Loading…
Tenderkart now works inside Claude and ChatGPT: search and analyse tenders right from your chat
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹73.6 LAccepted-AOC | L1 | Accepted-AOC L1 | |
| 2 | L2₹78.8 L+₹4.9 L (6.61%)Rejected-Finance | L2 | Rejected-Finance L2 | |
| 3 | L3₹84.8 L+₹10.8 L (14.7%)Rejected-Finance D NO 58 13 74 10 GF 111 VASAVI PARADISE GOWRI NAGAR WARD NO 42 NAD POST VISAKHAPATNAM 530009 AP | VISAKHAPATANAM | ANDHRA PRADESH | 530009 | L3 | Rejected-Finance L3 | |
| 4 | L4₹89.6 L+₹15.6 L (21.2%)Rejected-Finance | L4 | Rejected-Finance L4 | |
| 5 | L5₹97.3 L+₹23.4 L (31.6%)Rejected-Finance | L5 | Rejected-Finance L5 |
Tender Value
₹95.8 L
EMD Value
₹1.7 L
Closing Date
29 Oct 2021, 6:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
CWE AF TRIVANDRUM
CWE AF TRIVANDRUM HQ SAC IAF COMPLEX AKKULAM THURUVIKKAL POST TRIVANDRUM 11
Conversion of overhead lines to under ground lines at AF station Suryalanka
2021_MES_475753_1
CWE(AF)/TVM/SUR/ 82380 E8 conv OHL to UGL
Open Tender
Electrical and Maintenance Works
Item Rate
270 days
Suryalanka
Class C Category b(i)
7 documents required · 7 mandatory
₹1,000
AGE I AF Suryalanka
₹1.7 L
Yes
30 Nov 2021
17 Sept 2021
1 Nov 2021
17 Sept 2021
29 Oct 2021
8 Oct 2021
17 Sept 2021 - 28 Sept 2021
60 days
Amount
SCHEDULE 'A'
M&L for Dismantling concrete poles/ struts, street lights any size including removing of foundation and coping and removing from site complete all as specified and directed
M&L for dismantling of ACSR/AAC conductor of any size and type complete all as specified and directed
M&L for dismantling of insulator any type and size conductor of any size and type complete all as specified and directed
M&L for dismantling of cross arm, channels etc by removing nuts and bolts any type and size complete all as specified and directed
M&L for Dismantling stay assembly complete all as specified and directed
Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of 3.5 core 240 sqmm
All as per Item No.7 above but cable of size 3.5 core 150 sqmm
All as per Item No.7 above but cable of size 3.5 core 70 sqmm
All as per Item No.7 above but cable of size 3.5 core 50 sqmm
All as per Item No.7 above but cable of size 3.5 core 35 sqmm
All as per Item No.7 above but cable of size 3.5 core 25 sqmm
All as per Item No.7 above but cable of size 4.0 core 16 sqmm
All as per Item No.7 above but cable of size 2 core 10 sqmm
All as per Item No.7 above but cable of size 2.0 core 16 sqmm
Supply, installation, commissioning and testing of LT Feeder Pillar Box out door, double door type made out of CRCA Sheet of 3.15 mm thick with powder coated painting frame suitable size for fixing the I/C & O/G MCCB mentioned below made out of angle iron 45 x 45 x 6 mm and four numbers of 400 Amps aluminium strips / bars duly insulated on insulators - 4 Nos / suitable size Bakelite sheet, free space between MCCBs / busbar and other connection items should be provided, the space between ground to panel should be 60 cm with PCC foundation for LT Panel as required, LT panel should be provided with necessary locking arrangement, danger notice sticker, cable glands, internal wiring with FRLS copper wires of suitable size and comprising and including the following (for Near MRS Sub Station): (A) Main Incoming (i) MCCB conforming to IS:13947 (Part-II), IEC-947, TPN (4 pole), 250 Amps, 415 volts, 50 Hz, rupturing capacity 38 KA - 01 No. (ii) LED Multifunctional Panel meter to measure voltage, current, frequency, power factor, kWH, etc with all connected CTs (iii) LED indicating lamps with colour Red, Yellow, Blue (03 Lights) - 01 Set (B) Main Outgoing (i) MCCB conforming to IS:13947 (Part-II), IEC-947, (3 pole), 100 Amps, 415 volts, 50 Hz, rupturing capacity 26 KA - 03 No. (CSD-1, SMC-1 & SNCOs Mess 1) (ii) MCCB conforming to IS:13947 (Part-II), IEC-947, (3 pole), 63 Amps, 415 volts, 50 Hz, rupturing capacity 26 KA - 01 No. (Spare ) (iii) MCB TPN 6-32 Amps, 10 kA, C Curve - 04 Nos (MES complex , street light -2 & Spare ) (iv) Timer for street light with contact - 02 (Main road - 01 & guard room- 01)
Supply, installation, commissioning and testing of LT Feeder Pillar Box out door, double door type made out of CRCA Sheet of 3.15 mm thick with powder coated painting frame suitable size for fixing the I/C & O/G MCCB mentioned below made out of angle iron 45 x 45 x 6 mm and four numbers of 250 Amps aluminium strips / bars duly insulated on insulators - 4 Nos / suitable size Bakelite sheet, free space between MCCBs / busbar and other connection items should be provided, the space between ground to panel should be 60 cm with PCC foundation for LT Panel, LT panel should be provided with necessary locking arrangement, danger notice sticker, cable glands, internal wiring with FRLS copper wires of suitable size and comprising and including the following (OMQ Transformer):_ (A) Main Incoming (i) MCCB conforming to IS:13947 (Part-II), IEC-947, TPN (4 pole), 150 Amps, 415 volts, 50 Hz, rupturing capacity 38 KA - 01 No. (ii) LED Multifunctional Panel meter to measure voltage, current, frequency, power factor, kWH, etc with all connected CTs (iii) LED indicating lamps with colour Red, Yellow, Blue (03 Lights) - 01 Set (B) Main Outgoing (i) MCCB conforming to IS:13947 (Part-II), IEC-947, (3 pole), 125 Amps, 415 volts, 50 Hz, rupturing capacity 25 KA - 02 No. (Offrs Mess & Spare) (ii) MCCB conforming to IS:13947 (Part-II), IEC-947, (3 pole), 100 Amps, 415 volts, 50 Hz, rupturing capacity 25 KA - 01 No. (100 in living) (iii) MCB TPN 6-32 Amps, 10 kA, C Curve - 01 Nos ( Spare)
Supply, installation, commissioning and testing of LT Feeder Pillar Box out door, double door type made out of CRCA Sheet of 3.15 mm thick with powder coated painting frame suitable size for fixing the I/C & O/G MCCBs mentioned below made out of angle iron 45 x 45 x 6 mm and four numbers of 150 Amps aluminium strips / bars duly insulated on insulators - 4 Nos / suitable size Bakelite sheet, free space between MCCBs / busbar and other connection items should be provided, the space between ground to panel should be 60 cm with PCC foundation for LT Panel, LT panel should be provided with necessary locking arrangement, danger notice sticker, cable glands, internal wiring with FRLS copper wires of suitable size and comprising and including the following(OMQ):- (A) Main Incoming (i) MCCB conforming to IS:13947 (Part-II), IEC-947, TPN (4 pole), 100 Amps, 415 volts, 50 Hz, rupturing capacity 25 KA - 01 No. (iii) LED Multifunctional Panel meter to measure voltage, current, frequency, power factor, kWH, etc with all connected CTs (iv) LED indicating lamps with colour Red, Yellow, Blue (03 Lights) - 01 Set (B) Main Outgoing (i) MCCB conforming to IS:13947 (Part-II), IEC-947, (3 pole), 63 Amps, 415 volts, 50 Hz, rupturing capacity 16 KA - 02 No. (Stn House & Bldg No 71) (ii) MCB TP 40 Amps, 16 kA, C Curve - 04 Nos (OMQ bldgs 2 and spare 2) ((iii) Street light timer with contacts - 01 Nos
Supply, installation, commissioning and testing of LT Feeder Pillar Box outdoor, double door type made out of CRCA Sheet of 3.15 mm thick with powder coated painting frame suitable size for fixing the I/C & O/G MCCB mentioned below made out of angle iron 45 x 45 x 6 mm and four numbers of 500 Amps aluminium strips / bars duly insulated on insulators - 4 Nos / suitable size Bakelite sheet, free space between MCCBs / busbar and other connection items should be provided, the space between ground to panel should be 60 cm with PCC foundation for LT Panel as required, LT panel should be provided with necessary locking arrangement, danger notice sticker, cable glands, internal wiring with FRLS copper wires of suitable size and comprising and including the following (for MT Transformer): (A) Main Incoming (i) MCCB conforming to IS:13947 (Part-II), IEC-947, TPN (4 pole), 350Amps, 415 volts, 50 Hz, rupturing capacity 36 KA - 01 No. (ii) LED Multifunctional Panel meter to measure voltage, current, frequency, power factor, kWH, etc with all connected CTs (iii) LED indicating lamps with colour Red, Yellow, Blue (03 Lights) - 01 Set (B) Main Outgoing (i) MCCB conforming to IS:13947 (Part-II), IEC-947, (3 pole), 160 Amps, 415 volts, 50 Hz, rupturing capacity 26 KA - 01 No. (for TRU side connection) (ii) MCCB conforming to IS:13947 (Part-II), IEC-947, (3 pole), 200 Amps, 415 volts, 50 Hz, rupturing capacity 26 KA - 01 No. (Inving 200 ) (iii) MCB TPN 6-32 Amps, 10 kA, C Curve - 04 Nos (for street light & old diary farm & Spare ) (iv) Timer for street light with contact- 02 (street light)
Supply, installation, commissioning and testing of LT Feeder Pillar Box out door, double door type made out of CRCA Sheet of 3.15 mm thick with powder coated painting frame suitable size for fixing the I/C & O/G MCCB mentioned below made out of angle iron 45 x 45 x 6 mm and four numbers of 250 Amps aluminium strips / bars duly insulated on insulators - 4 Nos / suitable size Bakelite sheet, free space between MCCBs / busbar and other connection items should be provided, the space between ground to panel should be 60 cm with PCC foundation for LT Panel, LT panel should be provided with necessary locking arrangement, danger notice sticker, cable glands, internal wiring with FRLS copper wires of suitable size and comprising and including the following (HQ Transformer):_ (A) Main Incoming (i) MCCB conforming to IS:13947 (Part-II), IEC-947, TPN (4 pole), 150 Amps, 415 volts, 50 Hz, rupturing capacity 36 KA - 01 No. (ii) LED Multifunctional Panel meter to measure voltage, current, frequency, power factor, kWH, etc with all connected CTs (iii) LED indicating lamps with colour Red, Yellow, Blue (03 Lights) - 01 Set (B) Main Outgoing (i) MCCB conforming to IS:13947 (Part-II), IEC-947, (3 pole), 63 Amps, 415 volts, 50 Hz, rupturing capacity 26 KA - 04 No. (BSNL Tower, HQ Bldg, IT Complex & Spare 1) (iii) MCB TPN 6-32 Amps, 10 kA, C Curve - 02 Nos ( Armoury & DSC post) (iv) Timer for street light with contact - 01 (street light)
S&F in replacement of LT junction box outdoor, single door of size minimum 1 x 0.6 x 0.6 m (i.e 1 m height, 1 Mtr width and 0.6 mtr depth) or suitable higher size made out of CRCA Sheet of 3.15 mm thick with powder coated painting frame made out of flat iron 45 x 45 x 6 mm and four numbers of 100 Amps aluminium bars duly insulated on insulators / suitable size Bakelite sheet fixed horizontally including making necessary drilling on bus bars for fixing of out going cable upto 50 Sqmm XLPE - 05 Nos with minimum gap as per IE standards and one No MCCB of capacity 63 A, 4 Pole, 415 V 25 KA complete ( free space between MCCB / busbar and other connection items should be provided,) including fixing arrangement on poles at the height upto 1.5 Mtrs by using suitable size of iron flat bracket, nuts & bolts, danger notice sticker, cable glands, internal wiring with FRLS copper wires of suitable size complete all as specified and directed Note for Ser Item No 16 to 21 : 1. Contractor should submit the diagram of LT panels and Jn box for approval of Engr-in-Charge before placing order. 2. The quoted rate including necessary excavation and PCC work for erection of LT Feeder pillar box, gland, thimbles etc complete
Excavation in trenches, in soft/loose soil not exceeding 1.5 m deep and not exceeding 1.5m in wide for laying of cable,RCC Poles/stays and struts etc and getting out including trimming sides and forming bottom surface complete all as specified and as directed.
Returning, filling-in, including spreading, watering and well ramming in layers not exceeding 25 cm thick each, in soft /loose soil complete all as specified.
M & L for sand cushioning to underground cable including punning down of sand in layer complete all as specified and directed. Note :- Punned down thickness shall be measured for payment
M&L for laying common burnt bricks, sub class 'B', of size 230 x 115 x 75 mm in trenches for cable protection complete all as specified and as directed.
M&L Removing excavated material n exc. 50m and depositing where directed at a level n exc. 1.5 m above the starting complete all as specified and directed
M&L for Earthing complete with earth galvanized steel plate electrode 600x600x6mm buried directly in ground earth pit not less than 2.25 mtr below ground level with top edge of the plate not less than 1.5 mtr below ground level, surrounded from all sides with mixture of charcoal and common salt and electrode connected with galvanized earth lead GI strip 32X6 by means of bolts, check nut and washers of GI or steel, GI pipe light grade of 40 mm bore as protection pipe, GI strip of length not more than 7.5 mtr and connected to test point. GI pipe 20mm dia medium grade for watering, funnel with wire mesh, PCC pit and RCC (1:2:4) type B-1 for cover with 8 mm dia bar reinforcement both ways @ 140 c/c including excavation and earth work disposal of surplus soil to a distance not exceeding 50 mtr as shown on electrical plate No 3 of SSR 2009 complete all as specified and as directed.
M&L for Earthing complete with earth galvanized steel plate electrode 600x600x6mm buried directly in ground earth pit not less than 2.25 mtr below ground level with top edge of the plate not less than 1.5 mtr below ground level, surrounded from all sides with mixture of charcoal and common salt and electrode connected with galvanized earth lead 4 mm GI wire by means of bolts, check nut and washers of GI or steel, GI pipe light grade of 25 mm bore as protection pipe, GI strip of length not more than 7.5 mtr and connected to test point. GI pipe 20mm dia medium grade for watering, funnel with wire mesh, PCC pit and RCC (1:2:4) type B-1 for cover with 8 mm dia bar reinforcement both ways @ 140 c/c including excavation and earth work disposal of surplus soil to a distance not exceeding 50 mtr as shown on electrical plate No 3 of SSR 2009 complete all as specified and as directed.
Supply and fix Hot Dip galvanized octagonal poles of hight 7.5 Mtr bottom 130 mm, top 70 mm, 3 mm thick and base plate 200 x 200 x 16 mm including 1 Mtr single arm bracket, M20 x 600 mm J-Type Foundation bolts with zinc coat set of 4 Nos with double nut and double washers and connector 4 pole with MCB 40 Amps 4 pole connector with single pole 10 Amps MCB and suitable for XLPE cable entry upto size of 25 Sqmm Cable lugs complete all as specified and directed. Note : 1. Contractor should submit the diagram of pole with foundation details as per manufacturer recommendation before placing the order for approval of Engr-in-Charge. 2. The poles should withstand the wind pressure upto 120 Km/Hr
Supply and fixing LED street light fitting with and including individual high power 45 watt LED new generation energy saving and environmental friendly long life LED street light made up of pressure die cast alu with secondary optics, suitable for outdoor use IP 66, connected with connecting cable complete all as specified and as directed
Material and labour for re-fixing the dismantled street light from item No 2 including necessary clamps, nuts and bolts, bracket made out of 25 mm (Suitable for fixing of street light ) GI pipe not less than 1.3 Mtrs and bend to shape complete all as specified and directed
S&F in replacement of existing loop in-out junction box with non metallic FRP junction box suitable of size (Appx 350 x 250 x 150) with connector 4 way and including one MCB SP 6 A, 230V along with 2 Nos 'C' Clamps and back clamp made up of 20x3 flat iron and fixing on pole with necessary nuts bolts, washers, 2 Nos PVC cable glands of size not exc 4 core 25 sqmm, Cable lugs as required complete all as specified and as directed.
S&F in replacement of 3 core 1.5 sqmm PVC Insulated and Round Sheathed Multi Core Bright Annealed Bare Copper Conductor Heavy Duty Industrial Cable for Voltage Grade 1100 Volts as per IS: 694:1990 complete including making necessary connection by using proper connecting spares and taking down old unsv cable all as specified and as directed.
Supply and fix cable jointing kit for 1.1 KV grade cable for straight through joint complete with jointing material heat shrink type and accessories suitable for 3.5/core XLPE, armoured, Al conductor cable of size 25 to 70 Sqmm, Indoor/Outdoor type
Supply and fix cable jointing kit for 1.1 KV grade cable for straight through joint complete with jointing material heat shrink type and accessories suitable for 3.5/core XLPE, armoured, Al conductor cable of size 95 to 150 Sqmm, Indoor/Outdoor type
Supply and fix cable jointing kit for 1.1 KV grade cable for straight through joint complete with jointing material heat shrink type and accessories suitable for 3.5/core XLPE, armoured, Al conductor cable of size 185 to 240 Sqmm, Indoor/Outdoor type
Supplying and fixing in replacement of 1100 volts grade heavy duty cable PVC insulated aluminium conductor, served with inner sheathing of PVC tape and overall PVC sheathed in service connections twin core cable flat or circular stranded of size 6 Sqmm including taking down old unsv service cable complete all as specified
Supplying and fixing in replacement of 1100 volts grade heavy duty cable PVC insulated aluminium conductor, served with inner sheathing of PVC tape and overall PVC sheathed in service connections twin core cable flat or circular stranded of size 4 Sqmm including taking down old unsv service cable complete all as specified
Total of Schedule 'A'
Bismi Engineering
G T SERVICES
RMK INDUSTRIES
G V N R CONSTRUCTIONS
V SATYANARAYANA RAJU
Sai Ram Builders
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.PDF
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .