Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹2.0 CrAdmitted-Finance | ₹2.0 Cr | L1 | Admitted-Finance |
| 2 | L2₹2.1 Cr+₹5.0 L (2.46%)Admitted-Finance | ₹2.1 Cr+₹5.0 L (2.46%) | L2 | Admitted-Finance |
| Sl No | Description | Qty | Unit | SAINKO SYSTEMS L2 | AR ENTERPRISES L1 |
|---|---|---|---|---|---|
| 1.00 | TRANSFORMER (11 KV / 0.433 KV)
Supply, Installation, testing and commissioning of 800 KVA. 11/0.433 KV, 3 Phase, 50Hz, Dyn 11, Oil type, copper wound transformer with ON load tap changing arrangement on HV side in steps of +/- 2.50%, +/- 5% , having cable end boxes on HV side and 500 Amp. bus trunking arrangement on LV side complete with all accessories i/c first filling of filtered dehydrated oil and confirming to IS 2026 (Part 1 to Part 5) & as per specification attached complete in all respects as required at site. Note:Foundation work for transformer is not included. | 1 | Nos. | 32,11,600 ₹32,11,600 | 31,10,800 ₹31,10,800 Lowest |
| 2.00H.T. VCB (11KV) Design, manufacturing, testing at works, supply of HT Panel as per specification and comprising of the following :- | |||||
| 3.00INCOMER/OUTGOING PANEL | |||||
| 4.00630 A Vacuum circuit breaker of 26.3 KA ruputuring capacity at 11 KV rated, totally enclosed,air insulated metal clad housing, floor mounting, vertical isolation,vermin proof,fully interlocked horizontal drawout type having double isolation. | |||||
| 5.00Manually and motor operated, spring charged( release closing mechanism) trip free type,triple pole truck mounted draw out, vacuum circuit breaker, incorporating mechanical as well as electrical ON/OFF indication. Spring charge/discharge mechanical indicator. | |||||
| 6.00630 amp air insulated but encapsulated,PVC insulated Copper bus bars. | |||||
| 7.00C.T. chamber with C.T.'s 50/5. | |||||
| 8.0015 VA burden for protection (class 5P 10). | |||||
| 9.00Following protection shall be provided: | |||||
| 10.001 Nos IDMT relay with instantaneous 2 nos. over currrent (50, 50 N) element and 1 no. instantaneous earth fault element(50-50N).(O/C setting 50%-200% and E/F setting 20%-80%) | |||||
Tender Value
Refer Docs
EMD Value
₹4.1 L
Closing Date
29 Apr 2025, 3:00 pmClosed
DGM HQ BRIDCUL
BRIDCUL Opp Govt ITI Niranjanpur Saharanpur Road Dehradun
External Electrification and Allied works for Rajeev Gandhi Navodaya Vidhyalaya District Rudraprayag
2025_BRID3_82794_2
797/BRIDCUL/988/1/25 Dated 09.04.2025
Open Tender
Electrical Works
Item Rate
540 days
Rudraprayag Uttarakhand
Please refer Tender documents.
3 documents required · 3 mandatory
₹5,900
MD - BRIDCUL
₹4.1 L
BRIDCUL Dehradun
30 Apr 2025
16 Apr 2025
29 Apr 2025
16 Apr 2025
29 Apr 2025
23 Apr 2025
22 Apr 2025
Amount
TRANSFORMER (11 KV / 0.433 KV) Supply, Installation, testing and commissioning of 800 KVA. 11/0.433 KV, 3 Phase, 50Hz, Dyn 11, Oil type, copper wound transformer with ON load tap changing arrangement on HV side in steps of +/- 2.50%, +/- 5% , having cable end boxes on HV side and 500 Amp. bus trunking arrangement on LV side complete with all accessories i/c first filling of filtered dehydrated oil and confirming to IS 2026 (Part 1 to Part 5) & as per specification attached complete in all respects as required at site. Note:Foundation work for transformer is not included.
H.T. VCB (11KV) Design, manufacturing, testing at works, supply of HT Panel as per specification and comprising of the following :-
INCOMER/OUTGOING PANEL
630 A Vacuum circuit breaker of 26.3 KA ruputuring capacity at 11 KV rated, totally enclosed,air insulated metal clad housing, floor mounting, vertical isolation,vermin proof,fully interlocked horizontal drawout type having double isolation.
Manually and motor operated, spring charged( release closing mechanism) trip free type,triple pole truck mounted draw out, vacuum circuit breaker, incorporating mechanical as well as electrical ON/OFF indication. Spring charge/discharge mechanical indicator.
630 amp air insulated but encapsulated,PVC insulated Copper bus bars.
C.T. chamber with C.T.'s 50/5.
15 VA burden for protection (class 5P 10).
Following protection shall be provided:
1 Nos IDMT relay with instantaneous 2 nos. over currrent (50, 50 N) element and 1 no. instantaneous earth fault element(50-50N).(O/C setting 50%-200% and E/F setting 20%-80%)
All wiring necessary for the above including inter-connections. The size of the conductor should not be less than 2.5 sq. mm. Copper wire where required.
Test terminal block, fuses/2A SPMCB , circuit labels,set of phase, indication lamps etc. as per standard practise as under.
Red - Breaker close (ON)
Green - Breaker open (OFF)
Amber - auto trip
Clear - trip circuit healthy
Blue spring charged
Control :- T-N-C (Trip, Neutral. Close) breaker control switch with indication arrangement.
Terminal boxes with single gland trifucating cable box suitable for 11 KV Aluminium XLPE (E) cable of size 3C x 300 Sq. mm. for incoming/outgoing breaker.
HT Danger Plate.(as per IS specification)
2 Runs of 40 X 5 mm earth bus shall be provided for the full length of the panel.
Necessary D.C. supply healthy indication lamp (White Colour), switch with alarm.
Surge supressor as required.
DC Voltmeter, 0-50 Volt, Digital type.
HT Panel switchboard complete with all interconnections, labels, wiring etc, complete as described above specifications.
Providing and fixing HT danger notice plate 250 mm x 200 mm made of mild steel at least 2mm thick & vitreous enamelled white on both sides and with inscription in signal red colour on front side as required.
Supplying and Fixing of Fire buckets, round bottom made of G.I. Sheet 9-11 litres capacity duly painted as per fire brigade design, supported on hanging bracket chained and locked, initially filled with fine river sand, water as per directions of Engineer-in-charge.
Supplying and Laying of Rubber mat 1000 mm. Wide to withstand 11 KV dielectric strength as per latest IS 15652-2006 etc. as reqd.
Supply and fixing of fire extinguishers, ABC Type 9.00 kg. capacity(ISI Marked IS : 15683 ) complete with initial charges and wall bracket, along with supply of all materials and labour for proper completion of work.
Supply and fixing of CO2 type fire extinguishers, 4.50 kg. capacity(ISI Marked IS : 2878 ) complete with initial charges and wall bracket, along with supply of all materials and labour for proper completion of work.
Supply of 3 core stranded aluminium conductor 11KV grade XLPE (E) (Cross linked Polyethylene) insulated PVC bedded, Galvanised flat steel strip armoured cable confirming to IS : 7098 (part II with latest amendments).
300 sq. mm 3 core
Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 11 KV grade of following size direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc as required
Above 120 sq. mm and upto 400 sq. mm
Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 11 KV grade of following size in the existing RCC/HUME/ METAL pipe as required.
Above 120 sq. mm and upto 400 sq. mm
Supply and making indoor cable end jointing with cast resin compound, including lugs and other jointing materials, for 3 core 300Sq.mm. XLPE aluminium conductor cable of 11 kV grage as required.
Supply and making outdoor cable end jointing with cast resin compound, including lugs and other jointing materials, for 3 core 300 Sq.mm. XLPE aluminium conductor cable of 11 kV grage as required.
Supplying, Installation and commissioning of AMF start silent type 320KVA DG set comprising of suitable BHP diesel engine directly coupled to 3 phase 50 Hz 415 V alternator of 320 KVA rating at 0.8 power factor mounted on a common base frame, complete in all respects with all required safety devices, fittings, batteries, accessories, filters, residential type silencer, control panel, inbuilt diesel oil MS tank of 990 ltrs. capacity made of 2mm thick M.S. sheet complete with M.S. fuel piping, G.M. gate valves, supports, control cable between generating set and control panel, exhaust piping with asbestos roping, antivibration mounting pads, first filling of lubricant oil totally enclosed in air tight, dust proof, weather proof, powder coated cubical type, sound proof as per CPCB norms acoustic enclosure made of 2mm thick CRCA sheet with with heavy duty doors, lockable arrangement, sound proof insulation with high density rock/mineral polymer/fibre cloth and perforated CRCA sheets, suitable to reduce the sound level upto 75dba approx. at a distance of 1 mtrs. as per CPCB norms
AMF Panel Incoming-500 Amps FP MCCB of 35KA breaking capacity and contactor same rating
Main LT Panel
Same as above item but following mountings.
INCOMER:-
1 No 1250 Amp. 4P EDO ACB of 50KA (Ics=Icu) Breaking Capacity
1 No 500 Amp. 4P MCCB of 35KA (Ics=Icu) Breaking Capacity
1 No 500 Amp. 4P Contractor
2 No. Multi Function Meter.
2 No. CT FOR APFC PANEL
2 Set of phase indicating lamps with Single Pole MCB.
2 Set of ON / OFF indicating lamps with Single Pole MCB.
2 Set 50,50N,51,51N,27,32,49,59,86,95 CT's control.
BUS COUPLER:-
1 No 500 Amp. 4P MCCB of 35KA (Ics=Icu) Breaking Capacity
1 No 500 Amp. 4P Contractor
BUS BARS:-
1600 Amps. TP&N aluminium bus bars-1 nos.
600 Amps. TP&N aluminium bus bars-1 nos.
OUT GOINGS:-
4 Nos. 320 Amps. FP MCCB thermal magnetic release
3 Nos. 200 Amps. FP MCCB thermal magnetic release
2 Nos. 160 Amps. FP MCCB thermal magnetic release
2 Nos. 63 Amps. FP MCCB thermal magnetic release
1 Nos. 40 Amps. FP MCCB thermal magnetic release
2 Nos. 40A DP MCB
2 Nos. Space & Spare
CAPACITOR PANEL-200 KVAR
Incoming
One (1) No 320 Amp. 4P MCCB of 35 KA Breaking capacity
BUS BAR
1 Set of 400 Amps TPN Aluminium Bus Bars
OUT GOING
02 No. 125 Amps. TP MCCB (25 KA) (50KVAR)
02 No. 63 Amps. TP MCCB (25 KA) (25KVAR)
02 No. 40 Amps. TP MCCB (25 KA) (15KVAR)
02 No. 25 Amps. TP MCCB (25 KA) (10KVAR)
Panel described as above CAPACITOR PANEL-200 KVAR
FEEDER PANEL-1
INCOMER:-
1 No 320 Amp. 4P MCCB of 35KA (Ics=Icu) Breaking Capacity
1 No. Multi Function Meter.
1 Set of phase indicating lamps with Single Pole MCB.
1 Set of ON / OFF indicating lamps with Single Pole MCB.
BUS BARS:-
400 Amps. TP&N aluminium bus bars (25 KA)
OUT GOINGS:-
6 Nos. 100 Amps. FP MCCB
4 Nos. 16 Amps. DP MCB
2 Nos. Space & Spare
FEEDER PANEL-2
INCOMER:-
1 No 63 Amp. 4P MCCB of 25KA (Ics=Icu) Breaking Capacity
1 No. Multi Function Meter.
1 Set of phase indicating lamps with Single Pole MCB.
1 Set of ON / OFF indicating lamps with Single Pole MCB.
BUS BARS:-
100 Amps. TP&N aluminium bus bars (25 KA)
OUT GOINGS:-
3 Nos. 40 Amps. FP MCCB
2 Nos. 16 Amps. DP MCB
2 Nos. Space & Spare
FEEDER PANEL-3
INCOMER:-
1 No 320 Amp. 4P MCCB of 35KA (Ics=Icu) Breaking Capacity
1 No. Multi Function Meter.
1 Set of phase indicating lamps with Single Pole MCB.
1 Set of ON / OFF indicating lamps with Single Pole MCB.
BUS BARS:-
400 Amps. TP&N aluminium bus bars (25 KA)
OUT GOINGS:-
5 Nos. 125 Amps. FP MCCB
1 Nos. 63 Amps. FP MCCB
5 Nos. 16 Amps. DP MCB
2 Nos. Space & Spare
EXTERNAL LIGHTING PANEL Outdoor type
INCOMER:-
1 No 40 Amp. 4P MCCB of 25KA (Ics=Icu) Breaking Capacity
1 Set of phase indicating lamps with Single Pole MCB.
1 Set of ON / OFF indicating lamps with Single Pole MCB.
BUS BARS:-
60 Amps. TP&N aluminium bus bars (25 KA)
OUT GOINGS:-
2 Nos. 32 Amps. FP MCB
10 Nos. 16 Amps. DP MCB
2 Nos. Space & Spare
S.I.T.C of outdoor type feeder panel of incomer 1250A MDO ACB.
Providing and fixing M.V. danger notice plate of 200 mm X 150 mm, made of mild steel, at least 2 mm thick, and vitreous enameled white on both sides, and with inscription in single red colour on front side as required. Details of cost for one each
Earthing with G.I. earth plate 600 mm x 600 mm x 6 mm thick including accessories , and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. (but with charcoal or coke and salt) as required.
Earthing with copper earth plate 600 mm X 600 mm X 3 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required
Supplying and laying 25 mm X 5 mm copper strip at 0.50 metre below ground as strip earth electrode, including connection/ terminating with nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of brass nut bolt & spring washer spaced at 50mm)
Supplying and laying 25 mm X 5 mm G.I strip at 0.50 metre below ground as strip earth electrode, including connection/ terminating with G.I. nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of G.I. nut bolt & spring washer spaced at 50mm)
Laying of one number PVC insulated and PVC sheathed / XLPE power Cable of 1.1 KV grade of following size direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc as required.
Up to 35 sq.mm.
Above 35 sq.mm. and up to 95 sq.mm.
Above 95 sq.mm. and upto 185 sq.mm.
Above 185 sq.mm. and up to 400 sq.mm.
Laying of one number additional PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground in the same trench in one tier horizontal formation including excavation, sand cushioning, rotective covering and refilling the trench etc as required
Up to 35 sq.mm.
Above 35 sq.mm. and up to 95 sq.mm.
Above 95 sq.mm. and upto 185 sq.mm.
Above 185 sq.mm. and up to 400 sq.mm.
Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground including excavation and refilling the trench etc as required, but excluding sand cushioning and protective covering.
Up to 35 sq.mm.
Above 35 sq.mm. and up to 95 sq.mm.
Above 95 sq.mm. and upto 185 sq.mm.
Above 185 sq.mm. and up to 400 sq.mm.
Laying of one number additional PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground in the same trench in one tier horizontal formation including excavation and refilling the trench etc as required, but excluding sand cushioning and protective covering.
Up to 35 sq.mm.
Above 35 sq.mm. and up to 95 sq.mm.
Above 95 sq.mm. and upto 185 sq.mm.
Above 185 sq.mm. and up to 400 sq.mm.
Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing RCC/ HUME/ METAL pipe as required
Up to 35 sq.mm.
Above 35 sq.mm. and up to 95 sq.mm.
Above 95 sq.mm. and upto 185 sq.mm.
Above 185 sq.mm. and up to 400 sq.mm.
Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing masonry open duct as required.
Up to 35 sq.mm.
Above 35 sq.mm. and up to 95 sq.mm.
Above 95 sq.mm. and upto 185 sq.mm.
Above 185 sq.mm. and up to 400 sq.mm.
Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on wall surface as required
Upto 35 sq. mm (clamped with 1mm thick saddle
Above 35 sq. mm and upto 95 sq. mm (clamped with 25x3mm MS flat clamp
Above 95 sq. mm and upto 185 sq. mm (clamped with 25/40x3mm MS flat clamp
Above 185 sq. mm and upto 400 sq. mm (clamped with 40x3mm MS flat clamp)
Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on cable tray as required.
Upto 35 sq. mm (clamped with 1mm thick saddle)
Above 35 sq. mm and upto 95 sq. mm (clamped with 25x3mm MS flat clamp)
Above 95 sq. mm and upto 185 sq. mm (clamped with 25/40x3mm MS flat clamp)
Above 185 sq. mm and upto 400 sq. mm (clamped with 40x3mm MS flat clamp)
Supply of following siz of 1.1KV grade multicore aluminium conductor XLPE insulated and PVC shethed armoured cable as per IS 7098:1988 with up to date amendment
3.5 x 400 sq.mm.
3.5 x 300 sq.mm.
3.5 x 240 sq.mm.
3.5 x 185 sq.mm
3.5 x 150 sq.mm
3.5 x 120 sq.mm
3.5 x 95 sq.mm
3.5 x 70 sq.mm
3.5 x 50 sq.mm
3.5 x 35 sq.mm
3.5 x 25 sq.mm.
4 x 25 sq.mm
4 x 16 sq.mm
4 x 10 sq.mm
3 x 10 sq.mm
2 x 16 sq.mm,
2 x 10 sq.mm,
2 x 6 sq.mm,
Supplying and making cable end terminations with brass compression gland and aluminium lugs for following size of PVC insulated PVC sheathed/XLPE aluminium conductor cable of 1.1 KV grade, complete as required.
2 X 6 sq. mm (19mm)
2 X 10 sq. mm (19mm)
2 X 16 sq. mm (22mm)
3 X 10 sq. mm (22mm)
3½ X 25 sq. mm (28mm)
3½ X 35 sq. mm (32mm)
3½ X 50 sq. mm (35mm)
3½ X 70 sq. mm (38mm)
3½ X 95 sq. mm (45mm)
3½ X 120 sq. mm (45mm)
3½ X 150 sq. mm (50mm)
3½ X 185 sq. mm (57mm)
3½ X 225 sq. mm (62mm)
3½ X 240 sq. mm (62mm)
3½ X 300 sq. mm (70mm)
3½ X 400 sq. mm (82mm)
4 X 10 sq. mm (25mm)
4 X 16 sq. mm (28mm)
Supplying and making outdoor end termination with cast resin compound including aluminium lugs and other jointing materials for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.
3.5 x 400 sq.mm
3.5 x 300 sq.mm
3.5 x 240 sq.mm
3.5 x 185 sq.mm
3.5 x 150 sq.mm
3.5 x 120 sq.mm
3.5 x 95 sq.mm
3.5 x 70 sq.mm
3.5 x 50 sq.mm
3.5 x 35 sq.mm
3.5 x 25 sq.mm
4 x 16 sq.mm
Supplying and making straight through joint with heat shrinkable kit including ferrules and other jointing materials for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.
3.5 x 400 sq.mm
3.5 x 300 sq.mm
3.5 x 240 sq.mm
3.5 x 185 sq.mm
3.5 x 150 sq.mm
3.5 x 120 sq.mm
3.5 x 95 sq.mm
Providing, laying and fixing following dia RCC pipe NP2 class (light duty) in ground complete with RCC collars, jointing with cement mortar 1:2 (1 cement : 2 fine sand) including trenching (75 cm deep) and refilling etc as required.
100mm dia
150 mm dia
250 mm dia
300 mm dia
Supplying, installation & testing of 7.0 m high octagonal GI pole with single arm as per approved sample made from 3 mm sheet steel (Grade S 355 J0) with top diameter as 75mm and bottom dia as 150mm and base plate of 240x240x16 mm with suitable slot shaped holes for mounting the same on a shallow foundation, GI weather proof junction box with 16A SP MCB, loop-in-loop out terminals for 2nos. 2Cx6 sq.mm YWY cables and 2x2.5 sq.mm copper conductor from junction box to fitting and connected accessories as required etc. Contractor to include the cost of RCC foundation for pole as per structural detail.
Supplying, installation & testing of 9.0 m high octagonal GI pole with double arm as per approved sample. Contractor to include the cost of RCC foundation for pole as per structural detail.
Supply and fixing of LED Street light Fitting with mandatory driver set having die cast aluminium body and lenses suitable for 70Watt. to 80 Watt and Confirming to IP66 protection having Company LOGO Engraved complete in all respect with 4000-5000 system lumens High Power LED with lenses, >110lm/W, PF>0.95, THD <10% at full load, CRI>70, Avg Life Class 50000Hrs@L70,fitting itself suitable for 60-65mm OD pipe
S & F cast aluminium 4 mtr. Pole for post top light complete as required.
Supply and fixing of decorative 50 to 55 Watt LED Post top indirect light luminaire having Pressure die cast aluminium body and Clear glass with driver set confirming to IP 65 and above protection complete in all respect.
Supply and fixing of decorative 8 to 16 Watt LED bollard luminaire with driver set confirming to IP 65 protection complete in all respect
Supply & fixing of 16 mtr High mast shaft with 8 Nos. 250W LED light of approved make with rising system hot dip glavanized inside & out side dip, suitable for wind velocity as per IS 875 part 3 & having no circumferential weld, with accessories for high mast such as head frame & its control gear boxes power tool moter, 3 point suspension system with steel wire rope 6 mm dia, double drum winch, including making suitable foundation as per manufature drawing/ site reuiment along with foundation bolts nuts, washers, anchor plates etc, completee in all respect.
Supplying,installation,testing and commissioning of Astronomical time switch of following configuration to be mounted in feeder pillars / Lighting DBs for automatic switching On & OFF of street lights at sun set & sun rise or twilight(Auto ON, Auto OFF, Auto modes) with manual override facility with 12/24 hour display format with suitable battery and indication for relay status i/c programming at site complete as required.
1 output per phase and suitable for single phase supply
Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground including excavation and refilling the trench etc as required, but excluding sand cushioning and protective covering.
Up to 35 sq.mm.
Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on wall surface as required
up to 35 sq.mm.
Supply of following siz of 1.1KV grade multicore aluminium conductor XLPE insulated and PVC shethed armoured cable as per IS 7098:1988 with up to date amendment
Size 10 sq.mm x 3 core
Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required
3 X 10 sq. mm (22mm)
Earthing with G.I. earth pipe 4.5 metre long, 40 mm dia including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. with charcoal/ coke and salt as required
Supplying and laying 25 mm X 3 mm G.I strip at 0.50 metre below ground as strip earth electrode, including connection/ terminating with G.I. nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of G.I. nut bolt & spring washer spaced at 50mm)
Supplying and laying 6 SWG G.I. wire at 0.50 meter below ground level for conductor earth electrode, including connection/ termination with GI thimble etc. as required.
Input voltage 340V - 460V Supply, testing & commissioning of following, 3 phase natural oil cooled, rolling contact / linear type automatic voltage controller suitable for outdoor/indoor installation with automatic voltage correction rate of 8-10V/sec, consisting of regulator, Automatic control gear complete with all fittings such as lifting lugs, rating plate, earthing terminals, cable box etc. complete as required The Servo-voltage stabilizer shall have following provisions.
RATING - 800KVA
Output voltage 400V + 1%, 3 PH 50Hz
Efficiency (approx.) 99%
Ambient Temp. – 10 Deg. C to 50 Deg. C.
Cooling - ONAN
Suitable for 100% continuous cycle
Suitable for unbalanced load & balanced incoming supply.
Protection & Indications
MCCB at output terminal
Overload & short circuit protection.
Analog / Digital type voltmeter/phase with protection fuse & ON/OFF switch.
Analog/ Digital type Ammeter/ phase & ON/OFF switch.
Auto / Manual control arrangements.
Cable boxes at both ends.
SAINKO SYSTEMS (BID ID -377670)
stage.html
html • 0.03 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .