Loading…
Loading…
Tender ID
Tender Value
₹1.3 L
EMD Value
₹3,241
Closing Date
5 Feb 2026, 6:00 pmClosed
Assistant Executive Engineer
Assistant Executive Engineer, PWD electricalsubdivision kasaragod
UPS Installation
2025_PWD_822211_3
PWD/BLDG/TR/20734/2024_6_1_1/1
Open Tender
Electrical Works
Percentage
Kasaragod
Please refer Tender documents.
11 documents required · 11 mandatory
₹555
₹3,241
Yes
30 Jan 2026
30 Jan 2026
9 Feb 2026
30 Jan 2026
5 Feb 2026
30 Jan 2026
UPS Installation
OD180844/2024-2025: Supply Installation and testing and commissioning of 5kVA Online UPS . a) 1 Ph to1 Ph, b) Input - 160-260 V, pf : 0.99 @ full load, c) Output 230V/50Hz , pf : >.95 d) THD : ? 10% e) Overall Efficiency : 85% h)Ambient Temperature : 0-40°C i) Generator Compatibility available. j) Pure sine wave. k) Battery over charge & under charge cut off. l) Bypass arrangement. m) EN/IEC 620401 for General Safety compatibility n) EN/IEC 620402 for Electromagnetic Compatibility. o) EN/IEC 620403 for Performance o) EN/IEC 620404 or equal for Environmental Compatibility p) LED + LCD Display q) Approved UPS make Hykon/Zenon/Numeric/Equivalent . And 4 nos of 100 AH tubular battery with rack . s)Three year warranty for UPS and Battery.
2.3.2:Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 volts, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) 8 way, Double door
2.12.1:Supplying and fixing following rating, double pole, 240 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.40 amps
2.10.2:Supplying and fixing 5A to 32 A rating, 240/415 volts, 10 kA, ""C"" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. Single pole and netural
OD181411/2024-2025:Type 1+2 Photovoltaic Surge Protection Device - High Operating Voltage : 1200 V DC - Safe Operation : Significant physical separation guarantees insulation between polarities even for high DC voltages - Hight Discharge Current : Imax 60 kA for 4-module SPD (Iimp 12.5 kA)Imax 40 kA for 3-module SPD (Iimp 6 kA)
2.10.1:Supplying and fixing 5A to 32 A rating, 240/415 volts, 10 kA, ""C"" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. Single pole
1.17.30:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 x 6 sq. mm
1.17.21:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 x 4 sq. mm
1.21.1:Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required.20 mm
OD180846/2024-2025:20 mm Corrugated PVC flexible conduit
OD178500/2024-2025:Supply and providing 12x3mm brass nut and bolt etc. as required
OD180953/2024-2025:Charges for dismantling the existing EI
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.05 MB
BOQ_1398633.xls
BOQ • 0.32 MB
viewsbd.pdf
Tender Documents • 1.63 MB
viewnit.pdf
Tender Documents • 0.02 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .