Loading…
Tenderkart now works inside Claude and ChatGPT: search and analyse tenders right from your chat
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹90.6 LAccepted-AOC | L1 | Accepted-AOC LOWEST | |
| 2 | L2₹95.9 L+₹5.0 L (5.49%)Rejected-Finance | L2 | Rejected-Finance NOT LOWEST | |
| 3 | L3₹96.3 L+₹5.4 L (5.95%)Rejected-Finance NAYA BASS MAHAMANDIR JODHPUR RAJASTHAN 342006 | JODHPUR | JODHPUR | RAJASTHAN | 342006 | L3 | Rejected-Finance NOT LOWEST | |
| 4 | L4₹97.8 L+₹7.0 L (7.65%)Rejected-Finance 74 AJANTA COMMERCIAL CENTRE ASHRAM ROAD AHMEDABAD 380014 | AHMEDABAD | AHMEDABAD | GUJARAT | 380014 | L4 | Rejected-Finance NOT LOWEST | |
| 5 | L5₹1.0 Cr+₹12.1 L (13.3%)Rejected-Finance 164 HIRANI NAGAR OPP SIDDHI VINAYAK TEMPLE MADHAPAR KUTCH 370 020 | KACHCHH | GUJARAT | 370020 | L5 | Rejected-Finance NOT LOWEST |
Tender Value
₹98.2 L
EMD Value
₹1.7 L
Closing Date
3 Feb 2022, 6:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
CWE (AF) BHUJ
CWE (AF) BHUJ KHAVDA ROAD BHUJ KACHCHH PIN 370001
PROVN OF HT RING MAIN SYSTEM AT AF STATION NALIYA
2022_MES_499790_1
85234/E8
Open Tender
Civil Works
Item Rate
180 days
NALIYA
Please refer Tender documents.
7 documents required · 7 mandatory
₹1,000
Yes
GE (AF) NALIYA
₹1.7 L
Yes
6 Apr 2022
6 Jan 2022
7 Feb 2022
6 Jan 2022
3 Feb 2022
20 Jan 2022
60 days
Amount
Supply, installation, testing and commissioning of 11 KV, 630 Amps, Extensible Outdoor Fixed Type (IP54), RMU (Ring main unit) comprising of 03 Nos. 630 Amps motorised fixed-type Vacuum Circuit Breaker, inside robotically welded stainless steel 304 (Non Ferrite Non Magnetic Grade) tank having min. thickness 3+0.5 mm with IP 67 Degree of Protection and enhanced BIL of 125kVp internally to manage voltage surges and Air Insulated Metering Module of Class - 1. RMU should be provided with internal bus bars, as well as earthing bus bars of electrolytic grade copper, padlock provisions & complete with all accessories. The RMU shall be type tested for Internal arc test of 21kA/1 sec as per IEC62271-200. RMU shall have on-site-repairability features such as site replaceable bushing/coupling/mechanism and gas refilling at site. The earthing busbar shall be provided inside each cable compartment for solid earthing of Cable shields. The outer hinged main door should cover entire front of switchgear including cable doors for providing fail-safe protection. The unit shall include the following with all necessary standard fitting as required at site (S/S No 24, 29 & 31)
All as per item No.1 above herein before but having 4 Nos of VCBs 11 KV including all accessories of rating 630Amps (For S/S No 26, 33(PH), 28)
All as per item No 1 above hereinbefore but having 5 Nos of VCBs 11 KV including all accessories of rating 630Amps (For S/S No 20)
Supply, laying and testing cable XLPE Insulated , screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 11000 Volts grade with stranded aluminum conductor of size 95Sq mm 3 core including M&L for sand cushioning to UG cable in trenches with screened river washed sand cushioning in two layers i.e. 8cm below and 15cm above the cable (gently punned down by hand to depth of 10cm) conforming to IS 1255-1983 and also provide un-reinforced, precast concrete cable cover, class HV, Type 1, with peak, size 300 mm x 180 mm x 40 mm confirming to IS 5820 (M20 grade concrete) each other with gap between adjacent slab not exceeding 10mm over underground cable for protection complete all as specified and directed by EIC.
Supply, jointing and testing indoor type cable termination (heat shrinkable) suitable for 3 core, 11 KV/ underground electric cable, XLPE cable of size 95 sqmm complete all as Specified and directed.
Supply, jointing and testing outdoor type cable termination (heat shrinkable) suitable for 3 core, 11 KV / underground electric cable, XLPE cable of size 95 sqmm complete all as Specified and directed.
Supply, jointing and testing straight through type cable termination (heat shrinkable) suitable for 3 core, 11 KV / underground electric cable, XLPE cable of size 95 sqmm complete all as Specified and directed.
Supply and laying galvanised steel water tubing, light grade, IS-1239 marked with all fittings IS marked and laid in trenches under roads, through drains, fixed to poles/walls with required size flat iron clamp bolts, nuts and washers, for cable protection of 100 mm dia, including taking out old/existing pipes, complete all as specified and directed.
Cutting road/ pavement/ hard standing for laying of cable protection GI pipe including returning filling and making good disturbed surface by using PCC 1:3:6 type C2 complete all as specified and directed.
Supply fabricate, testing and commissioning of factory made HT outdoor distribution panel board double door of size 1000mmx1000mmx600mm including locking arrangement cubical type dust proof, weather proof, vermin proof aesthetical designed, IP 54 degree of ingress protection, CPRI approved, fabricated from 3mm thick CRCA sheet with front and rear opening including bus bar chamber, including bus bar chamber, 3 strips of copper bus bar of 400 Amps current carrying capacity insulated with colour sleeves, porcelain/ epoxy insulators, rail channels, cable entry, danger notice plate of 11000Volt made out of 14 gauge MS sheet over angle iron frame of size 50x50x6mm and 60cm grouted in ground and 60cm above GL including necessary excavation, foundation, PCC etc complete duly powder coated of approved colour all as specified and directed.
M&L for earthing complete with copper earth plate electrode 600mmx600mmx 3.15mm thick, thick buried directly in ground vertically to a depth not less than 2.25 mtr deep below GL with top edge of the plate not less than 1.5 mtr below normal GL and connected to earth plate . Earth plate surrounded by 15 cm thick packed layers of charcoal dust and common salt all around the earth plate and connected to earth lead of copper strip 20x3 mm by means of bolts, nuts, check nuts and washers of GI or steel and thimbles and other end of the earth wire connected to DB and protected by 50mm dia galvanized iron or steel pipe light grade and 20mm dia water pipe GI medium grade with funnel and wire mesh, including all necessary excavation and earth work PCC chamber in cement concrete 1:3:6 type C-2 and RCC cover and all as shown in electrical plate No 3 of MES schedule Pt I of 2009 and also including making test point for testing of earthing made out of gun metal or phosphorous bronze size 75x75x25 mm complete. Note : 1. Charcoal dust and common salt shall be filled in layers of 15 centimeters all around the earth plate. 2. Copper strip will be connected to test point through plinth protection necessary cost of repair to plinth protection/hard standing , brazing and welding deemed to be included in the item rate. 3. Copper strip beyond 7.5 RM will be measured and paid separately). 4. On completion the earth resistance test to be carried out. If desired value of resistance not obtained, the earthing will be re-done at no extra cost.
Danger notice plate of 1.6mm thick mild steel sheet, vitreous enameled white, with letters, figures and conventional skull and bones in signal red colour and fixed with M.S. clamps, bolts and nuts of approved size, for HT, 25x20cm size
Excavation in trenches not exceeding 1.5m wide and not exceeding 1.5m in depth and getting out in soft/loose soil, for under ground electric cable, pipes etc. all as directed and specified. (Note : Authorised width & depth shall only be excavated, measured and paid as specified in clause 3.2.3 of SSR pt II and 19.7.4.1 of SSR pt I)
Returning, filling-in including, spreading, watering and well ramming in layers not exc 25 cm thick each, in soft /loose soil complete all as specified
Removing excavated surplus soil to a distance not exceeding 50 m and depositing where directed at a level not exceeding 1.5 m above the starting point complete all as specified & directed.
Shifting of RMUs from one place to another place by disconnecting its all electrical HT connections transporting though their own veh and loading/ unloading etc. Note- The cost of the transporting veh, labour and crane is deemed to be included in unit rate.
Taking out HT cable of any size by proper disconnection from old panel and re-laying and connecting up the same serviceable cable for route diversion if any. Note: Excavation earthwork, cable covers, sand cushioning and GI protection pipe shall be measured and paid separately under relevant item.
Dismantling air break gang operated switches vertical/horizontal mounted including insulators and operating mechanism for repair/ replacement of broken/ worn out components and insulators etc.
Dismantling Cross Arms any size and type.
Dismantling concrete poles/ struts, any size and transporting to MES stores yard for reuse or remove from site if not suitable for reuse. Note : Serviceability of poles shall be decided by Engr-in-Charge
Dismantling stay assembly complete including demolition of concrete etc
JAZZCON ENGINEERS PVT LTD
Anil Builders
Electricals India
Pelectricals
M/s SK Traders
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .