Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹8.9 LAccepted-AOC D NO CC XX 1487 B1 CC 18 1786 B1 NEAR VVLP SCHOOL KONAM PALLURUTHY P O KOCHI 682006 | ERNAKULAM | KERALA | 682006 | L1 | Accepted-AOC L1 bidder | |
| 2 | L2₹9.4 L+₹10,100 (1.09%)Rejected-Finance 26 2579 THEVARA PO KOCHI ERNAKULAM KERALA 682013 | KOCHI | ERNAKULAM | KERALA | 682013 | L2 | Rejected-Finance Quoted rates are higher than L1 | |
| 3 | L3₹11.3 L+₹2.0 L (21.8%)Rejected-Finance | L3 | Rejected-Finance Quoted rates are higher than L1 |
Tender Value
₹10 L
EMD Value
₹20,000
Closing Date
4 May 2020, 6:00 pmClosed
Commander Works Engineer NB Kochi
Commander Works Engineer NB Kochi INS Dronacharya Fort Kochi Kochi 682 001
Comprehensive maint repair of central package chiller eater AC plant under GE Fort Kochi
2020_MES_329982_1
80998/E8
Open Tender
Electrical Maintenance Service
Item Rate
334 days
Fort kochi
c (i) and d (v)
7 documents required · 7 mandatory
₹500
GE FORT KOCHI
₹20,000
Yes
26 Jun 2020
29 Feb 2020
14 May 2020
29 Feb 2020
4 May 2020
20 Mar 2020
29 Feb 2020 - 13 Mar 2020
Amount
Comprehensive maint and servicing of the following AC Plants including repair / replacement of defective unserviceable parts during maint period, necessary periodical maint / checking of AC Plants as per manufacturers instructions :- (i) Microprocessor based chiller water plant 80 TR (Vajra) - 03 Nos (ii) Package type AC 11 TR (RAWS) - 03 Nos (iii) Package type AC 7.5 TR (NTR) - 03 Nos (iv) Package type AC 17.5 TR (Himagiri) - 03 Nos (v) Package type AC 8.75 TR (MSO) - 03 Nos Note :- (a) The rate quoted shall deem to be included the following repairs works :- (i) Checking and calibration of Microprocessor. (ii) Charging of refrigerant gas. (iii) Charging of compressor oil. (b) The rate quoted shall deem to be included General servicing of electrical panels and labour charge for replacement of motor starter, MCCB, MCBs, contactors, connectors, Ammeter, Voltmeter, Indicator lamp, Panel board rewiring with copper conductor of suitable size, and copper conductor for connection to motor from starter.
(c) The rate quoted shall deem to be included General servicing of AC plants every month for smooth functioning of AC plant, cost of log books, maint register and other stationary. Record of checking shall be recorded in a register as per the instruction of Engr in Charge. (d) The rate quoted shall deem to be included Cleaning of cooling tower minimum once in two months for the smooth functioning of all AC plant. (e) Material required for replacement shall be measured and paid under relevant Schedule item No : 2 to 22 as 'supply only'
Supply only Microprocessor controller suitable for 80 TR AC plant. Make : Soft Hard / L&T / Siemens or equivalent
Supply only temperature sensor transducers for 80 TR AC plant.
Supply only pressure sensor transducers for 80 TR AC plant.
Supply only Expansion valve for chiller unit of central AC plant of Cap 80 TR.
Supply only condenser safety valve (self resetting type).
Supply only water pressure gauge, 100 MM dia, 0 to 100 psi. Make : Fiebig / Standard / IMP or equivalent
Supply only DOL starter suitable up to 5 HP capacity pump motor / AHU motor / cooling tower motor. Make : L&T / Siemens / C&S or equivalent
Supply only power contactor for star delta starter suitable for 15 to 20 HP compressor motor. Make : L&T/ Siemens / C&S or equivalent
Supply only overload Relay, 20 - 32 Amps, direct mounting type. Make : L&T/ ABB / Siemens or equivalent
Supply only electronic Star-Delta timer, 160 - 500V, 3 - 30 sec. Make : L&T/ ABB / Legrand or equivalent
Supply only MCB, TP, AC, 415 volt of 32 Amp capacity "K" curve, 10 KA breaking capacity. Make : Legrand / Indo asian / Schneider or equivalent
Supply only MCB, TP, AC, 415 volt of 63 Amp capacity "K" curve, 10 KA breaking capacity. Make : Legrand / Indo asian / Schneider or equivalent
Supply only surface mounted LED phase indicator lamp assembly (RYB) set of three. Make : L&T / Schnieder / ABB or equivalent
Supply only Digital Voltmeter, 3 phase, 440 Volt. Make : L&T / AE / Elmeasure or equivalent
Supply only Digital Ammeter, 3 phase, 440 Volt. Make : L&T / AE / Elmeasure or equivalent
Supply only no volt coil 440 volts. Make : L&T/ ABB or equivalent
Supply only Refrigerant gas R 22 / 407 C. Make : mefron / refron/ fluron or equivalent
Supply only compressor oil 68 grade. Make : Servo/ BP/ HP or equivalent
Supply only 'V' belt A - 30. Make : Poly F Plus / Dunlop / Fenner or equivalent
Supply only 'V' belt A - 60. Make : Fenner/ Poly F Plus / Dunlop or equivalent
Supply only 'V' belt B - 77. Make : Fenner / Poly F Plus / Dunlop or equivalent
Dismantling of compressor of central AC plant for overhauling complete with connected copper pipe line and loading unloading mechanism and pump down the existing refrigerant in separate cylinder, disconnecting of electric motor of compressor, refrigerant line, gauges pipe and carry out the general overhauling of compressor of capacity 80 TR. Make :- Voltas, Model : CWC DR 0800 MNT including replacement of springs, aluminium washer packings, lathe work, cleaning, changing of compressor oil, cleaning of suction filter, oil filter, replacing of minor defective parts complete and the following :- (i) Charging of Nitrogen gas in unit and complete system at 300 psi pressure and checking of any dropping of pressure / leakage up to 24 Hrs and rectification of leakage if any. (ii) Vaccumisation of complete system for 24 Hrs for dropping of vacuum pressure and rectification of leakage if any. (iii) Charging of complete system with R - 22 / 407 C gas for maintaining the system pressure up to HP - 175 psi and LP - 65 psi. (iv) Measure the inlet and outlet temperature of Chiller unit for performance. (v) Testing & commissioning of compressor after completion. Note :- (a) Spares required for compressor shall be measured and paid under relevant Schedule item No : 24 to 31. (b) Any other items required for overhauling except described here - in - after shall be supplied by the contractor with out any extra cost to the deptt and the rates for the same shall deemed to be included in the quoted rates.
Supply only piston, piston rings, oil rings and piston pins.
Supply only cylinder assembly.
Supply only connecting rod.
Supply only bearings for big and small end of connecting rod. Make:- SKF / NTN / NSK or equivalent
Supply only crank shaft including both end bearings.
Supply only shaft seal assembly with `O' ring spring etc.
Supply only oil pump assembly.
Supply only suction and discharge valve reed assembly.
Material and labour for overhauling AHU of any capacity including cleaning of cooling coils with diluted castic soda, cleaning filters, replace both end shaft bearing bolts, nuts and washers and applying two coats synthetic enamel paint to inside the AHU, greasing of AHU blower motor and testing for smooth functioning complete all as specified and directed.
Material and labour for overhauling of pump set up to 3 HP capacity including remetaling of shaft, replacing bush / bearing, gland packing etc complete all as specified and directed.
Material and labour for overhauling of pump set 5 HP capacity including remetaling of shaft, replacing bush / bearing, gland packing etc complete all as specified and directed.
Material and labour for descaling condensing unit with chemicals and Nylon brush and replacing the gaskets suitable for 80 TR capacity.
Taking down unserviceable motor of AHU / CT fan / Pump / Compressor up to 3 HP capacity, cutting out the existing burnt out fan motor winding, cleaning the motor slots, rewinding the motor with insulated copper winding wire of existing gauge, applying varnish to winding, baking / heating up the motor to achieve the proper insulation resistance and refixing after repair at its original position complete all as specified.
All as per Serial Item No 36 here-in-before but 5 HP capacity motor of AHU / CT fan / Pump / Compressor.
All as per Serial Item No 36 here-in-before but 7.5 HP capacity motor of AHU / CT fan / Pump / Compressor.
All as per Serial Item No 36 here-in-before but 20 HP capacity motor of AHU / CT fan / Pump / Compressor.
Supply and fix scroll type sealed compressor of 5.5 TR capacity, recharging of gas, pressure testing etc including taking down old unserviceable scroll type sealed compressor complete all as specified. Note :- Refrigerant gas will be measured and paid separately under relevant Schedule item No : 18. Make:- Kirloskar / copeland / Emerson / GMC / Carrier or equivalent
All as per serial Item No 40 here-in-before but 8.25 / 8.75 TR capacity compressor. Make:- Kirloskar / copeland / Emerson / GMC / Carrier or equivalent
Supply and fix in repair cooling tower fan, 4 bladed, 750 mm dia made out of aluminium and dynamically balanced. Make : Evaprov / GEM / Adva-tech / Jyothi cooling or equivalent
Supply and fix in repair cooling tower fan, 6 bladed, 1800 mm dia made out of aluminium and dynamically balanced. Make : Evaprov / GEM / Adva-tech / Jyothi cooling or equivalent
Supply and fix in repair cooling tower sprinkler, 50 mm with branch pipe assembly. Make : Evaprov / GEM / Adva-tech / Jyothi cooling or equivalent
Supply and fix in repair cooling tower sprinkler, 150 mm with branch pipe assembly. Make : Evaprov / GEM / Adva-tech / Jyothi cooling or equivalent
AR Traders
N.O. Antony Contractors
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.PDF
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .