Loading…
Loading…
Tender Value
₹19.6 L
EMD Value
₹39,269
Closing Date
22 Jun 2026, 4:00 pm
EXECUTIVE ENGINEER RNB ELECTRIC DIVISION KASHMIR
RNB ELECTRIC DIVISION KASHMIR ENGINEERING COMPLEX RAJ BAGH
Infrastructural Development Upgradation B.W.O Installation of High Mast lights Genset in FNV Market Ganderbal B.W.O Electric work Electric part
2026_PWDJK_311690_1
NIT No.41//2026-27 Dt/06/06/2026
Open Tender
Electrical Works
40 days
Ganderbal
Please refer Tender documents.
4 documents required · 4 mandatory
₹800
EXECUTIVE ENGINEER RNB ELECTRIC DIVISION KASHMIR
₹39,269
6 Jun 2026
6 Jun 2026
23 Jun 2026
6 Jun 2026
22 Jun 2026
6 Jun 2026
This is a percentage-rate BOQ. The schedule below shows estimated quantities and rates. Bidders quote a single percentage above or below the total estimated cost.
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Part-A(Panel & Cabling ) | - | - | - | - |
| 2 | Design/Supply/Installation/Testing and commissioning of distribution/feeder outdoor panel having a sloped roof (3+1) Al. bus bar( Bus Bar shall be insulated with heat shrinkable sleeves and shall be colour coded having minimum size 20 mm x 10 mm with spacing as per latest IE Standards) of cubical type vermin proper double door lockable outdoor type fabricated out of 14/16 SWG MS Sheets powder coated weather proof, dust proof with IP 65 protection with angle iron stand of 2.5 feet height/ground clearance properly grouted in cement concrete of 1:2:4 ratio-filter with baby insulators/glands/thimbles suitable for use at 415 Volts 3 Phase,4 wire 50Hz system complete in all respects complete in all respects with following:
Incomer: 400 Amp TPN MCCB Adjustable Type with 50 kA Breaking capacity of L&T /ABB /Legrend /Simens make = 1 No.
Digital Multi function Volt Meter with C T of proper ratio. = 1 set indicators = 3 no.
Outgoing:
630 Amps TPN Aluminium Bus Bar = 1 Set
The Panel manufacturing unit should be CPRI Registered with latest ammended IEC / IS 61439 and the Contractor has to submit the test certificate of main switch gear's and Drawing's of panel (Showing claerly dimensions of panel with spacing of switchgear as per IE Standards ) & is to approved by Department not less than the rank of SDO before manufacturing of panel. | 1 | No | 85,000 | ₹85,000 |
| 3 | ENVIRONMENTALLY SAFE MAINTENANCE FREE COPPER ROD EARTHING SYSTEM Necessary soil treatment is to be made by the contractor in order to improve the Pit resistance Value.Supply,Installation and Testing of 75 mm copper Pipe Filled with Crystalline conductive Mixture with Eco friendly GEM Backfill Compound 2No. Bags also having Earth pit chamber (300mm x 300mm) with man- hole cover for the above. Including cost of 20mm Wide copper strip as required in one run fitted with of brass nut bolt & spring washer from EARTHING ROD up to MAIN Control PANEL through suitable DWC High Density Poly ethylene Pipe having Corrugation complete job. | 1 | No | 10,500 | ₹10,500 |
| 4 | Supply/Excavation/Laying/Testing and Commissioning of 3.5-Core 120 mm sq. Al armored PVC cable withstand voltage of 650/1100V ISI Marked. Havells/Polycab/RR-Kabel/KEI Make. IIncluding Supply/Laying of HDPE Pipe ISI marked along with all accessories like socket, bend, couplers etc. conforming to IS 14930, Part II complete with fitting and cutting, jointing etc.direct in ground (01 Ft below ground level) including excavation and refilling the trench of standard make as approved.The cable shall include end termination lugs with its crimping /taping.(Sub-Station to Main Panel) | 30 | Mtr. | 1,650 | ₹49,500 |
| 5 | Design,Fabrication,Supply, Installation, Testing and Commissioning of Main LT Control outdoor slopped Roof,Double Door panel Floor Mounted fabricated of 16 gauge sheet steel,the panel should have standing dust & vermin proof with gasket lockable door of 16 gauge sheet steel with angle iron stand of 2.5 feet height/ground clearance properly grouted in cement concrete (If Required) of 1:2:4 ratio-filter . The Panel should be painted with Electro static powder coated colour, Siemens grey structural with proper chemical pre-treatment with film thickness 35-40 Microns,duly fitted with Voltmeter, R/Y/B Phase-indicators etc with baby insulators/glands/thimbles suitable for use at 415 Volts 3 Phase,4 wire 50Hz system complete in all respects complete in all respects with following:-
Incoming: 1) 250 Amp-4 pole,50kA MCCB with extended terminals Adjustable Thermal & Fixed Magnetic with ROH Switch L&T/ABB/Legrand/Simens Make = 01 No.
2) 200 Amp-4 pole,50kA MCCB with extended terminals Adjustable Thermal & Fixed Magnetic with ROH Switch L&T/ABB/Legrand/Simens Make = 01 No.
Generator: 200 Amp Changerover ROH Switch Legrand/L &T/ABB Make including S/F/Crimping of Suitable Size of thimbles for connections
ByPass Switch: 3-Phase, Four Pole 200 Amp,415V Ac,50Hz,Rotatory Handle bypass Switch Legrand/L &T/ABB/Equivalent Make including S/F/Crimping of Suitable Size of thimbles for connections as per site requirement for bypassing AVR. as approved.
Outgoing: 600 Amp Suitable Al. Bus bar = 01 Set , 160 Amp 4 pole,36kA MCCB with extended terminals Adjustable Thermal & Fixed Magnetic with ROH Switch L&T/ABB/Legrand/Simens Make = 02 No. for 02 Ckts. Panel shall have provision for entry of cables from the bottom as required.
The Panel manufacturing unit should be CPRI Registered with latest ammended IEC / IS 61439 and the Contractor has to submit the test certificate of main switch gear's and Drawing's of panel (Showing claerly dimensions of panel with spacing of switchgear as per IE Standards ) & is to approved by Department not less than the rank of SDO before manufacturing of panel. | 1 | No | 2,00,000 | ₹2,00,000 |
| 6 | Design/Supply/Installation/Testing and commissioning of distribution/feeder outdoor panel having a sloped roof (3+1) Al. bus bar of cubical type vermin proper double door lockable outdoor type fabricated out of 14/16 SWG MS Sheets powder coated weather proof, dust proof with IP 65 protection with angle iron 50x50x6mm stand painted in black colour of 2.5 feet height/ground clearance properly grouted in cement concrete of 1:2:4 ratio-filter with baby insulators/glands/thimbles suitable for use at 415 Volts 3 Phase,4 wire 50Hz system complete in all respects complete in all respects with following
Incoming: 400 Amp Suitable Al. Bus bar =01 Set.
Outgoing: 1) 63Amp-4 pole,10kA TPN of L&T/Legrand/Schneider make as approved-01 No.
2) 40 Amp-DP,10kA of L&T/Legrand/Schneider make as approved-01 No.
3) 10-32 Amp-SP,10kA of L&T/Legrand/Schneider make as approved-08 No.
Panel shall have provision for entry of cables from the bottom as required.The Panel manufacturing unit should be CPRI Registered with latest ammended IEC / IS 61439 and the Contractor has to submit the test certificate of main switch gear's and Drawing's of panel (Showing claerly dimensions of panel with spacing of switchgear as per IE Standards ) & is to approved by Department not less than the rank of SDO before manufacturing of panel. | 4 | No | 34,000 | ₹1,36,000 |
| 7 | Providing of Earthing Complete by GI Pipe 40mm 3 mtr long through GI Strip 25x3mm | 5 | No | 2,234 | ₹11,170 |
| 8 | Supply/Laying/Testing and Commissioning of 3.5-Core 70 mm sq. Al armored XLPE Insulated,PVC cable Havells/Polycab/RR Make. Including Supply/Laying of HDPE Pipe ISI marked along with all accessories like socket, bend, couplers etc. conforming to IS 14930, Part II complete with fitting and cutting, jointing etc.direct in ground (01 Ft below ground level) including excavation and refilling the trench of standard make as approved.The cable shall include end termination lugs with its crimping /taping. | 200 | Mtr. | 1,050 | ₹2,10,000 |
| 9 | Part-B (High-Mast Lighting) | - | - | - | - |
| 10 | Supply installation testing & Commissioning of 12.5 Mtr HM (in 2 section) suitable for 12 No. Luminaries high mast lighting system (as per PLG 07 of ILP UK technical report no 7 of ILE UK /IS:875 Part-1 - 2015//BSEN10025/and IS:2062 )consisting of totally hot dip galvanised by piecewise single dipped method high mast, lantern carriage suitable for up to 12 nos luminaries with welded arm (excluding luminares), mast head frame assembly with full cover, including 1 No. LED 15 Watts aviation obstruction lights, double drum type self sustaining winch, integral power tool accesible from door with padlocking arrangement (winch motor with control circuit) hot dipped galvanised heavy duty pipe lightening finial, Stainless steel 6 mm dia. wire ropes (AISI 316, 7 / 19 costruction 3 no. rope for lantern carrage & 2 no. rope for winch assembly ) foundation bolt, torque limiter, EPR insulated PCP sheathed 5 core x 2.5 Sq.mm trailing cable.The mast is constructed from mild steel plates (as per IS 5986 Gr. 510) cut and folded to form a polygonal section, telescopic jointed and welding as per BS 5135.etc. as required on Existing Foundation.The OEM Must have Type test certificate for wind tunnel test . All as per pre approved by Engineer in charge. All as per pre approved by Engineer in charge. (Bajaj/Philips/Valmont/Utkarash/Surya/BPP Make) | 2 | No | 1,75,000 | ₹3,50,000 |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 1.58 MB
BOQ_1009175.xls
BOQ • 0.58 MB
Download all tender documents and submit your bid