| 1 | L1₹23 LAccepted-AOC HAVELI FALIYA NALIYA KUTCH 370 655 | KACHCHH | GUJARAT | 370655 | L1 | Accepted-AOC Lowest Bidder | |
| 2 | L-2₹24.7 L+₹1.7 L (7.60%)Rejected-Finance NAYA BASS MAHAMANDIR JODHPUR RAJASTHAN 342006 | JODHPUR | JODHPUR | RAJASTHAN | 342006 | L-2 | Rejected-Finance Other than lowest bidder | |
| 3 | Rejected-Technical PLOT NO 14 SHIV COLONY KATI GHATI RAJGARH ROAD ALWER RAJ | ALWAR | ALWAR | RAJASTHAN | - | Rejected-Technical Eligible category for the subject work is c(i) and c(vi) but the firm is enlisted in only c(i) category and the firm did not upload/submit hard copy of past experience in similar nature of work, hence not recommended for opening of Financial Bid. |
Tender Value
₹21.2 L
EMD Value
₹42,320
Closing Date
26 Nov 2024, 6:00 pmClosed
GE(AF) Naliya No. 1
GE AIR FORCE STATION NALIYA NO 01
SPECIAL REPAIR TO FIRE ALARM SYSTEM INSTALLED IN VARIOUS LOCATIONS, PROVN OF AIR CONDITIONERS FOR SQN COMPLEX AND PROVN OF INVERTER SPLIT AIR CONDITIONERS AT CERTAIN LOCATION AT 22 AU AND AF STATION NALIYA
2024_MES_682029_1
8012/E8
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
Naliya
Please refer Tender documents.
7 documents required · 7 mandatory
₹500
GE(AF) Naliya No. 1
₹42,320
Yes
31 Jan 2025
30 Oct 2024
29 Nov 2024
30 Oct 2024
26 Nov 2024
12 Nov 2024
Amount
Supply & fix in replacement of Intelligent Addressable fire alarm control panel with one Loop complying with EN 54 standard & LPCB approved and battery back up with the specifications as appended below:- Loop Capacity ( 99 Detectors +99 Devices) Networking up to 16 loops (Combination of 1; 2 & 4 Loops) 6x40 characters, blue liquid crystal display with backlight illumination, Configuration by keypad and PC, 160 Fire Zones, Fire, Fault and Auxiliary relays, Loop-Battery calculator for reliable system design, 7 day timer, Onboard diagnostic, EN54-2, EN54- 4, LPCB approved, Optional: 40, 80 or 160 zone alarm LEDs complete all as specified and directed. Make: Honeywell/Gulf Security Technologies
Supply & fix in replacement of electronically addressable intelligent combination of heat and photo electric smoke Multi detector with mounting base complying with EN 54 standard and LPCB approved with the specifications as appended below :- (a) Power- 24V, ≤ 0.8 mA (Standby Current) ≤5.0mA (Alarm Current). (b) Class A2R. (c) Indicator- Red Flashes in normal and illuminates in alarm. (d) Ingress Protection IP-22 & Material-ABS. Make: Honeywell/Gulf Security Technologies.
Supply & fix in replacement of electronically addressable intelligent sounder cum strobe with mounting base, continuous normal operation for atleast 15 minutes with sound level 65db- 120db measured at 1.5m with sound output variation +5db complying with the specifications as appended below :- (a) Power-12/ 24 V DC or 110 /220V AC, 1Ph, AC, 50Hz. (b) Range-1000 m. (c) Visual indication. Make: Honeywell/Gulf Security Technologies.
Tracing, fixing/replacing and aligning existing 2 core 1 Sqmm cable along with metal support wire from Armory section to Station HQ. Pipeing the cable for protection near Station HQ complex, mounting angles at required places near HQ complex to avoid breakage in future complete all as specified and directed.
Supply & fix intelligent Addressable Type fire alarm control panel with one Loop complying with EN 54 standard & LPCB approved and battery back up with the specifications as appended below:- (a) Power- AC 230V, 50Hz, 0.5 A. (b) 235 Devices including detectors, minimum 2 loop. (c) Relay- Fire Alarm/ F.P.E/ Fault/ Sounder. (d) configurable for PC Port- RS-232 interface. (e) LCD Display and with battery backup of 12 Hours in non alaram condition and 4 Minutes in alarm condition (Battery type 2 X 12V 7AH, sealed type. Make of Battery- Exide/Amron/Solance. Make of panel: Gulf Security (GST) /Siemens/Honeywell.
Supply & fix conventional Type fire alarm control panel with Battery back up and with the specifications as appended below:- (a) Power- AC 230V, 50Hz, 0.5 A. (b) Upto 99 Devices including detectors, minimum 2 Zones. (c) Relay- Fire Alarm/ F.P.E/ Fault/ Sounder. (d) LCD Display and with battery backup of 12 Hours in non alaram condition and 4 Minutes in alarm condition (Battery type 2 X 12V 4AH, sealed type. Make of Battery- Exide/Amron/Solance. Make of panel: Palex/Agni/ Ravel.
Supply & fix electronically addressable intelligent combination of heat and photo electric smoke Multi detector with mounting base complying with EN 54 standard and LPCB approved with the specifications as appended below:- (a) Power- 24V, ≤ 0.8 mA (Standby Current) ≤5.0mA (Alarm Current) (b) Class A2R, (c) Indicator- Red Flashes in normal and illuminates in alarm, (d) Ingress Protection IP-22 & Material-ABS Make: Siemens/Honeywell/GST.
Supply & fix conventional type photo electric Smoke detector with mounting base & with the specifications as appended below:- (a) Power- 24V, ≤ 0.8 mA (Standby Current) ≤5.0mA (Alarm Current) (c) Indicator- Red Flashes in normal and illuminates in alarm, (d) Material-ABS Make: Palex/Agni/ Ravel..
Supply & Fix electronically addressable intelligent Sounder Cum strobe with mounting base, continuous normal operation for atleast 50 minutes with sound level 65db-120db measured at 1.5m with sound output variation +5db complying with the specifications as appended below:- (a) Power-12/ 24 V DC or 110 /220V AC, 1Ph, AC, 50Hz (b) Range-1000 m (c) visual indication. Make: Siemens/Honeywell/GST
Supply & Fix Sounder with mounting base, continuous normal operation for atleast 30 minutes with sound level 65db- 120db measured at 1.5m with sound output variation +5db complying with the specifications as appended below:- a) Power-12/ 24 V DC or 110 /220V AC, 1Ph, AC, 50Hz b) Range-1000 m c) Without visual indication. Make: Palex/Agni/ Ravel.
Supply & fix intelligent loop isolator with mounting base complying with EN 54 standard and LPCB approved with the specifications as appended below:- a) Power- 24V, ≤ 3 mA (Standby Current) ≤15mA (Action Current) b) Class A , c) Initiating Mode- Yellow flashes when polling, illuminates in action, d) Ingress Protection IP-30 & Material-ABS Make: GST/Siemens/Honeywell.
Supply & fix electronically addressable intelligent resettable type manual call point with mounting base complying with EN 54 standard and LPCB approved with the specifications as appended below:- (a) Power- 24V, ≤ 0.6 mA (Standby Current) ≤1.8mA (Alarm Current) (b) Class A , (c) Initiating Mode- Pressing the action plate manually Resuming Mode-Manually Resumed by a special Key, (d) Ingress Protection IP-43 & Material-ABS Make: GST/Siemens/Honeywell.
Supply & fix manual call point with mounting base with the specifications as appended below:- (a) Power- 24V, ≤ 0.6 mA (Standby Current) ≤1.8mA (Alarm Current) (b) Class A. (c) Initiating Mode- Pressing the action plate/button manually. Resuming Mode Manually Resumed by a special Key/reset button. (d) Material-ABS. Make: Palex/Agni/ Ravel
Supply & fix programming card for programming of detectors and other devices in FACP , Comm.Interface: USB interface Comm.Distance <15m <5m , Baud Rate 2400bps Ambient Temperature 0℃ ~+40℃ , Relative Humidity ≤95%,non condensing complete all as per specified and directed. Make: GST/Siemens/Honeywell.
Supply & fix in replacement IO module card of Remote Terminal Unit panel with FRC cable for siren system panel complete all as per specified and directed. Make: CIMCON/SIEMENS/ABB
Supply & fix in replacement Digital input DI card of Remote Terminal Unit panel with FRC cables and its connecting accessories for siren system panel complete all as specified and directed Make: CIMCON/SIEMENS/ABB
Supply & fix in replacement Digital output DO card of Remote Terminal Unit panel with FRC cables and its connecting accessories for siren system panel complete all as specified and directed. Make: CIMCON/SIEMENS/ABB
Supply, installation, testing & commissioning CPU and Power Supply Card of Existing 2 loop conventional fire alarm control panel complying with EN 54 standard complete as all as per specified and directed.
Supply, installation, testing & commissioning conventional type Flame Detector with mounting base complying with EN 54 standard and LPCB approved with the specifications as appended below:- (a) Power- 24V, ≤ 0.8 mA (Standby Current) ≤5.0mA (Alarm Current) (b) Class A2R , (c) Indicator- Red Flashes in normal and illuminates in alarm, (d) Ingress Protection IP-22 & Material-ABS
Supply, installation, testing & commissioning electronically addressable intelligent resettable type MCP (manual call point) with mounting base complying with EN 54 standard with the specifications as appended below:- (a) Power- 24V, ≤ 0.6 mA (Standby Current) ≤1.8mA (Alarm Current) (b) Class A , (c) Initiating Mode- Pressing the action plate manually Resuming Mode-Manually Resumed by a special Key, (d) Ingress Protection IP-43 & Material-ABS
Supply and install 1.5 TR hi wall split units indoor/outdoor complete with cordless remote control unit and with in built air ioniser and Plasma filter for better indoor air quality with minimum 5 star rating and EER 3.2.of capacity as shown complete all as specified and directed.
Supply and install Electronic wall mounting type stablizer suitable for AC upto 1.5 TR Voltage stabilizer for automatic operation, single phase naturally air cooled indoor type and designed for input variation between 170 volt to 250 volt with output voltage stabilized at 230 volt with accuracy of ±2.5% and of capacity 4.0 KVA
Supply and fix in replacement industrial plug and socket with single pole and neutral enclosures with a two pin and earth plug and socket complete with one single pole MCB 20 Amps capacity complete all as specified and directed.
Supply and fixing/drawing wiring for Circuit / Submain wiring with PVC casing caping of suitable size inclusive of all tees, bends, elbows, reducers bell mouth tube ends and fixing accessories including all fixtures /fittings fixed on wall/ceiling along with earth wire with the following size of FRLS PVC insulated copper conductor, single core cable in surface/ recessed as required of 2 x 4.0 sqmm and 1 x 4.0 sqmm as earth wire complete all as specified and directed.
Supply & fix in replacement sub main wiring drawing through PVC casing caping with two single core 10 sq mm and one run of 10 sq mm as earth wire of stranded copper conductor PVC insulated and unsheathed cable of 1100 volts grade all as directed
Supply & fix in replacment of MCB DB SPN 8 ways single door with 240 Volt, 200 amps rated bus bar with all accessories fixed in the wall including taking old DBs any type and cap and making good and match with the existing surface of wall complete all as specified and directed.
Supply & fix in replacment of MCB DB SPN 4 ways single door with 240 Volt, 200 amps rated bus bar with all accessories fixed in the wall including taking old DBs any type and cap and making good and match with the existing surface of wall complete all as specified and directed.
Supply & fix MCB’s single pole, 6 to 32 Amps, 230 volts with ‘C’ curve, fixed in sheet metal board complete including connecting complete all as specified and directed.
Supply & fix MCB’s single pole & neutral, 63 Amps, 230 volts with ‘C’ curve, fixed in sheet metal board complete including connecting complete all as specified and directed.
Material and labour for earthing complete with GI earth plate electrode 60×60cm.× 5 mm thick, burieddirectly in ground (earth pit not less than 2.25 metres deep below groundlevel) with top edge of the plate not less'than 1.5 metres below normal ground level, connected togalvanised earth lead wire 4.0mm dia by means of bolts, nuts, check nuts and washers of galvanised iron or steel including provn of GI protection pipe light grade of 25mm bore and connected to earth wire earthing test point all as shown in electrical plate No.5 of SSR Part-I 2009 and as specified or indicated and testing on completion including necessary excavation & earthwork in any type of soil, PCC (1:3:6) type C1 chamber, precast slab 50mm thick in cement concrete (1:2:4)type B1 (reinforced with welded steel wire fabric (XPM) of weight not less than 4kg/sqm) with frame, funnel with watering pipe of 15mm bore medium grade, wire mesh and lugs, test point including salt, Coal etc. complete as specified or indicated including testing on complete all as specified and directed.
Supply and fix in replacement of Digitqa Automaticl Dual sequence timer opereted on 240 V,50 Hz, Rated 20 Amp, Micro controlled based technology use for ON/OF load sequentially for AC complete all as specified and as directed. Model no DAT-W or equivalant
Material and labour for point wiring complete with 1.5 Sqmm PVC insulated and unsheathed cable single core multi stranded copper conductor, 1100 volts grade drawn through and including PVC casing / capping/ concealed, medium grade of any size with all accessories like bends, junction boxes etc including copper earth continuity wire of PVC insulated of size 1.50 Sqmm and connected to common earth dolly with all accessories including sunken type pressed steel terminal boxes 3mm thick hylam/ bakelite sheet, for One 3 pin socket out let 5 Amp on independent board complete all as specified and as directed.
Supply & fix in replacement switch socket combination 3 pin 5 / 6 Amp flush type multipurpose complete all as specified and as directed.
Material and labour for Earthing complete with Copper earth plate electrode 600x600x3.15 mm thick buried directly in ground (earth pit not less than 2.25 m deep below normal ground level) with top edge of the plate not less than 1.5 m below normal ground level connected to copper earth strip of 20 x 3 mm (up to 7.5m in length from earth plate) by means of bolts and nuts checknuts and washers of galvanized iron or steel all as specified and shwon in electrical plate no 3 of SSR part 1 including Charcoal, Rock salt, necessary excavation and earth work in any type of soil PCC 1:3:6 type C1 chamber with RCC 1:2:4 type B1 40 mm thick cover with MS bar 8mm dia 150mm c/c reingorcement, watering funnel 32 mm dia light grade for protection of earth electrode 20 mm dia for watering all as speicified and directed and tested on completion complete all as specified and as directed. Note : - The unit rate quoted shall deemed to have included for GI protection pipe, Copper earth strip up to 7.5 mtr, GI water pipe, wire mesh , funnel , excavation, RCC pit cover.
Anil Builders (BID ID -3172338)
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .