconnecting HT & LT side connections, earthing strip of transformer, supporting angles, cross arm, shifting / transporting transformer carefully from the site to the workshop opening the top cover of the transformer, bushing, draining of oil from the transformer, lifting the core complete taking out defective coils from the core, cleaning the tank and reassembling the transformer after carrying out the repairs/replacement of worn out part, ovening the complete unit till to get desired megger value, transporting returning back to the site installing re-commissioning and testing of the transformer at its original place, connecting up HT & LT sides, earthings, supports / cross arms etc all as directed by EIC Note :- Spares, Rewinding of transformer,reinsulating & heating if required will be measured and paid separately under respective Sch'A' items
Supply & Fix in repair top cover gasket made up of 5 mm thick cork sheet.
Supply & Fix in repair HT bushing, porcelain vitreous brown body 1100 V grade as per IS 3347.
Supply & Fix in repair LT bushing, porcelain vitreous brown body 1100 V grade as per IS 3347.
Supply & Fix in repair HT brass studs along with washers for one terminal 11 KV transformer.
Supply & Fix in repair LT brass studs along with washers for one terminal 1100 Volts grade transformers.
Supply & Fix in repair breather assembly complete with silica GEL
Supply & Fix in repair temp level indicator including its bolts, nuts, gasket etc complete.
M & L for rewinding old / burnt out HT/LT coils by super enamelled copper winding wire / strips of appropriate size of super quality (as per existing material & size of transformer coils) including, insulating, varnishing, heating, keeping coils in position, etc for transformer up to 500 KVA.
M & L for re-insulation of heated / weak LV coils of transformer by super quality insulating materials, heating, varnishing , etc complete to improve IR value etc complete all as directed by Engr-in-Charge.
Supply, laying and testing, in replacement XLPE cable, Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 120 sqmm, 3.5 core , complete all as specified and as directed by Engr-in-charge.
Supply, laying and testing, in replacement XLPE cable, Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 50 sq mm 3.5 core , complete all as specified and as directed by Engr-in-charge.
Supply, laying and testing, in replacement XLPE cable, Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 16 sqmm, 4 core , complete all as specified and as directed by Engr-in-charge.
Supply, laying and testing, in replacement XLPE cable, Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 10 sqmm, 2 core , complete all as specified and as directed by Engr-in-charge.
Excavation in trenches in soft/loose soil not exceeding 1.5 mtr deep and not exceeding 1.5 mtr wide for laying of cables, pipes, RCC poles / stays and struts etc and getting out including trimming sides and forming levelled bottom surface all as specified and directed at site.
Returning, filling in, including spreading, watering and well ramming in layers not exceeding 25 cm thick each, in soft /loose soil complete all as specified.
Removing excavated material (soils) n exc. 50m and depositing where directed at a level n exc. 1.5 m above the starting point
Supplying & laying in repair factory made of unreinforced Precast concrete cover of class LV, type 1, flat, size 250 mm x 150 mm x40mm for protection for cable all as specified.
Dry sand filling in cable trenches for protection of cables with two layers below and above cable and punned down to speicified thickness complete all as specified and as directed. Note: Punned down thickness shall only be measured for payment.
Supplying and laying in replacement synthetic rubber insulated mats 2 mm thick for voltage upto 3.3 kV for electrical purpose as per IS 15652-2006, (superseding IS 5424) suitable for electrical shock safety of sizes 2m x 1m.
M&L for checking of transformer for any leakage and rectify the same by tightening of nut, bolt or replacing broken rubber gasket, drain plug etc. complete all as directed and directed by Engr-in-Charge.
Dehydration of transformer oil of transformers 11KV/433 Volt (03 Nos) of different capacities located at CGRA Naliya and ICGS Jakhau by dehydration machine and obtained dielectric strength should be more than 40 KV at 2.5mm gap complete all as specified & directed by Engineer-in-Charge.
M&L for topping up of transformer oil having die electric strength not less than 45 KV(at 2.5 mm gap) high voltage as per IS specification of low viscosity complete all as directed by Engineer-in-Charge Make:- Powerlink/Power-oil/Savita
M&L in replacement of silica gel of transformer breather complete all as directed by Engineer-in-Charge
M&L for repairs to existing out door LT panel, removing the unserviceable hinges from doors (1.6mm thick MS), grinding the welded portion, denting and levelling the door, welding suitable new hinges (Approx. 0.50 Kg) to doors including locking arrangement and one coat of synthetic enamel paint over a coat of rubber paint as that of existing colour complete all as specified and as directed.
Material and labour in repair for earthing complete with galvanized earth plate electrode in 60 cm x 60 cmx 6 mm thick buried directly in ground vertically at a depth not less than 2.25 meter below ground level with top edge of earth plate at depth not less than 1.5 mtr below ground level connecting to and including GI strip 32 mm x 6 mm by means of GI bolts, nuts, check nuts and washer light grade 40 mm dia GI protection pipe and connected to equipment, GI pipe medium grade 20 mm dia for watering an including funnel wire mesh, RCC pit cover and PCC 1;2:4 type B-1 including Rocksalt, charcoal, excavation and earth work disposal of surplus soil shown as plate No 3 of SSR Part - I 2009 and all as specified complete. Note : - The unit rate quoted shall deemed to have included for GI protection pipe, GI earth strip up to 7.5 mtr, GI water pipe, wire mesh , funnel , excavation, RCC pit cover complete.
M&L for lowering of High Mast lantern to carry out repairs for lights and cables, fittings,gear box servicing ,greasing of motor etc. and raising the lantern to its original position after replacement of items such as LED Flood light,LED driver etc. Note:- LED flood light, LED driver etc will be measured and paid seperately as supply only
Supply only LED driver suitable for flood light 180 watt to 250 watt , out door type of existing make and model as approved by accepting officer.
S&F in repairs power AC power contactor of rating 32 Amps AC3, 3 Pole complete all as specified and as directed. Make: L&T/ Siemens/ Schneider
M&L for Cutting of worn out aluminium cable terminal lugs from the HT/LT cable of any size, crimping of new aluminium cable Lugs and fixing with transformer / LT panel terminal studs including cutting/dressing of cable, excavation, redressing of excavated surface, providing sand cushioning and brick protection as directed.
M&L for cable jointing kit for 1.1 KV grade cable, straight through cold shrink type joint complete with jointing material and accessories suitable for 3.5 core XLPE armoured aluminium conductor cable of size 150 to 185 Sqmm complete all as specified and directed by Engineer-in-charge.
M&L for cable jointing kit for 1.1 KV grade cable, straight through cold shrink type joint complete with jointing material and accessories suitable for 3.5 core XLPE armoured aluminium conductor cable of size 70 to 120 Sqmm complete all as specified and directed by Engineer-in-charge.
M&L for cable jointing kit for 1.1 KV grade cable, straight through cold shrink type joint complete with jointing material and accessories suitable for 3.5 core XLPE armoured aluminium conductor cable of size 25 to 50 Sqmm complete all as specified and directed by Engineer-in-charge.
M&L for cable jointing kit for 1.1 KV grade cable, straight through cold shrink type joint complete with jointing material and accessories suitable for 3.5 core XLPE armoured aluminium conductor cable of size 10 to 25 Sqmm complete all as specified and directed by Engineer-in-charge.
S&F in repair MCCB, 200 Amps, four pole, 36 KA, 415 volt adjustable type complete all as specified and directed by Engineer-in-charge.
S&F in repair MCCB, 160 Amps, four pole, 25 KA, 415 volt adjustable type complete all as specified and directed by Engineer-in-charge.
S&F in repair MCCB, 100 Amps, four pole, 16 KA, 415 volt adjustable type complete all as specified and directed by Engineer-in-charge.
S&F in repair MCCB, 63 Amps, four pole, 16 KA, 415 volt adjustable type complete all as specified and directed by Engineer-in-charge.
S&F in repair MCCB, 40 Amps, four pole, 16 KA, 415 volt adjustable type complete all as specified and directed by Engineer-in-charge.
Supply and fixing in replacement street light fitting in new generation energy saving environmental friendly long life LED street light with single die ceramic base high power LED light source,PDC housing with top openable access to driver for ease maintenance , lumen output 3500-7000 , system effiency 100 lm/watt , color temp 5700 K , made up of LM6 high pressure die cast aluminium housing with toughned glass ,IP66 protection , PF 0.95 , operating voltage 140-270 Volt AC and impact of capacity 70 Watt (minimum) complete all as specified and directed by Engineer-in-charge. Make:- Philips /Havells / Wipro/ Bajaj / Halonix
M&L for taking down street light fitting from steel/PCC pole, supply & fixing of new LED driver of exisiting make and model of rating 50 to 75 Watt by taking out unserviceable LED driver and refixing the street light at its original position complete all as specified and as directed. Make: Bajaj/Crompton Greaves /C&S. Note: Work shall be done after switching off power supply from main LT panel.
Supply & Fix in replacement LED new generation, IP 65 LED post-top lantern 15 watt, energy saving, environmental friendly, long life aesthetically designed with symmetrical light distribution, spun aluminium landscape luminaire with high power LEDs as light source. Opal Cover for soothing uniform illumination complete all as specified and directed. Make - Havells, Model:CORALMINIPT15WLED757PSYMTOPC or equivalent in Bajaj/Halonix
Supply & Fix in replacement LED new generation, IP 65 LED post-top lantern 15 watt, energy saving, environmental friendly, long life aesthetically designed with symmetrical light distribution, spun aluminium landscape luminaire with high power LEDs as light source. Opal Cover for soothing uniform illumination complete all as specified and directed. Make - Havells, Model: RUBYMINIPT15WLED757PSYMTOPC or equivalent in Bajaj/Halonix
M&L for GI post for garden light made of GI pipe light grade 40 mm dia 1.5 mtr long 30cm in foundation and 1.2 mtr above ground duly painted with two coats of synthetic enamel paint over a coat of red oxide primer , PCC foundation 30x20x20cm incl dismantling old foundation and taking out old rusted GI post complete all as specified and directed.
S&F astronomical digital timer switch 16 amp, LCD display, astronomical programable by entering longitude and latitude, also adjustable up to plus/minus 2hrs turning on later and off earlier than sunset and sunrise, with battery backup, suitable for connection with three phase supply incl taking down old unserviceable timer switch of any type complete all as specified and as directed. Make: L&T/ Siemens/ Schneider/ Havells
S&F in replacement FRP based outdoor type Junction box pole Hinged (L) mounted with clamps and including MCB SP, 6 Amps complete all as specified and as directed.
M&L for preparation of old surfaces of steel swan neck tubular poles and making strip white and blue colour up to 1.5 mtr height from top of PCC foundation block with synthetic enamel paint and painting the complete pole with one coat of aluminium paint above 1.5 mtr height including numbering of poles with synthetic enamel paint black colour in 80 mm high letters complete all as specified and directed by Engineer-in-Charge.
M&L for preparation of old surface of PCC poles and applying two coats of synthetic enamel paint over a coat of red oxide primer with black & white or yellow colour strips 30cm each up to 1.5 mtr height from top of PCC foundation block and numbering of poles with synthetic enamel paint white in 80 mm high letters above 150 mm the top strip complete all as specified and directed by Engr in charge.
M&L for painting of GI pipe bracket and clamp any size on pole security lights applying two coats of synthetic enamel paint over a coat of red oxide primer including preparation of surfaces complete all as specified and as directed.
S&F in repairs TFC spiral wound polyamide 4040 membrane of 4 inch dia 40 inch long suitable for RO 500 LPH capacity complete all as specified and directed
S&F in repairs spun micron cartridge filter of rating 5 micron, length 20 inch long Jumbo " for RO plant 500 LPH capacity and 2.5 inch dia complete all as specified and directed
Supply only RO antiscalant chemical for RO 500 LPH capacity complete all as specified and directed
Supply and Fix in trenches/passing under roads 50 mm galvanised steel water tubing, medium grade, including necessary fittings such as GI bends,Tees, Union etc complete and connecting to water supply pipe line and connections including removing / taking down the old pipe line complete all as specified and as directed.
Supply and laying in trenches/passing under roads Unplasticised PVC pipes 50 mm bore of pressure rating 10 Kgf/sq cm water tubing, including necessary fittings such as bends, Tees, Union etc. complete and connecting to water supply pipe line and connections including removing / taking down the old pipe line complete all as specified and as directed
Supply and laying in trenches/passing under roads Unplasticised PVC pipes 40 mm bore of pressure rating 10 Kgf/sq cm water tubing, including necessary fittings such as bends, Tees, Union etc. complete and connecting to water supply pipe line and connections including removing / taking down the old pipe line complete all as specified and as directed
Supply and fixing on wall Unplasticised PVC pipes 25mm bore of pressure rating 10 Kgf/sq cm water tubing, including necessary fittings such as bends,Tees, Union etc complete and connecting to water supply pipe line and connections including removing / taking down the old pipe line complete all as specified and as directed
S&F in repair Upvc ball valve for UPVC pipe 50 mm bore and fixed after taking out old unserviceable one
S&F in repair Upvc ball valve for UPVC pipe 25 mm bore and fixed after taking out old unserviceable one
M & L for Cleaning of PVC water tank of capacity 5000 litres using bleaching powder, scrubbing of inner surface of tanks by means of wire brush for removing all scale formed and other foreign particles and washing completely all as directed including cleaning of inlet & outlet pipe easing of ball valves and refixing of lid etc, writing the cleaning date on tank with synthetic enamel paint etc complete all as directed
M&L for servicing the monoblock pump set, single phase, 1 HP by in and including replacing new bearings, greasing, MS steel/bolt of pump in all respect for smooth functioning etc all as directed.
M&L for Dismantling and taking out submersible pump set for any capacity from UG Sump or STP tank for repair or for finding of any type of fault, such as cable fault / leakage of pipe etc. and refixing in original position after repairing and lowering in the UG Sump, with replacement of damaged gasket and nut bolts etc including testing of submersible pump set etc complete all as directed. Note:- Rewinding shall be measured and paid under separate item.
M&L for Opening of 7.5 HP motor and pump and reassembling the complete pump after replacement existing burnt out winding wire with super enamelled copper conductor insulating winding wire, gauge and the turns of wire is as per the manufacture's specification of existing pump including transportation to work shop and back reinstalling, testing etc.
M&L for Opening of 6 HP submersible motor and pump and reassembling the complete pump after replacement existing burnt out winding wire with super enamelled copper conductor insulating winding wire, gauge and the turns of wire is as per the manufacture's specification of existing pump including transportation to work shop and back reinstalling, testing etc.
S&F in replacement of bearings of motor
S&F in replacement of bush of motor
S&F in replacement of bush of pumps
M&L for Rectification of leakage in DI/UPVC/GI water mains 50 mm to 100 mm bore including excavation in any type of soil (approx. 2 meter length,1.5 meter width, 1.5 meter depth) dewatering complete by using pump set for rectification of leakage , by replacing of any type of joint such as run lead joint / CT joint / quick fix clamp of any size including cutting, welding, drilling etc. (Note: cost of CT joint / lead joint/clamps is deemed to be included in the rates quoted by the tenderer.)
M&L for Rectification of leakage in DI/UPVC/GI water mains 20 mm to 40 mm bore including excavation in any type of soil (approx. 2 meter length,1.5 meter width, 1.5 meter depth) dewatering complete by using pump set for rectification of leakage , by replacing of any type of joint such as run lead joint / CT joint / quick fix clamp of any size including cutting, welding, drilling etc. (Note: cost of CT joint / lead joint/clamps is deemed to be included in the rates quoted by the tenderer.)
M&L for servicing of self starter assembly of DG sets 24/12 volts of 125 /100 KVA Gen set locate at ICGS Jakhau by disconnecting the self starter assembly from the engine and dismantling, cleaning all accessories, replacing worn-out parts like carbon brushes, bushes, contact plates, jumping levels etc and rewinding the u/s field coil and varnishing all as directed by Engr-in-charge.
M&L for servicing of self starter assembly of DG sets 24/12 volts of 82.5/62.5 KVA Gen set locate at CGRA Naliya by disconnecting the self starter assembly from the engine and dismantling, cleaning all accessories, replacing worn-out parts like carbon brushes, bushes, contact plates, jumping levels etc and rewinding the u/s field coil and varnishing all as directed by Engr-in-charge.
Supply and fixing in replacement fuel pipe from tank to fuel filter with banjo bolts and nuts as per sample length and size to meet the requirement of site condition.
S&F in replacement Gun-metal, globe or gate valve of size 50 mm bore, with iron wheel head, screwed both ends for iron pipe and fixed all as specified and directed.
S&F in replacement Gun-metal, globe or gate valve of size 25mm bore, with iron wheel head, screwed both ends for iron pipe and fixed all as specified and directed.
S& F in replacement 20 mm dia ball brass valves high pressure with polythene float and flynut complete screwed for iron pipe or brass ferrule and fixed all as specified and directed.
M&L for draining out complete mud and sludge from Anaerobic Zone of 80 KLD STP by using non clogging pumps and manually appx depth of vessel is 6.5 mtr from GL & removed silt /mud sludge etc to be dispose off away from the CGRA campus premises complete all as specified and directed by Engineer-in-charge. (Note:- During cleaning Anaerobic Zone of STP alternative for dispose off raw sewage will be made by contractor and cost for the same deemed to be included in this item)
M&L for draining out complete mud and sludge from sedimentation zone of 80 KLD STP by using non clogging pumps and manually appx depth of vessel is 6.5 mtr from GL & removed silt /mud sludge etc to be dispose off away from the CGRA campus premises complete all as specified and directed by Engineer-in-charge .
Dismantling and Taking up unserviceable Non clog horizontal type sewage submersible pump , Capacity 3 HP, from 6m deep tank and rewinding , replacement of bearings/bushes and reassemble and fixing at original position making mechanical and electrical connection and testing incl transportation charges from STP to workshop and back complete all as specified and directed by Engineer - in - Charge.
Dismantling and Taking up unserviceable horizontal type submersible pump , Capacity 7.5 HP, from 6 mtr deep treated water tank of STP and rewinding, replacement of bearings/bushes and reassemble and fixing at original position making mechanical and electrical connection and testing complete all as specified and directed by Engineer - in - Charge.
S&F in replacement V-belt of air blower of 80 MLD STP complete all as specified and directed.
Testing of treated water sample by testing of all parameters such as Organics ,Solids, Nutrients etc from Authorized Govt Lab incl transportation charges from STP at CGRA Naliya to Lab complete all as specified and directed. Test report shall be submitted to Engr-in-Charge.
Dismantling and Taking up unserviceable sludge pump of capacity 1 HP, from STP and rewinding incl replacement of bearings/bushes and reassemble and fixing at original position making mechanical and electrical connection and testing incl transportation charges from STP to workshop and back complete all as specified and directed by Engineer - in - Charge.
S&F in Replacement of 6 sqmm 3 core copper submersible cable complete all as specified and directed.
S&F hose box made of 18 gauge MS Sheet 800mm X 600mm X 250mm with double door with 4 mm thick glasses and door frame made of 16 gauge MS sheet painted fire red out side and brilliant white inside yard
S&F in replacement chlorination automatic dosing pump for RO plant as per sample all as specified and directed by Engr-in-charge.
M&L for Calcium hypochlorite-65-70% chlorine content in liquid calcium based granular disinfectant for treatment of water at STP complete all as specified and as directed
M&L for preparation and painting to old steel surface of hose box of any size with two coats of synthetic enamel paint over one coat of red oxide primer etc complete all as directed.
Dismantling of stone slabs and tiles laid bedded and pointed in any mortar of any description including removal of sand cushioning under paver block, complete all as specified and directed.
Demolition of concrete (unreinforced) in ground floors and paving n exc 15cm thickness (below or above ground level) complete all as specified and directed.
M & L for 100 mm thick cement concrete 1:4:8 type D-2 (40mm graded aggregate) as in floor/sub base and under interlocking all as specified and directed.
M & L for sand filling under floors or in foundations including spreading, levelling, watering and consolidation 30mm thick etc complete all as specified and directed.
Refixing of Machine pressed precast concrete interlocking pave block and shape and size confirming to IS 15658-2006 of 60mm thickness M-35 grade complete
S&F in replacement water circulating pump for RO plant of capacity 500 LPH as per sample all as specified and directed by Engr-in-charge.
GEE CEE ENTERPRISES
SHREE CHAMUNDA CONSTRUCTION WORK
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .