AMRUTA B ADHAV
Hazira Depot, Bharat Petroleum Corporation Limited
TAS CONTROL ROOM UPGRADATION FOR BPCL HAZIRA, MIRAJ AND AKOLNER DEPOT.
2584
1000387143
Single Tender
Works
Hazira Depot
4 Jun 2022
17 May 2022
23 May 2022
17 May 2022
20 May 2022
17 May 2022
18 May 2022 - 19 May 2022
60 days
TAS CONTROL ROOM
UPGRADATION AT BPCL HAZIRA,
MIRAJ AND AKOLNER DEPOT
Upgradation of Hardware and Software items and scope of work shall be as per
a) Upgradation of LRC servers and client PC with latest compatible operating
system with Honeywell EPKS SCADA and Safety builder software.
b) Upgradation of the complete Control Room Hardware such as LRC servers,
workstations, Terminal server and Ethernet switches as mentioned in site wise BOM.
c) Quantity of Hardware such as Servers, Client and EPKS Software features shall
be per existing at site and in detail mentioned in priced BOM.
d) All Graphics, user interfaces of SCADA and LRC applications will be upgraded in
line with new windows server, Windows 10 and EPKS 51x.x version software’s.
e) Successful testing, commissioning and integration of upgraded system with
existing Terminal Automation system installed at site.
f) Additional SAP-TAS PC shall be configured for spare purpose.
DETAILS OF SUPPLY MATERIAL
1) Supply and commissioning of Dell Tower type Server with 16 GB RAM, (4+1)
X300 GB 15K RPM Hard Disk, Single Intel 3.30GHz, and four-core processor
with below specification.(Qty for BPCL Hazira, BPCL Miraj and BPCL Akolner
is mentioned separately )
LRC SERVER SPECIFICATIONS
PARAMETERS Minimum Requirements
2 Model & type Dell Power Edge
3 Processor Intel Xeon E-2124 3.30GHz, four-core processor
5 Form factor Tower type
6 RAM 16GB (2x8GB)
RAID & Hard Disk
7 (4+1) x 300GB, 15K RPM, RAID5 configuration
8 H730p Controller (2GB cache)
9 System bus 1333MHZ FSB or higher
10 CD-R/W Drive DVD RW Drive
11 Graphics Integrated Matrox display controller
NIC Support & Integrated Broadcom 5720 Dual-Port 1Gb
Ethernet ports Network
Operating +10° to +35° C (50° to 95° F)
Storage -40° to +65°C (-40° to 149° F)
14 Operating system Windows 2016/2019 server
15 RAID Diagnostic RAID5 configuration
16 Resolution 1280x1024
Operating 10% to 80% (non-condensing)
17 Relative humidity
Storage 5% to 95% (non-condensing)
Serial 1 Serial 9-pin
18 Built In I/O Ports
LAN 2 RJ45 via Network
Interface Card USB 7 (1 front,
19 I/O Expansion 4 x PCI eGen3 slots
20 Power supply 495 Watt, Dual, Hot-plug, Redundant Power Supply
21 Monitor Minimum 22”
a) New supplied LRC servers will replace existing LRC servers, and the Vendor shall
provide supervision for installation of new supplied server. Physical dismantling of
existing LRC server is considered under BPCL scope of work.
b) The Supplied servers shall be installed in existing consoles and existing power
supply source will be utilized. If any modification required in console to suit the new
servers will be in scope of BPCL.
c) The Vendor shall supervise physical installation of the servers and undertake all
relevant commissioning works for the proposed LRC servers. BPCL shall provide for
the safe and secure storage for servers and loading-unloading services onsite.
2) Supply and commissioning of Dell Tower type Workstation 16 GB RAM, 2 x 1TB,
7.2K RPM, RAID1 Hard disk, Single Intel 3.60GHz, 4-core processor with below
specifications. Qty for BPCL Hazira, BPCL Miraj and BPCL Akolner is
mentioned separately)
Technical Specifications for Client PC’s (OIC/TTES/SAP-TAS)
Parameters Minimum Requirements
2 Model Tower type
3 Quantity As per BOM
4 Processor Intel® Xeon W-2123, 3.6GHz Turbo, 4C
5 Form factor Tower type
6 Chipset Intel Xeon
7 RAM 2x 8 GB DDR4, populated at first slot of each channel.
8 Hard Disk Drive 2 x 1TB, 7.2K RPM hard drive, non-RAID
9 Network 2 No.s PCIe Network Cards supporting FTE
4 available PCIe slots – only for use with the included
10 Expansion Bays
11 I/O Ports USB 10 (4 front, 6 rear)
12 Video Interface Standard Quad display NVIDIA P620
Keyboard: USB Windows compliant
Keyboard/ (equivalent or better) Mouse: USB Dell optical
13 Mouse 2-button w/scroll
(equivalent or better)
14 Optical Drive DVD+/-RW
15 Power Supply Single 950 Watt
16 Min. Windows
17 Monitor Min 22”
a) New supplied client machines shall be installed in place of existing client machines.
Vendor shall install new supplied client machines further dismantling of existing client
machines shall be done by M/s BPCL.
b) Supplied client machines shall be installed by Vendor in existing consoles and
existing power supply source will be utilized. If any modification required in console to
suit the new machines, will be in scope of BPCL.
3) Supply of Experion R5XX package with SCADA points, Windows 2019 Server
for LRC servers, license for flex station, Windows 10 OS for client machines
with documents and license copy. (Qty for BPCL Hazira, BPCL Miraj and BPCL
Akolner is mentioned separately)
Microsoft Windows Server
Microsoft Windows 10 IoT Enterprise LTSC
Microsoft SQL 2019 Runtime CAL
Processor & hardware support is based on the Windows release
Updated archive format and backup engine
SCADA points as per existing license with 20% spare of total used SCADA points at
their respective locations.
Supply of TTES and Tank craft as per latest server platform.
Flex station as per existing EPKS license.
Interfaces licensing as per existing EPKS license.
EPKS OPC classic and UA Client interface.
Experion PKS R5XX Media Kit
MacAfee Antivirus for all server and workstations.
New EPKS release will use Microsoft Windows 10 IoT Enterprise LTSC 2016/19,
Microsoft Windows Server IoT 2016/19, Microsoft Visual Studio 2017 and Microsoft
SQL Server 2019. All of these are an upgrade from the versions being used in existing
DETAILS OF SERVICES
4) Installation and commissioning of LRC and client machines. Supply of
Experion R5XX package with SCADA points, Windows 2019 Server for LRC
servers, license for flex station, Windows 10 OS for client machines With
documents and license copy
Upgradation of both LRC servers and Client machines with latest supplied
Experion package and its component application including
1) SQL Data base
2) SCADA Database and HMI
3) Handing over backup of PLC Logic, LRC reports and HMI
4) Configuration of LRC servers and TTES as per existing format of reports,
TAS-TFMS, SAP-TAS and bay configuration in LRCs and Client machines.
5) Configuration of safety PLC software, logic migration and
implementation.
6) Configuration of Process PLC software, logic migration and
implementation.
7) Migration of HMI, configuration of all reports, alarms and events as per
existing philosophy
NOTE – Vendor shall ensure upgradation of both LRC servers and Client
machines with all functionality available in existing TAS at individual
locations as per BPCL approved FDS and any additional functionality
already implemented at individual location and not limited to above.
Note - Skilled Manpower, safe and secure storage facility, loading and
unloading of material, civil and mechanical work if any for all supplied and
free issue items. Dismantling of existing LRC and client machines under
supervision of Honeywell Engineer
Final Bill of Material/Services
S Hazira Miraj Akolner
Description UOM Total
no Depot Depot Depot
Supply and commissioning
of Dell Tower type Server
with 16 GB RAM, (4+1)
1 X300 GB 15K RPM Hard Ea 2 2 2
Disk, Single Intel 3.30GHz,
and four-core processor as
per scope of work
Supply and commissioning
of Dell Tower type
Workstation 16 GB RAM,
2 x 1TB, 7.2K RPM, RAID1 Ea 6 6 6
Hard disk, Single Intel
3.60GHz, 4-core processor
as per scope of work
Supply of Experion R5XX
package with SCADA
points, Windows
Server for LRC servers,
3 license for flex station, Set 1 1 1
Windows 10 OS for client
machines With documents
and license copy. as per
Upgradation of both LRC
servers and Client machines
with latest supplied Experion
package and it's component
application including.1) SQL
Data base2) SCADA
Database and HMI3) Handing
over backup of PLC Logic,
LRC reports and HMI4)
Configuration of LRC servers
and TTES as per existing
format of reports, TAS-TFMS,
4 SAP-TAS and bay LS 1 1 1
configuration in LRCs and
Client machines.5)
Configuration of safety PLC
software, logic migration and
implementation.6)
Configuration of Process PLC
software, logic migration and
implementation.7) Migration
of HMI, configuration of all
reports, alarms and events as
per existing philosophy.
ADDRESS FOR DELIVERY & CONTACT PERSON FOR EACH LOCATION
BPCL HAZIRA DEPOT
Address: Hazira Co-Op Depot
Bharat Petroleum Corporation Ltd.,
Surat Hazira Road,
P.O. Ichhapore, Surat, Gujarat -
Contact Person Details: Ms. Amruta Adhav
Asst. Manager, Ops
Asst. Manager, Ops (CRI)
BPCL MIRAJ DEPOT
Address: Miraj POL Depot
Bharat Petroleum Corporation Ltd.,
Opp. Railway Goods Shed, Chandanwadi,
Miraj, Dist. – Sangli. Maharashtra-416410
Contact Person Details: Mr. Anil Sasi
Associate Executive Ops. Miraj Depot
Control Room In-charge (CRI)
BPCL AKOLNER DEPOT
Address: Akolner POL Depot,
Bharat Petroleum Corporation Limited
At post: Akolner
Tal and Dist. Ahmednagar
Contact Person Details: Ms. Sudam Khilari
Asst. Manager Ops. Akolner
Control Room In-charge (CRI)
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
RAW_HTML
2584.pdf
pdf • 0.04 MB
BUDGETDOC_2584.pdf
pdf • 0.34 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .