Loading…
Loading…
| # | Company | Status |
|---|---|---|
| 1 | Admitted-Finance DOOR NO 44 19 10 RAILWAY NEW COLONY BEHIND SIVALAYAM VISAKHAPATNAM AP 530016 | VISAKHAPATANAM | ANDHRA PRADESH | 530016 | Admitted-Finance |
| 2 | Admitted-Finance 8 51 PLOT NO 6 LIC COLONY SUJATA NAGAR PENDURTHY MANDAL VISAKHAPATNAM 530042 AP | 530042 | Admitted-Finance |
| 3 | Admitted-Finance D NO 35 14 13 1 R P PETA KANCHARAPALEM VISAKHAPATNAM 530 008 | VISAKHAPATANAM | ANDHRA PRADESH | 530008 | Admitted-Finance |
| 4 | Admitted-Finance 21 9TH MAIN 4TH CROSS GOWDAKEHOLA BAGALAKUNTE NAGASANDRA POST BANGALORE 560073 | BENGALURU URBAN | KARNATAKA | 560073 | Admitted-Finance |
| 5 | Admitted-Finance D NO 9 947 66 DOCTORS COLONY SHIVAJI PLEM VISAKHAPATNAM 530017 | VISAKHAPATANAM | ANDHRA PRADESH | 530017 | Admitted-Finance |
Tender Value
Refer Docs
EMD Value
₹13,800
Closing Date
16 Mar 2022, 6:00 pmClosed
Arnab Dey
GE(P) Navy Kalinga
Repairs/Maintenance to 11KVA VCBs, Battery Bank, Battery Charger at TSS Sub Station In Tech Area at INS Kalinga Visakhapatnam
2022_MES_511706_1
GE(P)/N/K/JOB/29 of 2021-22
Open Tender
Miscellaneous Services
Item Rate
15 days
GE(P) Navy Kalinga
Repairs/Maintenance to 11KVA VCBs, Battery Bank, Battery Charger at TSS Sub Station In Tech Area at INS Kalinga Visakhapatnam
2 documents required · 2 mandatory
₹500
Yes
₹13,800
Yes
19 Mar 2022
3 Mar 2022
17 Mar 2022
4 Mar 2022
16 Mar 2022
4 Mar 2022
Amount
Supply and fixing of 11kV CT, epoxy cast, current rating primary current 25-50 A, single/ double ratio, double core (Protection core-5P10 & Metering core- Class 1.0), 25 KA for 1 sec , with minimum 15VA Burden. Make: Areva/Schneider
Supply and replace/repair 110v DC/100Ah/20A battery charger along with DCDB , made of carbon steel duly powder coated finish,contineously welded and ground smooth, concealed door hinges, locking mechanism with key/padlocking handle, oil resistant gasket including taking down old rusted unserviceable battery caharger complete all as specified and directed by Engr-in-Charge. Make: AMARA RAJA / EXIDE / Soft Power Controls
Supply and replace/repair 12V, DC, VRLA cell and arrange properly with connecting leads inside battery rack suitable for control DC circuit of 11 KV VCBs and after assembling required voltage is 108V / 100AH including taking down old complete all as specified and directed by Engineer-in-Charge. Make: AMARA RAJA / EXIDE / AMARON
supply and fix including dismantling taking out existing unserviceable Busbar Supporting insulator for 11kV VCB panel of capacity 630 Amps all as specified and directed by Engineer-in-charge. Make -Areva/Schneider
supply and fix including dismantling taking out existing unserviceable Busbar Spout for 11kV VCB panel of capacity 630 Amps all as specified and directed by Engineer-in-charge. Make -Areva/Schneider
S&F multifunctional meter with LED display,accuracy class-1,including dismantling taking down unserviceable one and connection, programming, testing complete all as specified and directed. Make- Elmeasure , L&T , Schneider
Supply and fixing of Thermostat and space heater in place of unserviceable damaged space heater, 230V AC supply inside 11 KV HT VCB, cable chamber including dismantling & necessary connection, testing complete all as specified and directed.
Supply and fix cable jointing kit for 11 KV grade cable for indoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured Al conductor cable of size 185 sq. mm. Make : 3M/Denson/Raychem
Maintenance, servicing, Buffing/cleaning, Electroplating of copper Busbar in busbar chamber of each VCB panel including connecting bus bar from CT to main Bus bar & spout. servicing of support insulator by clean cloth and hot air blower/vacuum cleaner, checking for any loose contact, refixing of all nuts & bolts by Stainless Steel , refixing all covers , replacement of defective bus spout complete all as specified and directed Note :- Required new components will be measured and paid separately under relevant items.
M&L for maintenance/servicing of PT unit 11kV/110V by disconnecting and taking out from panel mounted position, checking & cleaning of fixed and moving contact points, cleaning/ decarbonising of bus bar connections, resin cast PTs using hot blower, CTC solution, applying backlot (Red) solution to the epoxy PT body, tightening of all nuts, bolts, washers, and refixing the same PT to original position, testing complete all as specified and directed.
SRI MAHALAKSHMI CONSTRUCTIONS
LEOENTERPRISES
M/S CHANDRA ENGINEERS AND CONTRACTORS
SRIVALLI ENGINEERS
ANJALI ENTERPRISES
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .