| 1 | L1₹7.3 LAccepted-AOC 0 AS ENTERPRISES DAYALACHACK HIRANAGAR KATHUA JAMMU KASHMIR 184144 UDYAM JK 09 0013310 | KATHUA | JAMMU AND KASHMIR | 184144 | ₹7.3 L Quoted ₹6.2 L | L1 | Accepted-AOC Being L1 |
| 2 | L2₹7.2 LRejected-AOC VILL CHANDPUR P O KHOUDA SUB TEHSIL TIHRA DISTT MANDI | MANDI | HIMACHAL PRADESH | 175001 | ₹7.2 L | L2 | Rejected-AOC Being L2 |
| 3 | L2₹7.2 LRejected-AOC | ₹7.2 L | L2 | Rejected-AOC Being L2 |
Updated dates
Tender Value
₹9.7 L
EMD Value
₹9,701
Closing Date
4 Feb 2026, 11:00 amClosed
Sr. XEN
ED HPSEBL DHARAMPUR
Tender for restoratation of 11 KV HT Line of Longani feeder damaged at Nalada due to heavy rain fall and flash flood on dated 01.07.2025 in Electrical Section Longani under Electrical sub-division HPSEBL Dharampur
2026_HPSEB_126272_1
134/2025-26
Open Tender
Supply and Erection
60 days
Dharampur
Please refer Tender documents.
3 documents required · 3 mandatory
₹590
₹9,701
13 Mar 2026
21 Jan 2026
4 Feb 2026
21 Jan 2026
4 Feb 2026
21 Jan 2026
Erection of S/T pole 10 mtr long,(Double pole structure) with RCC muff Including digging of pit of size 1.10x0.75x1.50, drilling of holes in poles, X-bracing set, X-arms, Fixing of insulators, X-arms, X- bracing set, fixing of barbed wire, Danger plate, filling of pit & ramming and painting of pole complete in all respects(C.C. 1:3:6 for muffing will be provided by the contractor).
Erection of HT earthing set comprising digging of pit, fixing of GI wire to the earth system,and filling of pit complete in all respects.
Erection of stay set HT line, comprising digging of pit, fixing of stay rod, filling of pit, Nozzeling and tightining complete in all respects.
Sagging of conductor 1 KM single GI wire, , comprising laying of Conductor, stringing & sagging, binding with insulator complete in all respects.
Erection of H T line with ACSR 100 mm² mm such as stringing, tensioning and sagging,jointing and fastening .
Mannual carriage of complete Material of H T line from road side to site of work
Transportation Charges for complete Material of H T line
ACSR 6/1/4.72 mm (100 mm²) {Includes 3 conductor lengths for 3Φ and Additional 1% (Sag, Jumpering and wastage)}
Steel Tubular Poles (10 m, Working Load > 227 kgf/m²) (with Ruling Span 90 m, 8 No. Run thro' and 3 No. Double Pole Dead End Structures)
Muffs (2000mm) with concerete filling
Belt Set - MS Angle Iron: 50x50x6, Length :1800 mm x 2 No.
X-Bracing Set - MS Angle Iron: 50x50x6, Length: 2125 mm x 2 No.
X-Arm (Horizontal) - MS Channel Iron C type: 100X50x6, Length: 2340 mm x 2 No.] ∆ Formation
Discs insulator sets on Dead End structures (comprising 1 No. Disc: ^^(Porcelain, BS, 12 kV, 90 kN) including Dead End Clamps, Straight stapples & Bend Stapples etc.) x (3 No. conductors) x (2 No. sides)
11 kV Pin Insulators (Porcelain, 12 kV, 10 KN): 3 No per pole structure
Stay set complete in all respect (i/c Stay Clamp) (1No. / Single Pole , 4 No. / Double Pole Structures)
Stay Wire (7/3.15 mm) (10.0 kg Per Stay Set)
HT Earthing set complete
Single Continous Earth wire (GI, 8 SWG) {alongwith 2 wire lengths for avg. one road crossing @ 20 m and Additional 3% (Sag, Earthing, Cross lacing above road and wastage)} @ 0.102 kg/m
Eye Hook for earth wire
GO Switch Handle Supporting: [Channel Iron (75x40x6 mm), Length : 460 mm
GO AB Switch Unit (11kV, 400A, 25 KA ) Tripple pole O/D type
D.O Fuse Unit
Half clamps: [On Double Pole Dead End structure: 4 No; On Run Thro' structure: 2 No ]
Full clamps: [On Double Pole Dead End structure: 4 No, Single Pole Run Thro' structure: 2 No]
Danger Plate (250X200X1.6 mm)
Nuts and Bolts of Various Sizes (Galvanised / Coated) [Preferably 16 mm Φ or more (with flat and spring washers)]
Red Oxide
Aluminium Paint
Barbed Wire
Erection of 100 kVA, 11/0.4 kV Sub-Station complete in all respect
Mannual/ Transportation/ Loading /Unloading Charges of complete Material of 100 KVA,11/0.4kV S/Stn from road side to site of work
Distribution Transformer (Ordinary), 11/0.4 kV, 100 KVA
Steel Tubular Poles (9 m, Working Load > 200 kgf/m²)
Muffs (2000mm) with concerete filling
X-Arm: [Channel Iron (100x50x6 mm), Length : 2800 mm X 2 Nos] for incomer line
MS Angle Iron (50X50x6 mm), Length: (2800 mm) x1 Nos for LA's
X-Arm: [Channel Iron (75x40x6 mm), Length : (2800 mm X 4 Nos] for supporting DO fuse unit & GO switch
X-Arm: [Channel Iron (100x50x6 mm), Length : 2800 mm X 2 Nos] for Transformer Bed
X-Arm [Channel Iron (100x50x6 mm), Length : (460 mm) x 2 Nos for supporting Main Channel of Transformer]
MS Angle Iron (50X50x6 mm), Length : (2800 mm) x 2 Nos
MS Angle Iron (35X35x6 mm), Length : (460 ) x 2 Nos
MS Angle Iron (50X50x6 mm), Length : (950 mm) x 2 Nos for Bed Knee Bracing
MS Angle Iron (50X50x6 mm), Length : (2800 mm) x 2 Nos
MS Angle Iron (50X50x6 mm), Length : (450 mm) x 1 Nos
GO Switch Handle Supporting: [Channel Iron (75x40x6 mm), Length : 460 mm
GO AB Switch Unit (11kV, 400A, 25 KA ) Tripple pole O/D type
D.O Fuse Unit
Surge Arrester, 9 kV Station Class (Porcelain Type)
Discs insulator sets (comprising 1 No. Disc: ^^(Porcelain, BS, 12 kV, 90 kN) including Dead End Clamps etc.)
Stay set complete (i/c Stay Clamps)
Stay Wire (7/3.15 mm) (7.0 kg Per Stay Set)
Pipe Earthing Set and
6 SWG GI wire For Earthing
Panel (Distribution Box LT for 100 kVA DTR MS Sheet of 1.6 mm ( 900x800x200 mm ) cubide Box complete with stand etc and Al Busbar (25x6mm)inside .painted /powder coated after primar coating ,MCCB 160 amp 3P 35kA , ICS =100 % ICU, Kit-Kit 200 Amp
Half Clamp (M.S. Flat 50X6 mm)
Full Clamps (M.S. Flat 50X6 mm)
Nuts and Bolts of Various Sizes (Galvanised / Coated) [Preferably 16 mm Φ or more (with flat and spring washers)]
Aluminium Thimble off size
Copper Thimble 200 Amp
Danger Plate
Barbed Wire
LT Cable 3.5 X 120 mm²
Aluminium Paint.
Red Oxide
Erection of CT/PT combined unit VT 11kV/110V, CT 10/5A, 15/5A, 20/5A, 25/5A, 50/5A, 100/5A, 150/5A, 200/5A, 400/5A,
Mannual carriage of complete Material
Transportation Charges for complete
Prov.CT/PT combined unit VT 11kV/110V, CT 10/5A, 15/5A, 20/5A, 25/5A, 50/5A, 100/5A, 150/5A, 200/5A, 400/5A,
Prov.3-ɸ, 4 wire CT operated Static Tri-Vector meter (CT-200/5 A) Accuracy Class: 0.5S, Category-C, DLMS Compliant
Prov. AAAC conductor 7/3.15 mm for jumper
Prov.PVC control cable 12 core 2.5 mm2 (multistrand copper)
Prov. Aluminium Thimble 500 mm
Prov. MSCI X-arm (2800X100X50X6mm) for CTPT bed (2Nos.)
Prov. MSCI X-arm (100X50X6mm) 2 Nos
Prov. MSAI Knee bracing set (950X50X50X6) 4Nos
a)MSAI (2800X50X50X6mm) 2Nos
b)MSAI (460X35X35X6mm) 2Nos
Prov. MS nuts & bolts various size (Galvanised / coted Preferably 16mm O or more with flat and spring wash
Please Enable Macros to View BoQ information
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.30 MB
Tendernotice_2.pdf
PDF • 0.31 MB
BOQ_186144.xls
BOQ • 0.36 MB
Download all tender documents and submit your bid