Loading…
Loading…
Eligibility, documents, scope, Go/No-Go checksEligibility, required documents, scope of work and Go/No-Go checks for this tender, in one click.
Tender Value
₹4.2 L
EMD Value
₹10,591
Closing Date
22 Oct 2026, 6:00 pm3d left
Eligibility, documents, scope, Go/No-Go checksEligibility, required documents, scope of work and Go/No-Go checks for this tender, in one click.
AEE
PWD Electrical Sub Division Tvpm
GENERAL-Guest House-Re-insulation of Chiller pipe line at Ground floor at Guest House, Thycaud TVPM-Maintenance work-Electrical AC Work
2026_PWD_880152_1
ESDT/ET-137/2026-27
Open Tender
Electrical Works
Percentage
120 days
PWD Electrical Sub Division Tvpm
please refer tender documents
6 documents required · 6 mandatory
₹935
₹10,591
15 Oct 2026
15 Oct 2026
24 Oct 2026
15 Oct 2026
22 Oct 2026
15 Oct 2026
This is a percentage-rate BOQ. The schedule below shows estimated quantities and rates. Bidders quote a single percentage above or below the total estimated cost.
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1Maintenanace | |||||
| 1.001 | 16.1.8:Supplying, laying /fixing, testing and commissioning of following nominal size of chilled water piping inside the building (with necessary clamps, vibration isolators and fittings but excluding valves, strainers, gauges etc.) duly insulated with 80 kg/cum density resin bonded fiber glass pipe section insulation covered with a layer of 120gm/sqm polythene sheet (vapour barrier) and finally applying 0.63 mm aluminium sheet cladding complete with type 3, grade 1 roofing feltstrip (as per IS: 1322 as amended up to date) at joints and repairing of damage to building etc. as per specifications and as required.
Note: The Pipes of sizes 150 mm & below shall be M.S. 'C' class as per IS: 1239 and pipes size above 150mm shall be welded black steel pipe heavy class as per IS : 3589,from minimum 6.35 mm thick M.S.Sheet for pipes upto 350 mm dia. and from minimum 7 mm thick MS sheet for pipes of 400 mm dia and above.Chilled water piping of nominal size - 100mm dia. (50mm thick fiber glass insulation) | 14 | metre | 4,127.66 | ₹57,787.24 |
| 1.002 | 16.1.9:Supplying, laying /fixing, testing and commissioning of following nominal size of chilled water piping inside the building (with necessary clamps, vibration isolators and fittings but excluding valves, strainers, gauges etc.) duly insulated with 80 kg/cum density resin bonded fiber glass pipe section insulation covered with a layer of 120gm/sqm polythene sheet (vapour barrier) and finally applying 0.63 mm aluminium sheet cladding complete with type 3, grade 1 roofing feltstrip (as per IS: 1322 as amended up to date) at joints and repairing of damage to building etc. as per specifications and as required.
Note: The Pipes of sizes 150 mm & below shall be M.S. 'C' class as per IS: 1239 and pipes size above 150mm shall be welded black steel pipe heavy class as per IS : 3589,from minimum 6.35 mm thick M.S.Sheet for pipes upto 350 mm dia. and from minimum 7 mm thick MS sheet for pipes of 400 mm dia and above.Chilled water piping of nominal size - 80mm dia. (50mm thick fiber glass insulation) | 14 | metre | 3,377.39 | ₹47,283.46 |
| 1.003 | 16.1.10:Supplying, laying /fixing, testing and commissioning of following nominal size of chilled water piping inside the building (with necessary clamps, vibration isolators and fittings but excluding valves, strainers, gauges etc.) duly insulated with 80 kg/cum density resin bonded fiber glass pipe section insulation covered with a layer of 120gm/sqm polythene sheet (vapour barrier) and finally applying 0.63 mm aluminium sheet cladding complete with type 3, grade 1 roofing feltstrip (as per IS: 1322 as amended up to date) at joints and repairing of damage to building etc. as per specifications and as required.
Note: The Pipes of sizes 150 mm & below shall be M.S. 'C' class as per IS: 1239 and pipes size above 150mm shall be welded black steel pipe heavy class as per IS : 3589,from minimum 6.35 mm thick M.S.Sheet for pipes upto 350 mm dia. and from minimum 7 mm thick MS sheet for pipes of 400 mm dia and above.Chilled water piping of nominal size - 65mm dia. (50mm thick fiber glass insulation) | 14 | metre | 2,862.51 | ₹40,075.14 |
| 1.004 | 16.1.11:Supplying, laying /fixing, testing and commissioning of following nominal size of chilled water piping inside the building (with necessary clamps, vibration isolators and fittings but excluding valves, strainers, gauges etc.) duly insulated with 80 kg/cum density resin bonded fiber glass pipe section insulation covered with a layer of 120gm/sqm polythene sheet (vapour barrier) and finally applying 0.63 mm aluminium sheet cladding complete with type 3, grade 1 roofing feltstrip (as per IS: 1322 as amended up to date) at joints and repairing of damage to building etc. as per specifications and as required.
Note: The Pipes of sizes 150 mm & below shall be M.S. 'C' class as per IS: 1239 and pipes size above 150mm shall be welded black steel pipe heavy class as per IS : 3589,from minimum 6.35 mm thick M.S.Sheet for pipes upto 350 mm dia. and from minimum 7 mm thick MS sheet for pipes of 400 mm dia and above.Chilled water piping of nominal size - 50mm dia. (50mm thick fiber glass insulation) | 14 | metre | 2,376.66 | ₹33,273.24 |
| 1.005 | 16.1.14:Supplying, laying /fixing, testing and commissioning of following nominal size of chilled water piping inside the building (with necessary clamps, vibration isolators and fittings but excluding valves, strainers, gauges etc.) duly insulated with 80 kg/cum density resin bonded fiber glass pipe section insulation covered with a layer of 120gm/sqm polythene sheet (vapour barrier) and finally applying 0.63 mm aluminium sheet cladding complete with type 3, grade 1 roofing feltstrip (as per IS: 1322 as amended up to date) at joints and repairing of damage to building etc. as per specifications and as required.
Note: The Pipes of sizes 150 mm & below shall be M.S. 'C' class as per IS: 1239 and pipes size above 150mm shall be welded black steel pipe heavy class as per IS : 3589,from minimum 6.35 mm thick M.S.Sheet for pipes upto 350 mm dia. and from minimum 7 mm thick MS sheet for pipes of 400 mm dia and above.Chilled water piping of nominal size - 25mm dia. (50mm thick fiber glass insulation) | 80 | metre | 1,593.73 | ₹1,27,498.4 |
| 1.006 | 90.14.5:Supply and fabrication conveyance and installation of angle iron frame work for wall mounting panel board | 50 | kg | 179.02 | ₹8,951 |
| 1.007 | OD148684/2026-2027:Supply, fabrication, Installation and testing of flexible connections constructed flexible double canvas sleeve in accordance with approved shop drawings and as per the specifications for each FCU unit. | 9 | each | 2,323 | ₹20,907 |
| 1.008 | 90.6.5.2:Supply and drawing the following sizes of multi-core PVC insulated & FRLS PVC sheathed 650/1100 V grade copper conductor round flexible cables conforming to IS 694 part I 1960 in the existing surface / recess conduit as required including giving necessary connections of the following sizes.2 core 0.75 sq mm | 180 | metre | 67.93 | ₹12,227.4 |
| 1.009 | OD148835/2026-2027:Dismantling G.I. pipes ( external work & internal work ) including excavation and refilling holes after taking out the pipes, manually / by mechanical means (Including Gas cutting machines, )including stacking of pipes within 50 metres lead as per direction of Engineer- in- Charges. | 60 | metre | 71.9 | ₹4,314 |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.04 MB
BOQ_1496629.xls
BOQ • 0.33 MB
mom1MAIN.pdf
Additional Documents • 1.06 MB
viewsbd.pdf
Additional Documents • 1.63 MB
Specificondtionsac-1.pdf
Additional Documents • 0.08 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .